PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: August 15, 2007
TO: Barbara Spiess
9401 215th Street SW
Edmonds, WA 98020
FROM: Jenny Readwin, Plans Ex finer
RE: Plan Check # 2007-0441
Project: Spiess Deck
Project Address: 9401 215''' Street SW
During re -review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Please add the following information to the site plan. Please redline plans or resubmit three (3)
new site plans scaled no smaller than 1"-20' and one on paper no larger than 8 %" x 14".
■ 8/15/07 Still need. 5/29/07 Still Need Property dimensions
■ 8/15/07 Still need. 5/29/07 Still Need. Label 215' Street SW
N ok
2) 8115107 Response says chimney is g -as. Please add this information to the plans. 5/29/07Still
need no response given. Show location of chimney on the plans. Per M1001.15 masonry
chimneys shall have a minimum 2" clearance to combustibles. Specify on the plans how this
will be obtained around the chimney.
3) 8/.15/07 Maximum run is 10" please revise and also show handraiUguardrail height, 4"
spacing between rails, etc. 5/29/07 Still need no response given Provide typical stair detail
showing rise, run, handrail, etc. complying with R311.5. Also, show how the stairs will be
framed. Plans appear to show the ledger continuing out but nothing is shown to support it on the
other end.. Engineer of Record to justify.
4) ok
5) ok
6) 8115107 Plans show on I' -6"x I'x6" footing to replace an existing: Is the footing typical If so
please not and if not dease_add footing size for remaining footings. 5/29/07 Still need no
response given Specify size of footings. Details say per plan and I was unable to locate this
information on the plans. Please specify.
7,) 8/15/07 Still need. No calculation provided and still not ledger shown for narrow portion of
deck. 5/29/07 Still need no response given Engineer of Record to specify ledger lag bolt size
and spacing and provide calculations to justify. Also clarify if ledger will continue along the
narrow portion of the deck. Nothing is shown on the plans at this location.