20070205114337.pdfoV EDS City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION �St ago (425) 771-0220 DATE: February 5, 2007 TO: Dean Capps Hartfieldhomes@comcast.net FROM: Jenny Readwin, Plans Ex ner RE: Plan Check 4 2006-1339 Project: Hartfield Homes SFR Project Address: 23521 88th Ave W. During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) 2/5/07 Site plan submitted still does not scale X "=20: Site plan submitted is not legible (can't read the numbers, hard to tell where the property lines are, etc.). Please submit 3 new clear legible site plans scaled no smaller than 1"=20' on no larger than 8 %Z" x 14" paper. 2) 2/5/07 Still need. On the site plan show all bump outs (i.e. fireplace, covered porch, concrete landings/patios, both trellis, etc.). All this information must be clearly labeled on the site plan. 3) 2/5/07 neighbors concrete step can not be used as the datum point. Response states that there is none available. Are there any survey property corner pins? Is the water meter existing? An alternate datum must be chosen or height inspection will need to be done by a Licensed Surveyor.. Please choose alternate datum point. Concrete step is not a specific enough datum point. 4) ok 5) ok 6) ok 7) ok