Loading...
20070703 Old Milltown Fire Connection Revision _1_.pdf Old Milltown – Fire Connection City of Edmonds TH 121 5 AVENUE NORTH • EDMONDS, WA 98020 • (425) 771-0220 FAX(425) 771-0221 Website: www.ci.edmonds.wa.us DEVELOPMENT SERVICES DEPARTMENT Planning • Building • Engineering Plan Review Comments Application: Date: # bld20070703 May 16, 2008 th Project Name/Address: Old Milltown/201 5 Ave S – REVISION 1 – Fire Connection Contact Person/Address/Fax: : Ralph Allen / e-mail: rwallen@gracearchitectspllc.com Reviewer: Division: Jeanie McConnell Engineering The resubmittal for the subject application has been reviewed but cannot be completed until the following items have been addressed/corrected. Please provide a written response to each item and resubmit 3 sets of revised drawings to Theresa Umbaugh, Permit Coordinator. The comments provided below were also provided under review of the DCDA revision submitted under permit #bld20060845. 1.SHEET C3 - The size of the DCDA has not been revised as previously requested. Please refer to detail E7.8, shown on sheet C4, for the correct orientation of the DCDA in the vault. Either the vault or the DCDA will need to be rotated 90 degrees. Rotating the DCDA will require additional bends in the fire line and could affect fire flows. Flow calcs will need to be revised accordingly. 2.Please revise the fire line layout to show the FDC connection to the supply line downstream of the PIV. 1 of 1 DATE E-MAILED 5/16/08 PAGE(s)