20070606115534.pdfOV EDr►�o Al �sr. tai° City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425)771-0220 DATE: June 6, 2007 TO: Manijeh Fahim Talebinia 8830 Main. Street Edmonds, WA 98026 FROM: Jenny Readwin,. Plans Ex 'ne RE: Plan Check # 2007-0388 Project: Talebina Garage Remodel for Salon Project Address: 8830 Main Street During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) 6/6/07 Still need %"sheetrock noted on the garage side of the wall. Note garage/dwelling separation on plans. Minimum %" sheetrock required on garage side of wall and minimum 20 minute rated or 13/8" solid core door between the garage and salon. 2) 6/6/07 Received Lighting Summary but Still need Envelope Summary. Complete the enclosed Envelope and Lighting Summary worksheets attached. The proposed room remodel does not appear to meet the minimum insulation R -Values. If they can not be met then a component performance analysis will be required. You may need to seek help from a design professional for completing a component performance analysis if required. 3) ok 4) opk 5) ok 6) 6/6/07Please show landing and any walkways on the site plan. On the site plan also show area of room in garage. Minimum 36" x 36" hard surface landing is required outside the exit door. Please not on plans. 7) ok 8) ok 2004 Washington State Nonresidential Energy Code Compliance Form EnSummary Climate Zone I B velope 2064 Washington Stale Nonresidential Energy Code compliance Forms - Revised May 2005 PrOjeCt1D Project Address Date Total Glazing Area Electronic version: these values are automatically taken from ENV--UA-1. Glazing Area Calculation Note: Below grade walls may be included in the For Building Department Use X 100 = Appfcant Name: Applicant Address: Applicant Phone. Project Description =New Building 0 Addition ❑ Alteration ❑ Change of Use F] Prescriptive ❑ Component Performance ❑ Systems Analysis Compliance Option (See Decision Flowchart (over) for qualifications) Space Heat Type 0 Electric resistance O All other (see over for definitions) Total Glazing Area Electronic version: these values are automatically taken from ENV--UA-1. Glazing Area Calculation Note: Below grade walls may be included in the (rough opening) Gross Exterior (vertical & overhd) divided by Wali Area times 100 equals %6 Glazing X 100 = Gross Exterior Wall Area if they are insulated to the level required for opaque walls. Concrete/Masonry Option Q yes Check here if using this option and if project meets all requirements for the Concretelblasonry Option. See Decision Flowchart (over) for qualifications_ Enter requirements for earth qualifying d no assembly below. Envelope Requirements (enter values as applicable) Fully heated/cooled space Minimum Insulation R -values Roofs Over Attic Ail Other Roofs Opaque Wallsl Below Grade Walls Floors Over Unconditioned Space Slabs -ori -Grade Radiant Floors Maximum U -factors Opaque Doors Vertical Glazing Overhead Glazing Maximum SHGC (or SC) Vertical/Overhead Glazing Semi -heated space 2 Minimum lnsulaSon R -values Roofs Over Semi -Heated Spaces 1- Assemblies with metal framing must comply with overall U -factors 2. Refer to Section 1310 for qualifications and requirements Notes: Opaque Concrete/Masonry Wall Requirements Wall Maximum U -factor is 0.15 (R5.7 continuous ins) CMU block walls with insulated cores comply If project qualifies for Concrete/Masonry Option, list walls with HC 2 9.0 Btulft -"F below (other watts must meet Opaque Wall requirements)_ Use descriptions and values from Table 10-9 in the Code. 'Wall description U -factor ;(including insulation R -value & position) 2004 Washington State Nonresidential Energy Code Compliance Form Uf1MlRtiifLill= State Nonresidential Energy Code Revised May 2006 Decision Flowchart Use this flowchart to determine if project qualifies for the optional Prescriptive Option. for Prescriptive Option if not, either the Component Performance or Systems Analysis Options must be used. 1302 Space Heat Type- For the purpose of determining bugding envelope requirements, the following two categories comprise all space heating types: Other_ All otherspace healing systems Including gas, solid fuel, all, and propane space heating systems and those systems fisted in the exception to electric resistance- (confined at right) All Insulation Installed? Mass Walt -No- N Criteria OK? N (below) Yes Mass Wall Insulation Req_ Mass Wall U0,15IR5.76 CMU Block ins. Cares Wood Frame R19 Metal Framed Rtg No Electric Resistance: apace n061ing systems wn= use %ewc resiswnce START elements as the primary heating system including baseboard, radiant, and forced air units where the total electric resistance heal capauty exceeds 1.0 Witt' of the gross conditioned floor area. Exception: Heat pumps and terminal electric reaislanm hearing In yanable air volume distribution systems. Sectric Resistance Ye Heat? All insulation Installed? Below Grd Wall (ext) R-10 Wood Metal Below Grd Wall (cth) R-19 R-10 Below Grd Wall (oth) Roofl3VefAttiC R-30 Roof Over Attic R-38 All Other Roof R-21 R-30 U-.0.034 Raised f=loor R-19 U-0.029 Slab -On -Grade Slab -On -Grade R-10 Radiant Floor R-10 Radiant Floor R-10 Opaque Door U-0-60 Mass Walt -No- N Criteria OK? N (below) Yes Mass Wall Insulation Req_ Mass Wall U0,15IR5.76 CMU Block ins. Cares Wood Frame R19 Metal Framed Rtg No Electric Resistance: apace n061ing systems wn= use %ewc resiswnce START elements as the primary heating system including baseboard, radiant, and forced air units where the total electric resistance heal capauty exceeds 1.0 Witt' of the gross conditioned floor area. Exception: Heat pumps and terminal electric reaislanm hearing In yanable air volume distribution systems. Sectric Resistance Ye Heat? All insulation Installed? Wall Heat Capacity (HC) Assembly Description Assy.Tag Wood Metal Below Grd Wall (ext) R-10 R-10 Below Grd Wall (oth) R-19 U-0.002 Roof Over Attic R-38 U-0.031 Alt Other Roof R-30 U-.0.034 Raised Floor R-30 U-0.029 Slab -On -Grade R-10 R-10 Radiant Floor R-10 R-io Above Grade WaII R Mass Wall Wail Rib wood, or —N Criteria OK? NO - 0.062 m (below) Yes Yes Yes Mass Wall Insulation Req. Mass Wali U0.15IR5.7ci Yes Yew_ CMU Block Ins. Cores Wood Frame Rig ir Metal Framed U0.062 Glazing Criteria Met? Glazing Criteria Met? Glazing Vest OH Glazing Vert OH No Area % UVat UVal SHGC Area % UVal UVal SHGC 0-30% 0,55 0.70 0-45 4-30% 0-40 0.60 0.40 30-45% 0.45 0.60 0.40 X30 Not Allowed X45% Not Allowed No Yes Prescriptive �s Na Path Allowed Component Performance or Systems Analysis Required Concrete/MasaOption* Wall Heat Capacity (HC) Assembly Description Assy.Tag HC*` Area (sf) HC x Area *If the area weighted heat capacity (tic) of the total above grade wall is a minimum of 9.0, the Concrete Masonry Caption may be used. —For framed wails, assume FIC=1A unless calculations are provided; for all other thralls use Totals Section 1009. Area weighted HC- divide total of (HC x area) by Total Area 2004 Washington State Nonresidential Energy Code Compliance Form 2004 Washington State [•lonresidentia[ Enargy Code Compliance Fame Revtsed May 2905 Project Address Date Space Heat Type Q Plectdcresistance 0 AM other For Building Department Use Glazing Area as %g gross exterior wall area Prop. Max -Target Concrete/Masonry Option Q Yes O No Notes: If glazing area exceeds maximum allowed in Table, then calculate adjusted areas on back (over). Building Component Proposed UA Target UA List components by assembly ID & page # U factor x Area (A = UA (U x A) U -factor x Area A) = UA (U x A) U= Plan ID: U= Plan 113- - 3fzir�IctraltsLr:tbtlear3�g C' U= Plan ID. s3,r�` L I.. C N U= Plan ID: J 0 U= Plan ID: s U= Plan ID: U= Plan ID: U= Plan ID: a' c Q U= Plan ID: �: apt t er t M �� (tyiu U= Plan ID: _ :E � } - d U= Plan ID:"l�b S C U= Plan ID:�•- i U= Plan ID: >�r� A,•�:tiz=rte :,_,.-'>.,,a;rT:T. Plan ID; ' -- _ -::.:: - ;- ; ar; O U= Plan ID: U= Plan ID: M o U= Plan ID: _--trst5Qpi- o U= Plan ID: u R-- Plan ID: R= Plan ID: = '_. _ i3sis'..Irtefri9 R= Plan ID:.. � -S)'� s,n s� p R= Plan ID :iiz!j'.ia...riir:sE°=':�T'f�"i`�Ci:... .._i_:S"F:...-.-i•'"O' �•%t'c:9�f:i Do tr R= Plan ID: :a31'���-i.r,�x4xc:;M �.•.:...-.....:w.. .n^u :zuc5:.ra..' R= Plan ID-- D:R= R=Plan ID-- D:R= R=Plan ID: ** R= Plan ID: iu - t R= Plan ID:cr Q. 0 R= Plan ID-- D:p R= Plan ID: "Note: sum of Target Areas here should uaI Target Opaque Wall Area see back a'cs"�:nes'�;�" rte,' `Y•`',e'?�� mri�x._ea�y%+?358i R= Plan ID: o v a n R= Plan ID: eft' k R= Plan ID: n - Note: If insulated to levels required for opaque walls, list above with opaque walls -c R= Plan ID: Z5 c c 'b R= Plan ID: Q R= Plan 10: R= Plan ED. R= Plan ID: n A 2 a R= Plan ID: o R= Plan ID.gg R= Plan ED.re CiY31afoF z 4??)4?a. .For CMU walls, indicate core insulation material. Total Totals 10 6omply: 1) Proposed -total UA shall not exceed Target Total UA. 2) Proposed Total Area shall equal Target Total Area. 2004 Form Glazing Proposed SHGC Target SHGC List components by assembly ID & page 9 SH(3C' x Area (A) = SHGC x A SHGC x Area (A) = SHGC x A 1D: Glazing Area OG= OG= IE]: VG= _i5nt�iss CD Note: OG = overhead glazing Opaque Areal IVG ID: V - vertical glazing Gross Exterior Watl Max Glazing Area .-. qv _.� _tet. •�-�•eaM1:':"fltyA.=iSx, .�_ L�.+P�h,. ID- - Glazing Area Target OG Area in Roots over Atlics Target OG Area in Other Roots Max OG Remaining blesser lesser = `Note: Manufacturers SC maybe used in lieu of SHGC. below. Proposed Opaque Area Proposed OG Area Target OG Area Totals Roofs over Attics Totals For compliance: Proposed total SHGC x A shall not exceed Target total SHGC x A NOTE: Since 1997 SHGC compliance for vertical and overhead'glazing is allowed to be calculated together_ If the total amount of glazing area as a % of gross exterior wall area (calculated on ENV--SUM7) exceeds the maximum allowed in Table 13-1, then this calculation must be submitted Use the resulting areas in the Target UA and SHGC calculations above. . Proposed Areas: Numbered values are used in calculations below. Roofs over Attics Omer Roofs Walls Glazing Area OG= OG= VG= Note: OG = overhead glazing Opaque Areal IVG - vertical glazing Gross Exterior Watl Max Glazing Area Maxim um Target Area (Table 13-1) - Glazing Area Target OG Area in Roots over Atlics Target OG Area in Other Roots Max OG Remaining blesser lesser = Target VG Area For Targgt OG's, the qui lesser values are - - - = used bath here and below. Proposed Opaque Area Proposed OG Area Target OG Area Target Opaque Area Roofs over Attics Other Roofsiz'"'` Proposed Opaque Area Proposed VG Area Target VG Area Target Opaque Area Walls I f E- I _ Target Areas OK Note: If there is more than one type of wall. the Target VG Area may be distributed among them, and separate TargetOpaqueAreas found. If the Target Areas for Opaque Walls listed on the front must equal the total calculated here_ Target Values in shaded twxes are used in the applicable Target UA calculations an the front. Target VG Area and Total Target OG Area are also used in the applicable Target SHGC calculations above.