20070201145743.pdf0 �a City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
Fsr sgo (425) 771-0220
DATE: February 1, 2007
TO: David Oskamp
Stevens Healthcare
FAX: 425-640-4443
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check #2007-0057
Project: Stevens Healthcare — Mechanical in Emergency Room
Project Address: 2160176"' Ave W
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where changes can be
found on the plans. Submit 2 sets of revised plans/documents to Marie Harrison, Permit Coordinator.
1. This building is Type IA construction. Provide a building section at the location of the proposed
mechanical work area(s) showing:
a. Number of stories above this floor (cannot tell if it is located in the 1 -story portion of the
building).
b. How the 1 % hour fire rated roof -ceiling and/or 2 hour fire rated floor -ceiling will be
maintained such as with a shaft, etc. IBC 601, 707
c. The location of the exhaust fan outlets in relation to existing building openings and air
intakes.
2. If the mechanical engineer will not be including this requested information on his plans, the plan
addressing item 1 above must be stamped and signed by a State licensed Architect or Professional
Engineer.