PLAN REVIEW COMMENTS
BUILDING DIVISION
(425)771-0220
DATE: July 12, 2007
TO: Airflow Mechanical
FAX: 425-776-3837
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check #2007-0702
Project: Stevens Health Care — Mechanical for Finance
Project Address: 21727 76th Ave W, Suite H
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator.
1. The floor plan provided showing the mechanical alterations is the "existing" floor plan, not the
proposed floor plan. Submit 2 sets of revised mechanical plans based on the proposed floor plan
as approved under Permit #2007-0369.
2. Provide supply and return to each room/space.
3. Call out cfin of new exhaust fan.