City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
Tom Leren
tom@lerendesign.com
s�
Jenny Readwin, Plans Ex mine ,
Plan Check # 2007.0401
Project: Treiber Addition
Project Address: 923 Pine Street
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Note garage/dwelling separation on plans. Minimum I/2" sheetrock required on garage side of
wall and 5/8" type X on the ceiling when there is habitable space above and minimum 20 minute
rated or 13/8" solid core door.
2) It appears that there will be a site built shower. Provide shower pan construction detail including
materials, drain, slope, etc.
3) Specify cfm of bath fan on the floor plan (50 cfin minimum).
4) Provide calculations to justify that larger posts and/or footings are not required on the existing
exterior wall size of FB3 (5 %2' x 18" GLB),
5) Sheet 3 calls out details A/4, B/4 and C/4 but these details are not on sheet 4. I believe they
should be A/3, B/3 and C/3. Please clarify and correct as necessary.
f) Sheet 3 calls out B/3 on the foundation plans but detail B on this page does not apply to this
area. Please coordinate all details.