20070830091803.pdfDATE: August 30, 2007
TO: Brian
FAX: 425-776-3622
FROM: Ann Bullis, Assistant Building Official
RE: Revision to Permit 2007-0278
Project: Aegis Mechanical Revisions
Project Address: 21500 72nd Ave W
During re -review of the revised plans for the above noted project, it was found that the following
information, clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please submit revised plans/documents to Marie Harrison, Permit
Coordinator.
1. Previous comment 3: Per City/owner meeting on 8/30/07, both fire dampers and smoke dampers (or
combination fire/smoke dampers) are required per IBC 716.5.3.1 for all penetrations of the shaft wall
near the central stair. This item is still outstanding. Also, abandoned openings in the shaft, such as at
the crawlspace and at room 331, must be infilled with I -hour construction.
City of Edmonds
`' s;
PLAN REVIEW COMMENTS
BUILDING DIVISION
�sr l8go
(425)771-0220
DATE: August 30, 2007
TO: Brian
FAX: 425-776-3622
FROM: Ann Bullis, Assistant Building Official
RE: Revision to Permit 2007-0278
Project: Aegis Mechanical Revisions
Project Address: 21500 72nd Ave W
During re -review of the revised plans for the above noted project, it was found that the following
information, clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please submit revised plans/documents to Marie Harrison, Permit
Coordinator.
1. Previous comment 3: Per City/owner meeting on 8/30/07, both fire dampers and smoke dampers (or
combination fire/smoke dampers) are required per IBC 716.5.3.1 for all penetrations of the shaft wall
near the central stair. This item is still outstanding. Also, abandoned openings in the shaft, such as at
the crawlspace and at room 331, must be infilled with I -hour construction.