20070503115414.pdfDATE: May 3, 2007 TO: FROM: 0 City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 Tom Leren tom@lerendesign.com s� Jenny Readwin, Plans Ex mine , Plan Check # 2007.0401 Project: Treiber Addition Project Address: 923 Pine Street During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Note garage/dwelling separation on plans. Minimum I/2" sheetrock required on garage side of wall and 5/8" type X on the ceiling when there is habitable space above and minimum 20 minute rated or 13/8" solid core door. 2) It appears that there will be a site built shower. Provide shower pan construction detail including materials, drain, slope, etc. 3) Specify cfm of bath fan on the floor plan (50 cfin minimum). 4) Provide calculations to justify that larger posts and/or footings are not required on the existing exterior wall size of FB3 (5 %2' x 18" GLB), 5) Sheet 3 calls out details A/4, B/4 and C/4 but these details are not on sheet 4. I believe they should be A/3, B/3 and C/3. Please clarify and correct as necessary. f) Sheet 3 calls out B/3 on the foundation plans but detail B on this page does not apply to this area. Please coordinate all details.