Loading...
20070641.pdfo�n City of Edmonds bd_ 35 Q� ,,;3.... PLAN REVIEW COMMENTS BUILDING DIVISION �S1$90 (425) 771-0220 DATE: December 3, 2007 TO: Erik Bredb erg AD Shapiro Architects FAX: 425-778-3032 FROM: Ann Bullis, Assistant Building Official RE: Plan Check #2007-0641 Project: New Townhouses (Building B) Project Address: 23006 Edmonds Way During review of the proposed plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator. 1. Previous item 2: On the "existing conditions" plan, the label is missing for the dark dashed line between parcel B and parcel C. The same line is also not labeled on the site plan. Please revise. 2. Previous item 3: Clearly note on 20/A0.1 that this plan is for reference only for "future" lot perimeters and that the subdivision must first be approved by the City of Edmonds. 3. Previous item 4: The Building Enclosure letter submitted must still be signed by the architect. 4. Previous item 5 — retaining walls on overall site plan: Label the type of retaining walls shown at the rear of building E (e.g. concrete, keystone, etc.). Show the location and extent of the 3' high rockery now shown at the rear of building F. Coordinate civils, site and landscape plans to show all retaining walls and rockeries, and cross reference construction details on both site and civil plans. Detail 16/A1.2 is for walls up to 4 feet high, while some walls shown on the site plan exceed this height. Revised detail and provide structural calculations for walls over 4 feet high. 5. Previous item 6 & 7: Since you are now designing to the TRC (confirmed with architect 11129/07), revise code information on Sheet A0: a. 2003 IRC, 2003 UPC, 2004 WSEC, and 2003 VIAQ b. R3/U occupancies c. Type of heating system (forced air furnace, in -floor hydronic, etc.). 6. Previous item 8 & 10: Show the cantilevers on the east side of building B, and dimension setback to cantilever. Show the decks and cantilevers on the west side of building B. Dimension the encroachment of the patios into the east setback area. Some setbacks appear to have been added to the future lot perimeters plan, but they need to the on the site plan. 7. On the site plan, relocate the "area of work" to be associated with Building B rather than Building A. Also, the height calc box and elevations need to be added to building B. 8. Provide construction detail showing how prefab concrete stair treads are to be installed. 9. North exterior wall of Building B (previous item 14): a. An imaginary property line needs to be placed between buildings A and B. Assuming it will be placed per the "future lot perimeters plan", exterior walls of both buildings must be 1 -hour fire resistive construction with no openings permitted (IRC R302). b. Clearly show on Sheet A2.1 and A2.2 that the north exterior wall of the building is 1 - hour fire rated, and cross reference construction details with listed and tested assembly. c. The exterior wall symbol on the wall key Sheet A2.1 is not the same symbol as shown on the floor plans. Please coordinate. Also, the reference to I SA/A9.1 is the incorrect wall type. It should reference wall types B 1 and D 1 for 1 -hour walls for both types of siding. d. The north elevation view on Sheet A3.1 shows both stucco and cement fiber siding. Clarify where one siding stops and the other starts. e. Revise construction details D/A9.1 and B/A9.1 to show exterior 5/8" Denshield Fireguard over the exterior sheathing per GA WP3615 on 12/A0.1. f. Provide a details of the roof termination and trim on the exterior side of the wall. Show where 2 & 3/A4.2 apply. Exterior wall trim cannot encroach closer than 24" to the imaginary property line. 10. At rear patio door of each unit, there needs to either be a 36" minimum landing in the direction or travel or a complying step (IRC R311.4.3). Clearly show/dimension on the unit floor plans. 11. Duplex separation walls with future property line between (previous item 11): a. On Section 16/A4.1 change reference detail number for lid to 4/A4.2. b. On detail 4/A4.2 label the roof joists so it is clear that the walls are extending to the underside of the structural roof sheathing. Also, revise the gyp at the underside of the roof sheathing so it starts at the edge of the double top plate (the structural sheathing should be continuous over the double top plate with no gyp in between). c. Revise I/A0.1 notes to reference 1 -hour exterior walls instead of fire barriers. The town house separation would be two 1 -hour exterior walls. Also, clarify with notes that you are using IRC R317.2.2 exception instead of a parapet. Change R2 occupancy to R3. d. On Section 16/A4.1 the gyp must cover the rim joists of each wall. e. Detail18C/A9.1: 1. Each wall must be a 1 -hour wall, therefore 5/8" type x gyp (or whatever materials the listed and tested assembly requires) will be required on the air space side of each wall. The listed and tested assembly IBC Table 720.1(2) 16-1.1 has been tested for fire exposure from the inside only which does not meet IRC R302.1. Both of these walls must be tested for fire exposure from both sides, so a new assembly must be provided. Also, the walls together must have an STC rating of 45 or more (IRC Appendix K). ii. Fire blocking is required at the floor lines and roof -ceiling line of the air space created between the walls. Show the fire blocking and call out the material (IRC R602.8). You may want to coordinate with your contractor since this can be tricky to build. ill. Clarify that both fire rated walls will extend to the underside of the structural roof sheathing. iv. Clearly show and note on the site plan that no utilities will pass through the common foundation and townhouse separation walls. V. On the roof plan A2.1, show that no penetrations are permitted for a distance of 4 feet on each side of the two walls. 12. Previous item 11: Unable to find fire stopping details on the plans. Page 2 of 3 13. Detail 9/A4.2: The perimeter of the handrail measures more than 6 1/4" therefore it must meet R311.5.6.3 Q. Clearly dimension handrail to show it meets all requirements of this exception. 14. Detail 14/A4.2: Dimension the height of the guard above finished floor/grade. 15. Detail 7/AI.2: Revise to show the handrail end returned at the bottom of the stair. 16. Previous item 12: Provide floor areas for each dwelling unit. 17. Previous item 18: Still waiting for letter from geotechnical engineer. 18. Previous item 19: Still waiting for Special Inspection and Testing Agreements. These must be submitted prior to permit issuance. 19. Detail 2/A9.1, clearly note that all wood in contact with concrete must be pressure treated. 20. Overflow drains are required in addition to the roof drains. See IRC R903.4.1 for requirements. Show on roof plans and provide details. 21. Provide structural calculations for metal grate guard at decks to show that it meets loads in Table R301.5. (Details on A4.2) 22. Sec attached comments from City Consultant. Provide written responses to each comment and where changes can be found on the plans Page 3 of 3 Eagle Eye Consulting Engineers, P.S. PO Box 523 Olalla, WA 98359 hoytjeter@centurytel.net 360 874 0562 Fax 360 874 0591 To: Marie Harrison City of Edmonds Edmonds, WA 98020 Re: Valhalla Building B (Townhouse) 23006 Edmonds Way Edmonds, WA 98020 Plan Review # 20070641 Date: November 16, 2007 EECE # EDM 07-29 (2) Structure Stated Gross Area S.F. First floor 1296 Second floor 1296 Total 2592 Garage 1061 Total 3653 Sprinkler Yes The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the Structural, Ordinance, Energy and Barrier Free requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. No Comments at this time a Page 2 of 4 EECE#: EDM 07-29 (2) Edmonds #: BLD20070641 Valhalla Building B STRUCTURAL COMMENTS ARCHITECTURAL COMMENTS Sheet A2.1 Building Plans 1. Please clarify where Detail XX/A4.1 occurs. I believe the intent is that this call out is to reference 16/A4.1. 2. It appears that these floor plan call outs do not match the Unit floor plan call outs on A2.2. Please modify accordingly. Sheet A2.3 Unit B2 Floor Plans (New Sheet) 3. Please add a smoke alarm on each level. One is required at garage level hall way. R313 4. Please add a smoke alarm on each level. One is required at First Floor level. R313 5. Please add a smoke alarm to the area giving access to the Second Floor bedrooms. R313 Sheet A4.2 Wall Sections, Details 6. Detail 3: Please clarify call out `See IN A4.2'. Detail 13/A4.2 is for the stair handrails. Sheet A7.1 (New Sheet) 7. Door Schedule: Please add to the door schedule which door type is to be used at each door. Three door types are shown in elevation. Sheet A9.1 Details S. SS. Detail 2: EOR, please provide an analysis for the wood ledger. This still does not appear to be addressed at this time. Page 3 of 4 EECE#: EDM 07-29 (2) Edmonds #: BLD20070641 . Valhalla Building B Ventilation and Indoor Air Quality Sheet A2.2 Unit B 1 & B2 Floor Plans (This sheets has been changed to reflect just the B 1 Floor plans) 9. 56. Please show the required ventilation for the washer and dryer room. WSV&IAQC 303.3.1 Please specify the size of the fan shown in the washer/ dryer room. 10. 58.,40R, please clarify the whole house ventilation requirements for this structure. WSV&IAQC 303.4 Sheet notes state that the whole house fan is required to be 65-98 CFM. Based on the stated unit area, the maximum CFM shall not exceed 90. Please modify drawings accordingly 11. Sheet notes state that the whole house fan is to be in the Master Bathroom. Plans show Master Bath fan to be 50 CFM. This does not match whole house fan specification in the sheet notes. Please modify accordingly. 12. 59. Please clarify how the dryer will be vented to the exterior on the drawings. It is not clear how this will be done based off the information submitted. This does not appear to be addressed. Room fan is shown, but not dryer vent. 13. 60. AOR, please clarify the required kitchen fan size and show locations. WSV&IAQC 303.3..1 This does not appear to be addressed. Sheet A2.3 Unit B2 Floor Plans (New Sheet) 14. Sheet notes state that the whole house fan is required to be 65-98 CFM. Based on the stated unit area, the maximum CFM shall not exceed 90. Please modify drawings accordingly. 15. Sheet notes state that the whole house fan is to be in the Master Bathroom. Plans show Master Bath fan to be 50 CFM. This does not match whole house fan specification in the sheet notes. Please modify accordingly. Energy code No Comments at this time. Page 4 of 4 EECE#: EDM 07-29 (2) Edmonds #: BLD20070641 Valhalla Building B Additional corrections may be required following receipt of corrections and additional information as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874- 0562 between 8:00 a.m. and 5:00 p.m. Hoyt Jeter, P.E. President