Loading...
20070313094429.pdfor E� City of Edmonds F d PLAN REVIEW COMMENTS BUILDING DIVISION (425)771-0220 DATE: March 13, 2007 TO: Ralph Eaton FAX: 425-672-2827 FROM: Ann Bullis, Assistant Building Official RE: Plan Check 42007-0139 Project: Driftwood Players. --Covered storage addition Project Address: 950 Main Street During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide these comments to the Architect of Record and have him revise the plans and provide written responses to each comment. Submit revised plans/documents to Marie Harrison, Permit Coordinator. 1. Note the building Type of Construction (VA) and occupancy (Al) on the plans. 2. Archived plans show this building as Type VA (1 -hour) Construction. The addition must also be Type VA Construction including 1 -hour fire rated columns, beams, and roof -ceiling. Provide listed and tested 1 -hour fire rated assembly details for each and cross-reference where they apply on the plans. 3. Provide details showing how the fire rated materials will be protected from exposure to weather. 4. Provide footing information, including size and depth below grade, soil bearing pressure, etc. 5. Provide roof snow load (Edmonds is 25 lb ground snow load). 6. The siding and existing gypsum sheathing will need to be removed/altered at the ledger — clearly show this on the detail, including flashing. 7. Provide beam calculation to verify 4x4 beam and dimension the span on the plans. 8. Revise proposed joist hanger to accommodate proposed 2x4 rafters (the LUS proposed is for 2x8 rafters). 9. Note on the section detail if the floor of the covered structure will be left dirt or will be another material. 10. All wood exposed to weather or in contact with concrete must be pressure treated or naturally resistant to decay.