20070202093952.pdfo Eby City of Edmonds -� Q PLAN REVIEW COMMENTS BUILDING DIVISION gst 1 g90 (425) 771-0220 DATE: February 2, 2007 TO: Mary Lou Vigil 18428 74' PI W Edmonds, WA 98026 FROM: Jenny Readwin, Plans E L r RE: Plan Check # 2007-0079 Project: Covered Porch Project Address: 18428 74" PI W During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Pier blocks do not meet conventional construction. Revise plans to 12"x12"x12" poured footings or provide calculations from a Washington State Licensed Professional Engineer to justify pier blocks. 2) All wood exposed to weather must be pressure treated. Specify if posts and exposed framing members are pressure treated. 3) According to the rafter span tables in the International Residential Code the 2x6 rafters at 24" o.c. are over spanned. Add an additional 2x6 in between the existing rafters so the spacing is 12" o.c., upgrade to 2x8 rafters or provide calculations from a Washington State Licensed Professional Engineer. 4) Clarify on the framing plan how the roof is framed around the fireplace at the house. Also note minimum 2" clearance to combustibles is required around masonry wood burning chimneys. 5) On the section detail show flashing where the roof connects to the house. 6) Specify size and spacing of lag bolts attaching roof ledger to the house.