20070808144129.pdfTO: Attila Hegyi
Sebes 1 @comcast.net
FROM: Jenny Readwin, Plans Ex in
RE: Plan Check # 2007-0795
Project: Hegyi Remodel
Project Address: 19620 81St Place W
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Provide general roof framing plan to show that the walls being removed are non-bearing.
2) Provide typical wall detail for proposed walls (i.e. 2x4 @ 16" o.c., double top plate, etc.).
3) Show kitchen configuration on the existing as well as proposed floor plans.
4) Minimum. 100 cfm exhaust fan is required over the kitchen stove. Please note on plans.
5) Show location of proposed skylights on the floor plans.
6) According to your conversation with Ann Bullis, Assistant Building Official at the counter, it is
not possible for the new stairs to completely meet the current code. Provide stair detail for
proposed stairs (rise, run, handrail, headroom, etc.) and clearly show the stair that will be 1116"
higher. Please also supplement the detail with a written request for modification from the code
explaining the reason the stairs can not be constructed to meet current code. Also, a 36" door at
the top of the stairs to maintain the landing and stairway width is required. If this is not possible
please also include this in your written request for modification.
City of Edmonds
of�
tpPLAN
REVIEW COMMENTS
BUILDING DIVISION
Fst t s9°
(425) 771-0220
DATE: August
8, 2007
TO: Attila Hegyi
Sebes 1 @comcast.net
FROM: Jenny Readwin, Plans Ex in
RE: Plan Check # 2007-0795
Project: Hegyi Remodel
Project Address: 19620 81St Place W
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Provide general roof framing plan to show that the walls being removed are non-bearing.
2) Provide typical wall detail for proposed walls (i.e. 2x4 @ 16" o.c., double top plate, etc.).
3) Show kitchen configuration on the existing as well as proposed floor plans.
4) Minimum. 100 cfm exhaust fan is required over the kitchen stove. Please note on plans.
5) Show location of proposed skylights on the floor plans.
6) According to your conversation with Ann Bullis, Assistant Building Official at the counter, it is
not possible for the new stairs to completely meet the current code. Provide stair detail for
proposed stairs (rise, run, handrail, headroom, etc.) and clearly show the stair that will be 1116"
higher. Please also supplement the detail with a written request for modification from the code
explaining the reason the stairs can not be constructed to meet current code. Also, a 36" door at
the top of the stairs to maintain the landing and stairway width is required. If this is not possible
please also include this in your written request for modification.