Loading...
20070308092816.pdf.a..:. City of Edmonds Plan Review Corrections Plan Check #� iv Date'Zool Project Name/Address f DZ Contact Person/Address Department: Building �-' Engineering ❑ Planning ❑ Fire ❑ Public Works ❑ Reviewer Axin1tsi -- -- - Submit 2 sets of revised plans/documents to the Permit Coordinator. ❑ Corrections may be made by red lining plans/documents on file with the City. C DATE - OTAtta.ch fax transmittal) PAGE L OF / FJ1'Ii¢t CITY OF EDMONDS SPECIAL INSPECTION AND TESTING AGREEMENT The project at'1(1l "W'l 1 1 issued under building permit number Zeb -7 -- tj> by requires special inspection and/or testing per IBC Chapter 17. The complete list of special inspections is attached to this document. BEFORE A PERMIT CAN BE ISSUED: The owner and contractor and special inspector shall complete this agreement and the attached structural test(s) and inspections schedule including the required acknowledgements. APPROVAL OF SPECIAL INSPECTORS: Each special inspector shall be approved by the Building Official prior to performing any duties or inspections. Each special inspector shall submit Statement of Qualifications to the Building Official for review_ Special inspectors shall display identification when performing special inspections on site. Special inspection and testing shall meet the minimum requirements of IBC Chapter 17 and the following: A. Duties and Responsibilities of the Special Inspector 1. Observe Work The special inspector shall observe the site work for conformance with the approved (stamped) plans and specifications and applicable workmanship provisions of the IBC. Architect or Engineer reviewed shop drawings may be used only as an aid to inspection. Special Inspections are to be performed on a continuous basis—meaning that the special inspector is on site at all times observing the work requiring special inspection. Periodic inspections, if any, must have prior approval by the City based on a separate written plan reviewed and approved by the Building Official and the engineer or architect of record. 2. Report Non -conforming Items The special inspector shall bring non -conforming items_ to the immediate attention of the contractor and note all such items in the daily field report. Any item not resolved in a timely manner shall be immediate cause of the special inspector to notify the Building Official of the plan deviation, error, change or omission. It shall also be the duty of the special inspector to promptly notify the engineer or architect. 3. Complete Daily Reports Each special inspector shall complete and sign both the special inspection record and the daily report form for each day's inspection. These records shall remain at the jobsite with the contractor for review by the City Building Inspector_ 4. Furnish Weekly Reports The special inspector or inspection agency shall furnish the City with weekly reports of tests and inspections. The project engineer or architect, and others as designated shall also be copied on reports. Weekly reports must include the following: • Description of daily inspections and tests made with applicable locations • List of all non -conforming items • Report on status of non -conforming items (resolved or unresolved) • Itemized changes authorized by the Architect, Engineer and City if not included in non- conformance items. S. Furnish Final Construction Report The special inspector or inspection agency shall submit a final signed report to the City stating that all items requiring special inspection and testing were fulfilled and reported. And, to the best of f.:1TEMP1BUILD1NG1SpeeiallnspectionAgreementlBC_doe 7/04 his/her knowledge the project is in conformance with the approved plans and specifications, approved change orders and the applicable workmanship provisions of the IBC. Items not in conformance or unresolved items or any discrepancies in inspection coverage, (i.e., missed inspections, periodic inspection when continuous inspections were required, etc.) shall be specifically itemized in this report. B. Contractor_ Responsibilities I . Notify the Special Inspector It is the duty of the contractor to notify the special inspector when work is ready for special inspection. Note, the items listed on the attached schedule and as noted on the approved plans and specifications are required to have special inspections. Adequate notice shall be provided by the contractor so that the special inspector has time to become familiar with the project. 2_ Provide Access to Approved Plans The contractor is responsible for providing the special inspector access to approved plans at the jobsite. 3. Retain Special Inspection Records The contractor is responsible to retain at the jobsite all special inspection records submitted by the special inspector. These records are to be provided to the City building inspector upon request. C. City of Edmonds Building Department Responsibilities 1. Approve special inspectors or inspection agencies The building department shall approve all special inspectors and special inspection requirements. 2. Monitor special inspection and approve weekly reports Work requiring special inspection and the performance of special inspectors shall be monitored by the City Building Inspector. llis/Iler approval most be obtained prior to placement of concrete or other similar activities in addition to that of the special inspector. 3. issue Certificate of Occupancy The Building Official way issue a Certificate of Occupancy after all weekly special inspection reports including the final report have been submitted and accepted. D. Owner Responsibilities The project owner or the engineer or architect of record acting as the owner's agent shall fund special inspection services. E. Enjineer or Architect of Record Responsibilities The engineer or architect of record shall include special inspection requirements on the plans and specifications. ACKNOWLEDGEMENTS I have read and agree to comply with the terms and conditions of this agreement. Owner Date Special Inspector Date General Contractor Date City Building Official Date L=ITEMPIBUILDING1SpeciallnspectionAgreement]BC_doc 71134 SPECIAL INSPECTION AND TES'T'ING SCHEDULE REINFORCED CONCRETE, GUNITE, GROUT AND MORTAR: Co"Crese Gunits G" mt Mortar Tcsts v Tests Mix Designs Reinfmcing Placement Bitch Plant kmtuion Cast PRECASTIPRESTRESSED CONCRETE: rw so6r-rem rTly,t� Aggregatc`Cests Reinforcing Tests Tendon Teats Mix Dcsiuns Reinforcing Placement Insm Placemew Concrete Hatching Concrete Placement Instal)a ion Inscprtion Cast Samoks MASONRY: Special InspWim Susses Used — hrliminary Acceptance Tests (Masowv knits. wall Prisms) — Subsequenl Tests (MorLw- Grout. FicM wall Prisms) — Placement Inspection of Units ADDITIONAL INSTRUCTIONS OR OTHER TESTS AND INSPECTIONS: ft7-. o r �o STRUCI`URAL S'MEL/WELDING: — Sample and Test dist spedf c rnembeis below) — Shop Material Identification — weldi€ kVDShop D Field Ultrasonic 1-Pcction O Sb -P O Field — Higb-strength mdug Iospcetim D Shop O Feld DA325 ON Ox OF D A490 Meta) Deck Welding inspection — Reinforcing Steel Welding lwpmkkm — Metal Stud Welding Inspection ____ Concrete Insert Wehiittg )nspecyion FIRFU ROOFING: — Placement Inspection — Density Tests — Thickness Tests — Inspect Batching INSULATING CONCRETE: — Sample and Test — Placement Inspection Unit Weights FILL MATERIAL: — Acceptance Tests Placement Inspection — Field Density STRUCTURAL WOOD: Shear Wall Nailing Inspection — hsspcction of 6111 -jam Fab. — Inspection of Truss Joist Fab - Sample and Test Components Form convicted by-. TckTborr No.: Date_ GSM.. STRUCTURAL TESTS AND SPECIAL INSPECTIONS TABLE 1704.5.3 1 FVFI 7 APF( IAI INCPI"!_TFnm For S1: °C=(°F-32)/1.8. a. The specific standards referenced are those listed in Chapter 35, 1704.11.3 Thickness. The average thickness of the sprayed fire-resistant materials applied to structural elements shall not be less than the thickness required by the approved fire-resistant design. Individual measured thickness, which exceeds the thickness specified in a design by 114 inch (6.4 mm) or more, shall be recorded as the thickness specified in the design plus '14 inch (6.4 mm). For design thicknesses I inch (25 mm) or greater, the minimum allowable individual thickness shall be the design thickness minus '/4 inch (6.4 mm). For design thicknesses less than 1 inch (25 mm), the minimum allowable individual thickness shall be the design thickness minus 25 percent. Thickness shall be determined in accordance with ASTM E 605. Samples of the sprayed fire-resistant materials shall be selected in accordance with Sections 1704.11.3.1 and 1704.11.3.2. 1704.11.3.1 door, roof and wall assemblies. The thick- ness of the sprayed fire-resistant material applied to floor, roof and wall assemblies shall be determined in ac- cordance with ASTM E 605, taking the average of not less than four measurements for each 1,000 square feet (93 mz) of the sprayed area on each floor or part thereof. 1704.11.3.2 Structural ft-aming members. The thickness of the sprayed fire-resistant material applied to structural members shall be determined in accordance with ASTM E 605. Thickness testing shall be performed on not less than 25 percent of the structural members on each floor. 352 2003 INTERNATIONAL BUILDING CODE® FREQUENCY OF INSPECTION REFERENCE FOR CRITERIA Continuous Periodically ACI 5301 ACI 530.1/ during task during task IBC ASCE 51 ASCE 61 INSPECTION TASK listed listed section TMS 4028 TMS 6112a 1. From the beginning of masonry construction, the following shall be verified to ensure compliance: a. Proportions of site -prepared mortar, grout and prestressing grout for bonded tendons. T X Art. 2.6A b_ Placement of masonry units and construction of mortar joints. — X — — Art. 3.313 c_ Placement of reinforcement, connectors and Art. 3.4, prestressing tendons and anchorages. X Sec. 1. l2 3.6A d. Grout space prior to grouting. X — — Art. 3.21) e. Placement of grout. X — — Art. 3.5 f. Placement of prestressing grout_ X — — — Art. 3.6C 2. The inspection program shall verify: a. Size and location of structural elements. — X – Art. 3.3G b_ Type, size and location of anchors, including other details of anchorage of masonry to X — — Sec. 1.2.2(e}, — structural members, frames or other construction. 2.1.413.1.6 c. Specified size, grade and type of reinforcement. X — Sec. 1.12 Art. 2.4, 3.4 d. Welding of reinforement. X — — Sec. 2.1,10.6.2, 3.2.3.4(b) e. Protection of masonry during cold weather (temperature below 40°F) or hot weather — X Sec. 2104.3, — Art. LSC, (temperature above 90aF). 2104.4 1.$1) £ Application and measurement of prestressing force. X — — Art. 3.613 3. Preparation of any required grout specimens, mortarX Sec_ 2105.2.2, specimens and/or prisms shall be observed. _ 2105.3 Art. 1.4 4. Compliance with required inspection provisions of the construction documents and the approved submittals — X — — Art. 1.5 shall be verified. For S1: °C=(°F-32)/1.8. a. The specific standards referenced are those listed in Chapter 35, 1704.11.3 Thickness. The average thickness of the sprayed fire-resistant materials applied to structural elements shall not be less than the thickness required by the approved fire-resistant design. Individual measured thickness, which exceeds the thickness specified in a design by 114 inch (6.4 mm) or more, shall be recorded as the thickness specified in the design plus '14 inch (6.4 mm). For design thicknesses I inch (25 mm) or greater, the minimum allowable individual thickness shall be the design thickness minus '/4 inch (6.4 mm). For design thicknesses less than 1 inch (25 mm), the minimum allowable individual thickness shall be the design thickness minus 25 percent. Thickness shall be determined in accordance with ASTM E 605. Samples of the sprayed fire-resistant materials shall be selected in accordance with Sections 1704.11.3.1 and 1704.11.3.2. 1704.11.3.1 door, roof and wall assemblies. The thick- ness of the sprayed fire-resistant material applied to floor, roof and wall assemblies shall be determined in ac- cordance with ASTM E 605, taking the average of not less than four measurements for each 1,000 square feet (93 mz) of the sprayed area on each floor or part thereof. 1704.11.3.2 Structural ft-aming members. The thickness of the sprayed fire-resistant material applied to structural members shall be determined in accordance with ASTM E 605. Thickness testing shall be performed on not less than 25 percent of the structural members on each floor. 352 2003 INTERNATIONAL BUILDING CODE®