PLAN REVIEW COMMENTS
- BUILDING DIVISION
Fst 1g90 (425) 771-0220
DATE: May 10, 2007
TO: Michael Nelson
miken@gpaving.com
FROM: Jenny Readwin, Plans Ex ine
RE: Plan Check # 2007-0423
Project: Addition
Project Address: 10607 226th Street SW
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Cross reference all details on sheet S to their location on the plans. Cross out any details that do
not apply to this house.
2) 8403.1.3 requires all vertical rebar to have a standard hook. Revise all applicable foundation
details on sheet S to reflect.
3) On the post/beam detail on sheet 5 the past -to -footing connector must be visible to the inspector
in order to verify. Please revise detail to show visible post -to -footing connector.
4) On the floor plan show minimum 36" hard surface landing outside garage man door.