tpPLAN REVIEW COMMENTS
BUILDING DIVISION
Esr: 18go (425) 771-0220
DATE: August 9, 2007
TO: Brian
FAX: 425-776-3622
FROM: Ann Bullis, Assistant Building Official
RE: Revision to Permit 2007-0278
Project: Aegis Mechanical Revisions
Project Address: 21500 72nd Ave W
During review of the revised plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where changes can be
found on the plans. Please submit revised plans/documents to Marie Harrison, Permit Coordinator.
1. Revised mechanical plans must be stamped and signed by the mechanical engineer of record.
2. Revise Exhaust Fan Schedule on Sheet M0.01 to omit dryer vent booster fans per City approved plans.
3. At mechanical shaft near the central stair, both fire dampers and smoke dampers (or combination
fire/smoke dampers) are required per IBC 716.5.3.1 for all penetrations of the shaft wall. New
equipment was provided and alterations made to the duct system requiring the upgrade.
4. Exhaust fan 102 missing from soiled laundry room per City approved plans.
5. Show revision of dryer vent shafts at each applicable floor through to roof.