Loading...
20070201145743.pdf0 �a City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION Fsr sgo (425) 771-0220 DATE: February 1, 2007 TO: David Oskamp Stevens Healthcare FAX: 425-640-4443 FROM: Ann Bullis, Assistant Building Official RE: Plan Check #2007-0057 Project: Stevens Healthcare — Mechanical in Emergency Room Project Address: 2160176"' Ave W During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Submit 2 sets of revised plans/documents to Marie Harrison, Permit Coordinator. 1. This building is Type IA construction. Provide a building section at the location of the proposed mechanical work area(s) showing: a. Number of stories above this floor (cannot tell if it is located in the 1 -story portion of the building). b. How the 1 % hour fire rated roof -ceiling and/or 2 hour fire rated floor -ceiling will be maintained such as with a shaft, etc. IBC 601, 707 c. The location of the exhaust fan outlets in relation to existing building openings and air intakes. 2. If the mechanical engineer will not be including this requested information on his plans, the plan addressing item 1 above must be stamped and signed by a State licensed Architect or Professional Engineer.