Loading...
20070807121213.pdfEagle Eye Consulting Engineers, Inc. PO BOX 523 Olalla WA 98359 C:206 356-7790 P:360 874-0562 F. 360 874-0591 To: Emerald Fire Att: Ross Bell 11021 Cramer Rd. K.P.L. Gig Harbour, WA 98329 Re: Steven's Hospital: ICU -PCU: 3`1 Level 21601 76th Avenue West Edmonds, WA Plan Review Number # 20070167 EECE EDM07-06 (2) Second review comments The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes (Fire Suppression only). The following comments, deficiencies/corrections must be addressed prior to completion of pians review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for Fire Suppression requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to Meet or will meet other departmental requirements, conditions and concerns before permit approval. Steven Hospital 21600 76`x' Ave W Permit #20070167 FIRE SUPPRESSION COMENTS General Page 2 of 2 EECE # EDM 07-06 (2) 1. Calculations: Your calculations only extend back to the 4 inch standpipe. Please provide water supply data that shows that the required flow and pressure are available at the connection to the 4 inch standpipe. NFPA 13, 14.4.1.3 Sheet 1 2. Provide a longitudinal brace on the 2 inch main located by the hydraulic design area. NFPA 13, 9.3.5.4 3. Rooms E3019, E3022A, and E3024 thru E3028 have water closets (toilet rooms) in them. These are required to have sprinklers in them. Either verify that they are already there or provide them and show on the plans. NFPA 13, 8. 1.1 4. Show and provide a sprinkler head in the entry vestibule for room E3019. NFPA 13, 8.1.1 Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (206) 356- 7790 between 8:00 a.m. and 5:00 p.m. By: Hoyt Jeter PE President