Loading...
20070621081512.pdfDATE: June 21, 2007 City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 TO: Shawn Leiser Fax 206-533-6038 FROM: Jenny Readwin, Plans Exmi RE: Plan Check ## 2006-1384 Project: Walnut St Condo (Duplex) Project Address: 301 Walnut St. During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) ok. 2) ok 3) ok 4) a) South stair enclosure: i) ok ii) ok iii) ok b) ok c) ok d) Elevator shaft: i) ok ii) 6121107 Show 60 minute rated door at the lower floor like what is shown on the main floor. Provide manufacturer's specifications for the specific elevator to be installed. If the elevator is not provided with minimum 1 -hour fire rated hoistway doors at each opening, self-closing 1 - hour fire rated doors are required at each wall opening in the elevator shaft to maintain the required shaft rating. e) 6/21107 This information can not be deferred. Please show location of equipment room. You should talk to Labor and Industries about elevator equipment room requirements now so you can design it per their requirements to avoid future location problems. This all needs to be shown on the plans. Show the location of the elevator equipment room on the floor plans. Ventilation (supply and exhaust) will be required to maintain the required operating temperature specified in the manufacturer's information. Show the location of supply and exhaust air. If penetrations are made in the 1 -hour rated assemblies, shown how the fire rated assembly will be maintained, such as with gypsum lined joist bays, shafts, etc. 5) ok 6) ok 7) ok 8) ok 9) ok 10) 6/2I/07See attached additional Comments. See attached structural comments from city consultant. Respond to each item in writing. Eagle Eye Consulting Engineers, P.S. PO Sox 523 Olalla, WA 98359 hoytjeter@centurytel.net 360 874 0562 UO Fax 360 874 0591 To, Theresa Umbaugh 121 5th Avenue N Edmonds, WA 98020 Re: Gallaugher Duplex June 1, 2007 301 Walnixt Street Edmonds, WA 98020 Plan Review # 2006-1384 EECE # EDM 07-02 (2) Second comment letter Structure Area S.F. Lower floor 674 - Main floor 1620 Upper floor 1620 Total 3914 Garage 571 Total 4485 eck Upper floor 50 rand total 4535 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the Structural requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. Page 2 of 3 EECE#: EDM 07-02 (2) Gallaugher Duplex (2006-1384) STRUCTURAL COMMENTS Sheet S2 FOUNDATION/2� FLOOR PLAN: 1. 4. EOR please sped the required connection of the (4) 2x6 to the 5-114X11-718 PSL dropped. The drawings still does not specify the required connections for the PSL. This should be added clearly to the drawings. 2. 5. IBC section 2305.2.5 requires blocked diaphragm to be classified as a rigid diaphragm. Since the floor cantilever out the lateral forces are required to transfer to the interior shear wall through the horizontal diaphragm. Please specify the diaphragm to be completed blocked in order to transfer the required forces. The response state the code does not requires blocked diaphragm when using rigid analysis. The only way to justify rigid analysis is by calculating the deflections of the diaphragm. The current adopted code only recognized blocked diaphragm to calculate the deflections per IBC 2305.2.2. ( Also TBC 2006 has this requirements alos) Modify drawing to state blocked diaphragm or modify analysis accordingly. Sheet S3 3RD FLOOR/ROOF FRAMING PLAN: 3. 7. EOR, please provide an analysis for the deckframing considering wind uplift. IBC 1605.3.1 EOR analysis was not submitted. Submit analysis to justify. 4. 8. Shear wall schedule: EOR, please modify panel edge stud far shear wall mark B level 1 to state 3X members are required. When nails are spaced at 2" O/C the minimum size panel edge member shall not be less then a single 3X. TBC 2306.4.1 The code does not allow member to be over stressed even by 2% as noted in the response. The engineer's response that he accept overstress member is not code compliant. The city will have to accept member that are overstressed. T will not sign off any member that is overstressed even if by a little bit. In addition the code is very clear that a single 3X shall be used for nails spacing at 2" OIC. This also is in the 2006 IBC. Modify drawings to state 3X member and not double 2X when nail spacing is at 2" as required per code and modify drawings so no member or elements are overstressed. ( Also note the 3X is required due to the nailing not the loading as per commentary submitted in the response) 5. 10. EOR please provide analysis for the lateral loads transferred through the horizontal diaphragm to the interior shear wall B on the lower floor. Note the main floor diaphragm is unblocked and this force is required to be added The load path is required to transfer this lateral force. Base off the submitted analysis Page 3 of 3 EECE#: EDM 07-02 (2) Gallaugher Duplex (2006-1384) an unblocked diaphragm will not transfer this force. Please modem accordingly. IBC table 2306.3.1 See comment 2 above. Additional corrections may be required following receipt of corrections and additional information as requested. Your pians are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874-0562 between 8A0 a.m. and 5:00 p.m. By: Hoyt Jeter, P.E. President