Loading...
20070312135714.pdfa ED City of Edmonds o PLAN REVIEW COMMENTS BUILDING DIVISION Est. 1 s9° (425) 771-0220 DATE: March 12, 2007 TO: Charlie Nathan Nathan Construction FAX: 425-771-7105 Dennis Christianson Christianson Design Research Sent vial e-mail: christianson_dennis yahoo.com FROM: Ann Bullis, Assistant Building Official RE: Revision to Permit #2006-0412 Project: Employee Benefits of America Revisions Project Address: 22817 102nd Place West During review of the revised plans/documents for the above noted project, it was found that the following information, clarifications or changes are still needed. Please refer to attached letter from the Building Official dated 2128/07 and one additional item from 2123/07 Building Division plan review comments. Please submit the followine outstandina items to Marie Harrison. Permit Coordinator: 1. As -built Civil Plans (3 copies) to scale. 2. Special Inspection reports for the North stair: reinforcement, welding, epoxy anchors, structural observation per IBC 1704.3. 3. As -built shop drawings for North stair (with structural engineer's review stamp and approval). 4. Provide one revised reduced site plan no larger than 8 % x 14 for microfilming with the permit. Comments regarding revised site plan „submitted March 1, 2007: The revised site plan must fully replace the original approved site plan. A comparison was done and it was found that the following information must still be provided on the revised site plan. Please resubmit 3 copies of the full size site plan, and one copy of the reduced site plan (maximum size 8 %2 xl4): 5. North arrow. 6. Height calculations, including corner elevations and datum point used in height calculations. 7. Cantilever at offices 217 and 221. 8. Two balconies at north side of building. 9. Label trash enclosure area. 10. Label concrete walkways and driveway asphalt paving. 4"2 C. 1 S 9 1v CITY OF EDMONDS 121 STH AVENUE NORTH - EDMONDS. WA 98020 - (425) 771-0220 • FAX (425} 771-0221 Website: www.ct.edmonds.wa.us DEVELOPMENT SERVICES DEPARTMENT Planning • Building • Engineering Mr. Charlie Nathan Nathan Construction 9792 Edmonds Way, PMB 266 Edmonds, Washington 98026 GARY HAAKENSON MAYOR February 28, 2007 RE: EB of A Building @ 22817 102nd Place West, Edmonds (Permit 92006-0412) Dear Mr. Nathan, The City is prepared to grant Temporary Occupancy on the EB of A Building at 22817 102nd Place West in Edmonds for a period not to exceed 60 calendar days. The following outstanding items shall be completely resolved by this timeframe or occupancy of the building shall be jeopardized: • As -built North Elevation View (2 copies) -- 5Q1a$M%►�7 2-)ZE3/0? • As -built Site Plan (3 copies) to scale - 5V3M%Tir�j> 4-�x-8/07 • As -built Civil Plans (3 copies) to scale— NOT- 'VP_T'0LaMITTUV • As -built Landscape Plan (3 copies) to scale--50J3M%T C-1> -2-f 27%a7 • Respond in writing to Planning Correction dated 2126/07 (copy enclosed) with regard to the east wall. If the Planning Division requires additional aesthetic work on this wall it shall be completed within the timeframe of the temporary occupancy. - 5VrrMtT'TC�� Z/241/0-7 • Special Inspection reports for North stair: e€rs, reinforcement, welding, epoxy anchors, and structural observation per IBC 1704.3. -- HOT- VaT- S v131�1►T1"ED • Structural calculations for North stair piers -- Svi�M 1TI•G-`P> =>/,& r4 "7 • As -built shop drawings for North stair --- NoT - YET 50W WTTC--i-7 • Installation of Illuminated Sign with Braille for North stair Assisted Rescue -- 570031F-cT" `ID F1 EQ> f 0s/42%GT'r ao o 0-1 "M M `I I LV" 1G -r Ar- r1NA_t�- 1W5e_n rV' The City strongly encourages you to immediately submit all outstanding items. Be advised additional plan revision review fees shall be charged for the review of these materials. Sincerely, Jeannine L. Graf Building Official Cc: EB of A building owner. CT Engineering MTC Dennis Christensen, AIA CG Engineering • Incorporated August 11, 1890 • Sister City - Hekinan, Japan } oI E1)Ar City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION Fsr. t gqo (425) 771-0220 DATE: February 23, 2007 SEE terr6Z 14PU 14 T- bi;AF TO: Dennis Christianson Christianson Design Research f7 S t �'� () , 2610 204t4 Street S.W. Lynnwood, WA 98036 Also Sent vial e-mail: christianson dennisn ahaa.com FROM: Ann Bullis, Assistant Building Official RE: Revision to Permit #2006-0412 Project: Employee Benefits of America — Revision to site plan and north garage exit Project Address: 22817 102"d Place West During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Submit 3 sets of revised plans/documents to Marie Harrison, Permit Coordinator. Revised Civil and Etft&eaff plans still have not been submittedfor City review and approval as previously noted in City correspondence to you dated 1/29/07, 1/30/07, 2/1/07, and 2/9/07. *e� r- ----Ul TL MU to r re iew .2"' Provide structural calculation for piers and note minimum soil bearing pressure in structural notes. �! Page 9 of the structural calculations notes "depth of the pier per geotech", however Geo Group NW field report dated 2/16/07 noted that they had not observed the depth and subgrade of the piers that had already been installed. Provide special inspection report from Geo Group NW addressing these issues and verifying soil bearing pressure per the structural design. 4 The City Building Inspector did not inspect reinforcement installation prior to pour. Provide field re by the Special Inspector for the reinforcement installation. port ,,6' Provide a floor plan of the stairway and partial inside of the garage showing compliance with IBC 1007.2 exception #2 and 1007.8 for Exterior Area For Assisted Rescue and stairway construction plan that the shop drawings were prepared from (stamped and signed by Architect): a. On the building floor plans, the door swings out. Show the wheelchair route of travel to the wheelchair space. The wheelchair is not permitted to obstruct the exit path of travel. b. Show the location of the exit door and swing of the door. Dimension the distance from the door in the open (90°) position to the north guardrail. c_ Dimension the distance from the door opening to the top stair nosing. d. Dimension 30"x48" wheelchair space (IBC 1007.6. 1) e. Dimension the minimum 48" clear width between handrails (IBC 1007.8.2) f_ The door must be 3/, hour fire rated. g• Show identification requirements for the Exterior Area For Assisted Rescue: Illuminated sign with Braille meeting ICC/ANSI A 117.1 section 703 (copy enclosed for your use) mounted on the wall adjacent to the latch side of the door (on the inside of the garage) that states EXTERIOR AREA FOR ASSISTED RESCUE. r h. Both stairway handrails must be continuous and 34" minimum to 38" minimum above the stair nosing measured vertically to the top of the handrail. The shop drawings do not show this. i. Both stairway handrails must extend a minimum of 12" beyond the top and bottom of the stairway. The shop drawipgs do not show this. j_ Dimension the spacing bei'Ween intermediate rails (must be spaced so that a 4" sphere cannot pass through). The shop drawings do not clearly show that this is being met. k. Note the required loads for the guardrail/handrail per IBC 1607.7. The shop drawings do not show that this is met. 60 Submit revise shop drawings addressing the applicable corrections above. Submit a revised north elevation view of the stair, rockery, etc. The partial elevation view submitted 219/07 does not match the stair in the shop drawings, only shows part of the building, and is on paper over 4 feet long which is too long to microfilm for archive purposes. Please revise and resubmit. Special inspection is required for epoxy anchor installation and welding_ We will assume MTC (Materials Testing & Consulting) will be doing the special inspections. If they will not be doing the special inspections, contact Marie Harrison for a new Special Inspection and Testing Agreement form (must be submitted prior to the issuance of the revision). 0 Provide one revised reduced site plan no larger than 8 %z" x 14". Page 2 of 2