Loading...
20070613114429.pdfDATE: June 13, 2007 City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425)771-0220 TO: David Oskamp doskamp@stevenshealthcare.org FROM: Ann Bullis, Assistant Building Official RE: Plan Check #20 07-0 3 8 0 Project: Interior remodel of surgery floor (basement) locker rooms Project Address: 2160176' Ave W During re -review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Please submit revised plans/documents to Marie Harrison, Permit Coordinator. 9 3. 4. Previous item 7 not addressed: The accessible route of travel is required throughout the remodeled areas, including but not limited to restrooms, locker rooms, showers, maneuvering distances, etc. Provide details showing compliance and cross-reference where they apply on the plans. Previous item 8 not provided: Provide the I -hour listed and tested assembly reference number for partition type 01 on Sheet A2.01. Include all assembly construction requirements. Previous item 9: New detail 4/A2.01 does not show the location or fire rating of the fire rated floor - ceiling assembly. As noted previously, if the ceiling grid is part of the fire rated assembly, the soffit (as well as other penetrations such as headers) must maintain the fire rating of the floor -ceiling assembly. If the fire rated floor ceiling assembly is above the soffiticeiling grid area, clearly show this on the plans. The demolition plans also notes that ceiling tiles will be replaced, so the determination of whether the ceiling grid system is part of the fire rated floor -ceiling assembly is very important and is the architect's responsibility to clearly show on the plans. Previous item 10 was not addressed. The alteration work is not exempt from IBC/WAC 3409.6. If the architect chooses to use exception #1 of that section, as noted previously, provide a letter stamped and signed by the architect (reference the code exception), stating what parts of the existing site and building are not accessible, the project cost and what 20% of it equals, list the upgrades that will be done as part of this permit as well as showing that the total cost of the upgrades is at least 20%.