PLAN REVIEW COMMENTS
BUILDING DIVISION
�sr, 1s9° (425)771-0220
DATE: March 29, 2007
TO: Jose Cadiz
cadizgc@earthlink.net
FROM: Jenny Readwin, Plans Ex ine
RE: Plan Check # 2007-0228
Project: Huyer Addition/Remodel
Project Address: 7824 203' St. SW
During re -review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) 3/29/07 Site plan still does not show setbacks to proposed addition. Please dimension this on
the site plan. Also, still need copy on 8'/"x 14" or smaller paper and scaled no smaller than
1"--20'. Please provide. Site plan does not have all minimum submittal requirements
(topography, water/sewer/gas lines, setbacks to proposed addition, etc.). See attached sample
site plan for minimum submittal requirements. Please submit three (3) new site plans scaled no
smaller than 1"=20' on 8 1/2 x 14 paper. Also, per email from JoAnne Zulauf, Permit
Coordinator dated February 26th the height calculations points need to be revised to include
garage now that it is being attached by the new addition. Please revise height calculations
accordingly.
2) ok
3) ok
4) 3/29/07 Note on plans says replace beam in attic as needed. Please specify size of beam and
provide calculations. This is not something our building inspector checks in the field. It must
be reviewed during plan review. Also, clearly show how all loads through the over framed
area are being carried to hearing. Provide a complete roof framing plan including the existing
house to verify that proposed wall to be removed is non-bearing. Also, note garage framing and
how the addition will be tied in.
5) ok
6) ok
7) ok.
8) ok
9) ok
10) ok
11) ok
12) ok
13) ok