Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
20070907114402.pdf
AoV EDO City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION Fsr 1890 (425) 771-0220 DATE: September 7, 2007 TO: Mike Adams FAX: 425-774-7803 FROM: Ann Bullis, Assistant Building Official. RE: Permit Application: 2007-0696 Project: Arbor Villa 8 -unit Condominium Project Address: 7507 212th Street SW Below are combined comments from the City's plan review consultant and myself: Please provide written responses to each comment as to how it has been addressed (support with code sections where applicable), and where changes can be found on the plans. Please submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. NONSTRUCTURAL COMMENTS 1) Sheet R0.00: a) Use and Occupancy, add S2 occupancy for parking garages, and add 1 hour fire separation (in sprinklered building). b) Energy Code, revise for Residential Energy Code. Also, please complete enclosed worksheets and resubmit 2 copies. c) Code Information — Construction Type, note type of sprinkler system as NFPA Standard 13R. d) Code Information — Occupancy, add S2 occupancy for parking garages. e) Code Information — Governing_ Codes, revised edition of Energy Code to 2004, revise edition of National Electrical Code to 2005, and remove NFPA 101. f) Deferred Submittals remove Type A unit casework (since there is no Type A unit), replace fire protection system with fire sprinkler and fire alarm as separate submittals. Also add State elevator, Life Safety Plan/Fire Emergency Guide, Listed & Tested Fire Stopping Assemblies, Landscape Irrigation (if applicable), Building Enclosure Certification Letter, Maintenance Bonds. g) Special Inspections, revise to match special inspection list under structural comments below plus any additional inspections required by the Structural Engineer. 2) Sheet A1.00: a) Dimension distance between proposed building and existing 6 -unit building. b) Show imaginary property line between proposed building and existing 6 -unit building. Dimension distance from imaginary property line to each building. c) Note the Type of Construction for the existing 6 unit building. d) Based on 60 parking stalls on site, 3 must be accessible and dispersed throughout the site. One must be for the new building. e) Where the accessible path of travel from the public sidewalk to the building entrance is located in a vehicle drive aisle, provide a minimum 44" wide painted crosswalk. f) Add S2 garage occupancy. 3) Based on location of imaginary property line in item 2b above, provide opening percentage calculations for each building. Provide opening percentage calculations on the plans for all side of the building. 4) Provide occupant load calculations for each floor and the total building. 5) Provide unit numbers on the floor plans. 6) Dimension the accessible maneuvering distances at common area doors and unit entry doors (see attached figure). Also, dimension clear width of corridor, including at turns and in front of elevator. 7) The stairway must be enclosed in a 1 -hour fire rated exit enclosure per IBC 1019. A redesign is required to accommodate the exit enclosure. The exit enclosure must exit directly to the outside or to a 1 -hour exit passageway (IBC 1020) that leads directly to the outside. Provide section detail of the stairway showing fire barrier walls continuous to the underside of the floor/roof decking. Show if the enclosure will terminate at a 1 -hour roof assembly rather than the underside of the roof sheathing (IBC 706.4 exception 2). 8) It appears that the Architect is using IBC 1018.2 Buildings With One Exit. Clearly note this on the plans, and show on the floor plans for each unit that the travel distance will not exceed 50 feet to an exit, such as an exit enclosure (see IBC 1002 for definition of exit and IBC 1015.1 for measurement of travel distance). Also, clearly show that each sleeping room will have an egress window meeting IBC 1024 (no egress window exceptions apply when you are using IBC Table 1018.2). The den/offices in the north units have closets and are considered sleeping rooms. A complying egress window is required from each of these rooms. Note egress window dimensional requirements and sill height on the plans. 9) % hour rated corridors are required on all floors (however a 1 -hour listed and tested assembly will be required to meet and STC of 50+), with self-closing 20 minute rated doors with gaskets. Glazed openings (fixed, not openable) must be minimum 20 minute fire window assemblies (IBC 715.4 exception 2) or wire glass constructed per IBC 715.4.3. Also, see number 8 above regarding egress windows. Show all information on the plans and cross-reference to wall, door and glazing schedules. 10) Dwellings must be separated from each other with 1 -hour fire partitions with an attic draftstop extending to the underside of the roof sheathing per IBC 717.4 (also see exceptions — if exception is used, note on plans). Provide listed and tested 1 -hour assemblies with tested STC rating. 11) Walls and floor -ceilings separating dwellings from other dwellings or common areas (such as corridors, stair enclosures, elevator and mechanical shafts, etc.) must meet a Sound Transmission Class (STC) of 50 or more. Provide listed and tested assemblies showing compliance. 12) Provide listed and tested fire rated assemblies for walls, floor -ceilings, roof -ceilings, and individual protection of structural members supporting a floor and roof or more than one floor, as well as fire barriers and horizontal assemblies (such as from Gypsum Fire Resistance Design Manual, UL or IBC Chapter 7 Tables). Provide details with complete listed and tested assemblies and reference on the floor plans where they apply on the floor plans and building sections. The few wall types on the floor plans did not cross-reference to details that could be verified. Required fire resistive construction must be clearly shown on the plans due to the Type of Construction, dwelling unit fire separations, fire rated corridors, exit enclosure, elevator shaft, etc. Page 2 of 4 13) Where deck floor -ceilings and roof -ceilings must be 1 -hour fire rated, provide construction details and listed/tested assemblies with materials that can be exposed to weather (revise 2/A8.00 accordingly). Decks are also considered openings and must be included in percentage calculations noted in #3 above. 14) Eaves must be 1 -hour fire rated. Revise 4/A8.00 accordingly. 15) The elevator shaft must be 1 -hour fire rated and meet IBC 706 for fire barriers. 16) All penetrations of the 1 -hour rated assemblies must be firestopped per IBC 712.3. 1 -hour rated putty pads must be installed on the electrical boxes, unless exception for steel electrical boxes is used (see IBC 712.3.2). Provide fire stopping details with listed and tested fire stopping assemblies (such as UL, FM, etc.). 17) Where ducts, exhaust fans, can lights, etc. penetrate the 1 -hour fire rated assemblies, show how the rating will be maintained, such as with lined joist bays, vertical shafts, soffits, etc., and provide details. 18) Revise 7/A8.00 for 1 -hour construction. 19) Switch labels for Master Bedroom and Master Bathroom for northeast and northwest units on the 2nd and 3rd floors. 20) At the north units on all floors, provide a minimum clear dimension of 40" between the pantry and counter (ICC/ANSI Al 17.1 Section 804.2.1). At south units dimension distance from range/cabinets to wall adjoining entry. 21) At Type B unit bathrooms, at toilet dimension the minimum clearances for parallel approach per ICC/ANSI A117.1 Section 1004.11.3.1.2.1. 22) Floor Plan Notes: a) For Note #2, note stud size and spacing at typical walls. b) Revise fire blocking note to include fire stopping where applicable. 23) Whole House Ventilation: Since electric wall heaters will be the source of heat, how will fresh air be provided to all habitable spaces, particularly those on the interior of the building? For ventilation requirements noted on the floor plans, since the whole house exhaust fan will be the kitchen fan, note how the required 24 hour timer will be provided. 24) Parking garage ventilation is required per VIAQ 304. Show the location of the parking garage exhaust outlets. They must meet IMC/WAC 502.7.3.6 #2, including 10 feet from property line, 10 feet from building openings, and 10 feet minimum above grade. 25) Handrails are required on both sides of the stairway with top and bottom handrail extensions. IBC 1009.11 26) Complete Lighting Summary form for common areas and exterior lighting. 27) Show locations of illuminated exit signage and emergency lighting (IBC 1011, 1006), and specify power back-up. 28) Note on the plans what type of ventilation system will be used for the corridor/common areas. The system will be checked with the mechanical permit/plans. STRUCTURAL COMMENTS 29) Revise Special Inspections on Sheet S-0 to include: a) Soil Bearing Verification b) Placement of Fill and Compaction c) Foundation Drainage d) Structural Wood: Periodic special inspection of Shearwalls 2, 3, 4, 5, & 6, nailing, anchor bolts, holdowns, dragstruts, etc. (IBC 1707.3) e) Structural ,Steel: Welding, High-strength bolting (A325) Page 3 of 4 Complete the enclosed ,Special Inspection and Testing Agreements (one form for geotech and one for structural special inspector). Have the owner, general contractor and special inspector sign the form(s) and return for Building Official approval prior to permit issuance. 30) Structural engineer to provide Quality Assurance Plan per IBC 1705 on structural notes page. 31) General contractor must provide signed Contractor Responsibility Statement per IBC 1706 prior to permit issuance. 32) Clarify on structural plans stud size for shearwalls, bearing walls, etc. ADDITIONAL STRUCTURAL COMMENTS BY CITY PLAN REVIEW CONSULTANT CaIculations 33) Please recheck the shear wall aspect ratio for the shear wall SW5 that is only 1.75 ft long (2nd floor framing plan of S2.00), and reduce the shear wall capacity accordingly (multiplied by 2W/H) per IBC table 2305.3.3. Drawings 34) General ---- Provide blocking and strap around opening in horizontal diaphragm bigger than 4'-0" (for example: stairway & elevator shaft opening) for stress concentration, per IBC 2308.11.3.3. 35) Sheet A4 — Building section A. Provide structural concrete wall/foundation detail for the elevator pit. 36) Sheet S 1 — Detail 12. Please specify the edge distance for the 518" anchor bolt. Shouldn't there be 2 anchor bolts per each shear wall to take care of both the compression and tension and seismic forces that could come from opposite direction than the design assumed? 37) Sheet S2 — Detail 6,7 & 8. To assure the stress uniformly spread out, please specify non - shrinkage high strength grout below base plate. Please call out anchor bolt edge distance (where occurred). 38) Sheet S2 — Detail 10. Please provide standard hook for the rebar in the footing per IRC R403.1.3. 39) Sheet S2 — Framing plans show single columns support beams of different depths. Clarify detailing to address connection requirements for what appears to be the standard case of unequal depths. 40) Sheet S 1.00&S2.00 — Claxify/coordinate section cut labels. Section labels like 13,15, 16, 18,19, 21 does not correspond to any detail in the drawing set. System of identification within submitted package needs to be consistent. Page 4 of 4 r C2 b� W Q m V■ > > DX0 1 VS 11) CD DC) z Cl) na'INAN .q .q o0 N 0 1, r �r W rn r C2 b� W Q Fm N 00 r3 � i Q 0 Q. CY) X a o S3 CD Q a � O h N ri :` V■ � r i V, 1 VS 11) na'INAN m cn.; cn ilm CD ;e' r£ ch k i�``-> 'ice Q g �. lu Cl) - :-,-,.vim-': ...r..- � Fm N 00 r3 � i Q 0 Q. CY) X a o S3 CD Q a � O h N ri :` V■ � �- V, 1 VS 11) CD Q Chapter 4. Accessible Routes 18 ICCJANSI Al 17.1-2093 r ----- I n j *If Both closer and latch are provided I I r—rt-------� 18 min I 1 I � LO 445 I I 1 F LO I 12 min* I 1 I o CIDr I 305 I ] f 00N I I I I I (a) Front Approach, Pull Side (b) Front Approach, Push Side r--------------, 1 4 I I I 14 I I I I I 1 S� I c o I 36 min 1 l� � I 42 min I � I o ,- I � 915 I I 1065 I `n r I I I 1 Nov I ] (c) Tinge Approach, Pull Side * If both closer and latch are provided **48 min (1220) if bath closed and latch provided 12 min* 305 F----------� I i 22 min m I I 560 E oI I I c'] rl I I I I (e) Hinge Approach, Push Side (d) Hinge Approach, Pull Side *54 min (1370) if closer is provided r ---_ -------i I <I I I Ic 24 min E N I 610 � r I z1, (f) Latch Approach, Pull Side r ----------- l4 I ! I c E 24 min I "' E co 610 j 1 I I (g) Latch Approach, *48 min (1220) Push Side if closer is provided Fig. 404.2.3.1 Maneuvering Clearance at Manual Swinging Doors 2006 Washington State Nonresidential Energy Code Compliance f=orm 2006 Washington State Nonresidential. Energy Code ComMance Forms ReO;ed duly 2007 Project Info Project Address Date For Building Department Use Applicant Name: _ Applicant Address: Applicant Phone: Project Description ❑ New Building ❑ Addition ❑ Alteration ❑ Plans Included Refer to WSEC Section 1513 for controls and commissioning requirements - Compliance Option O Prescriptive O Lighting Power Allowance Q Systems Analysis (See Qualification Checklist (aver). Indicate Prescriptive &LPA spaces clearly on plans.) Alteration Exceptions I (check appropriate box - sec. 1132.3) ❑ No changes are being made to the lighting ❑ Less than 60% of the fixtures new, installed wattage not increased, & space use not changed. Maxianuan Allowed Lighting Wattage Location Allowed (floodroom no.) Occupancy Description Watts per ft2 "' Area in ft2 Allowed x Area -- i-rom t aoie 30-1 tover) - document all exceptions on roan L i U -Lt -A i otal Aiioweo wausl Proposed Lighting Wattage I Location Number of (floor/room no.) Fixture Description Fixtures Watts/ Watts Fixture Proposed Total Proposed Watts may not exceed Total Allowed Watts for Interior -total Proposed Watts Notes: 1. For proposed Fixture Description, indicate fixture type, lamp type (e.g- T-$), number of tamps in the fixture, and ballast type (if included). For trade Fighting, fist the length of the track (in feet) in addition to the fixture, lamp, and ballast information. 2. For proposed Watts/Fixture, use manufacturer's listed maximum input wattage of the fixture (not simply the lamp wattage) and other criteria as specified in Section 1530- For hard -Wired ballasts only, the default table in the NREC Technical Reference Manual may also be used. For track lighting, list the greater of actual luminaire wattage or length of track multiplied by 50, or as applicable, the wattage of current limiting devices or of the transformer. .3. List all factures. For exempt lighting; note section and exception number, and leave Wafts/Fixture blank. ATTACHMENT A 2006 Washington Nonresidential Energy Code Compliance Farms State Nonresidential Code Compliance Form Revised July 2007 Prescriptive Spaces Occupancy: Q warehouses, storage areas or aircraft storage hangers OOther Qualification Checklist Lighting Check if 95% or more of fixtures Comply with 1,2 or 3 and rest are ballasted. Note: if occupancy type is "Other" and is the Fixtures: (Section 1. Fluorescent fixtures which are non -lensed with a) 1 or 2 two lamps, b) reflector fixture answer checked, number of ruxfures in the space is not limited by Code. 1521) or louvers, c) 5-60 waft T-1, T-2, T-4-, T-5, T-8 lamps, and d) hard -wired elec- Cleady indtcate these spaces an plans. If 1.2 tronic dimming ballasts. Screw-in compact fluorescent fixtures do not qualify. not qualified, do LPA Calculations. Cafeterias, fast food establishments . restaurantsibare 2. Metal Halide with a) reflector b) ceramic MH lamps - 150w c) electronic ballasts Post office 1.1 3. LED lights. TAFt1 G AK_4 I Inif I inhfiPnwAr Allnwanr-n fl RAI Use LPA IA Use LPA Wls Automotive facility 0.9 Office buildings, officeladministrative areas in facilities of other use types (including but not limited to schools, hospitals, institutions, museums, banks, churches .1.11 1.0 Convention center 1.2 Penitentiary and other Grou 1-3 Occupancies 1.0 Courthouse 1.2 Police and fire stations 1.0 Cafeterias, fast food establishments . restaurantsibare i .3 Post office 1.1 Dormitory 1.0 Retail , retail banking, mail concourses, wholesale stores(pallet rack shelving) 1.5 Exercise center 1.0 School buildings (Group E Occupancy only), school' classrooms, day care centers 1.2 Gymnasia', assembl spaces' 1.0 Theater, motion picture 1.2 Health care clinic 1.0 Theater, performing arts 1-6 Hospital, nursing homes, and other Group 1-1 and 1-2 Occupancies 1.2 Transportation 1-0 Hoteltmotel 1.0 Warehouses". storage areas 0.5 Hotel ban ueticonference/exhibition hall ' 2-0 Workshops 1.4 Laboratory spaces (all spaces not classified "laboratory" shall meet office and other appropriate cate ones 1.8 Parking garages 0-2 Laundries 1,2 Libraries 1.3 Plans Submitted for Common Areas Onl Manufacturina facility 1.3 Main floor building lobbies (except mall concourses 1.2 Museum 1.1 Common areas, corridors, toilet facilities and washrooms, elevator lobbies 0.8 Footnotes Tor Table 15-1 .1)' In cases in which a general use and a spectfic use are fisted, the specific use shall apply. In cases in which a use Is not mentioned specifically, the Unit Power Allowance shall be determined by the building official. This determination shall be based upon the most comparable use specified in the table. See Section 1512 for exempt areas. 2) The watts per square foot may be increased, by two percent per foot of ceiling height above twenty feet, unless specifically directed otherwise by subsequent footnotes. 3) Watts per square foot of room may be increased by two percent per foot of ceiling height above twelve feet. 4) For all other spaces, such as seating and common areas, use the Unit Light Power Allowance for assembly. 5) Watts per square foot of room may be increased by two percent per foot of ceiling height above nine feet. 6) Reserved. 7) For conference rooms and offices less than 150re with full height partitions, a Unit Lighting Power Allowance of 1.10 wife may be used. :8) Reserved. .9) For indoor sport tournament courts with adjacent spectator seating over 5,000, the Unit Lighting Power Allowance for the court area is 2.60 Wife. 10) Display window illumination installed within 2 feet of the window, provided that the display window is separated from the retail space by walls or at least three -quarter -height partitions (transparent or opaque). and lighting for free-standing display where the lighting moves with the display are exempt. An additional 1.5 w/ftz of merchandise display luminaires are exempt provided that they comply with all three of the following: a) located on ceiling -mounted track or directly on or recessed Into the ceiling itself (not on the wall). b) adjustable in both the horizontal and vertical axes (vertical axis only is acceptable for fluorescent and other fixtures with two points of track attachment). c) fitted with LED, tungsten halogen, fluorescent, or high intensity discharge lamps. This additional lighting power is allowed only if the lighting is actually installed. 11) Provided that a -floor plan, indicating rack location and height, is submitted, the square footage for a warehouse may be defined, for computing the interior Unit Lighting Power Allowance, as the floor area not covered by racks plus the vertical face area (access side only) of the racks. The height allowance defined in footnote 2 applies only to the floor area not covered by racks. - 2006 Washington State Nonresidential Enerav Code washbwlm Form Project Info Prof Addres _. .-.. .. Date Watts Proposed For Building Department Use Name: Appl..Name Appl. Phone r Project Description ❑ New ❑ Addition ❑ Alteration [I Plans Included Refer to WSEC Section 1513 for controls and commissioning requirements. Compliance Option O Lighting Power Allowance O Systems Analysis Building Grounds (luminaires > 100 Watts) ❑ Efficacy > BO lumensAN ❑ Controlled by motion Sensor ❑ Exemption (list) Alteration Exceptions (check appropriate box - sec. 1132.3) ❑ No changes are being made to the lighting ❑ Less than 80°1° of the fixtures new, Installed wattage not increased, & space use not changed. Tradable Maximum Allowed LiLrhting Wattaze Tradable Locatlons Allowed Watts Area (ft), perimeter Description per fie or per If (if) or # of items Allowed Watts x ft (or x 1f Watts Proposed rotas Auoweo watts f Use mfgr listed maximum input wattage. For fixtures with hard -wired ballasts only, ! Tradable Proposed Lighting Wattage the default table in the NREC Technical Reference Manual may also be used. Location Number of Fixture Description Fixtures Wafts! Fixture Watts Proposed • �•�• • •.•in.�ca• rraaw —.Y Awa cxa.ccu i uwk f UUWULI YuclMi IV[ CXLL:IIVI Non -Tradable Maximum Allowed Lightinz Wattaze iota• I-roposea YvausI I Non Tradable Locations Allowed Watts Description per fe or per If Area (ft), perimeter Allowed Watts (If) or # of items x fe (or x If) Waits Proposed Non -Tradable Proposed Lighting Wattaze Location Number of Fixture Description Fixtures Wafts/ Fixture Waits Proposed Froposea vvatis may not exceea Allowea watts tar Category ATTACHMENT B 2006 Washington State Nonresidential Energy Code Compliance Form fid:�t=��[•]r�llf#E�I11[!E#t+l!fl#Ii111 •11111 A 2006 Washington State NonresldenU Energy Gods Cnmpliance Forms Revised July 2007 TABLE 15-2 LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS Tradable Surfaces Uncovered Parking Areas (Lighting power Parking lots and drives 0.15 W/ft densities for uncovered Building Grounds parking areas, building Walkways less than 10 feet wide 1.0 W/linear foot -grounds, building entrances and exits, canopies and overhangs Walkways 10 feet wide or greater plaza areas 0.2W/ft and outdoor sales areas Special feature areas may be traded.} Stairways 1.0 WIfe Building Entrances and Exits Main entries 30 W/Iinear foot of door width Other doors 20 Wllinear foot of door width Cano fes and Overhangs Canopies (free standing and attached and 1.25 W/ft overhangs Outdoor Sales Open areas (including vehicle sales lots) 0.5 W/lre Street frontage for vehicle sales lots in addition. to "open area" allowance 20 W/lincar foot Non -Tradable Building Facades 0.2 W/ft2 for each illuminated wall or Surfaces (Lighting surface or 5.0W)'linear foot for each power density illuminated wall or surface length Automated teller machines and night depositories 270 W per location plus 90 W per additional ATM per location calculations for the following applications can be used only for the specific application and cannot be traded between surfaces or with other exterior fighting. The following allowances are in addition to any allowance otherwise Entrances and gatehouse Inspection stations at guarded facilities 1.25 WIfe of uncovered area (covered areas are included in the "Canopies and Overhangs" section of "Tradable Surfaces" Loading areas for law enforcement, fire, ambulance and other emergency service vehicles 0.5 W/ft2 of uncovered area (covered areas are included in the "Canopies and Overhangs" section of "Tradable Surfaces" Material handling and associated 0.5 Wlfe permitted in the "Tradable Surfaces" storage section of this table.) Drive -up windows at fast food 40OW per drive-through restaurants Parking near 24-hour retail entrances 800 W per main entry city of edmonds development information Washington State Energy & Ventilation Codes Residential Compliance Worksheets Prescriptive Approach CODES: Edmonds Community Development Code Chapters 19.30 and 19.35 Washington State Energy Code 2006 Edition Washington State Ventilation & Indoor Air Quality Code 2006 Edition The purpose of the State energy code is to provide minimum standards for new or remodeled construction to achieve efficient use and conservation of energy. This handout provides the basic minimum codes for prescriptive compliance. The basic prescriptive approach for energy code compliance is the easiest way to determine or show code compliance. It is a straight takeoff and comparison of total window (glazing) and door opening area versus the heated floor space. The percentage of glazing shown on the enclosed charts determines the minimum U -value of all windows and doors for the project, and the insulation R -value for wall, floor, slab and ceiling insulation. This handout is intended to provide minimum prescriptive compliance and it is not intended as a substitute for the entire State Energy Code. Also included in this packet is a Ventilation and Indoor Air Quality Worksheet. Tighter construction and insulation standards have introduced a vast amount of chemicals and other pollutants into dwellings. The process of natural ventilation has also been greatly reduced due to the required sealing of sheathing at walls and floor levels_ The State Ventilation and Indoor Air Quality Code (VIAQ) has been created as a means for bringing in fresh outdoor air, and exhausting interior stale air. The VIAQ code allows either a manual portal system or a mechanical system that runs unmonitored on a timer to convey the air. Forms and additional information about the State Energy and Ventilation Codes can be found on the WEB at www.ener .wsu.edu. PLEASE COMPLETE THE FOLLOWING ATTACHED ENERGY AND VENTILATION WORKSHEETS AND SUBMIT TWO (2) COPIES WITH YOUR BUILDING PERMIT APPLICATION. Revised 7/07 0V EDA. O v � 0 t. l 16 f CITY OF EDMONDS ENERGY & VENTILATION RESIDENTIAL COMPLIANCE WORKSHEETS PRESCRIPTIVE APPROACH PLEASE COMPLETE THE FOLLOWING ENERGY AND VENTILATION WORKSHEETS AND SUBMIT TWO (2) COPIES WITH YOUR BUILDING PERMIT APPLICATION. DATE PROPERTY ADDRESS PROPERTY OWNER JOB TYPE ❑ New ❑ Addition ❑ Remodel (check all that apply) ❑ Single Family ❑ Multi --Family # Units HEATED FLOOR AREA Existing New Total HEATING BY ❑ Gas ❑ Electric ❑ Other SYSTEM TYPE ❑ Forced Air Furnace Hydronic: Infloor ❑ heaters Radiant E]E]Wall ❑ Other FOR CITY USE ONLY PLAN REVIEW # DATE OF REVIEW MAXIMUM GLAZING % COMPLIANCE OPTION WHOLE HOUSE VENTILATION SYSTEM TYPE: MANUAL FORTIWINDOW VENT WITH EXHAUST FAN INTEGRATED FORCED --AIR FURNACE COMMENTS: Revised 7107 2006 WSEC Chapter 6 Qualification Form- Zone I Residential Prescriptive (Chapter 6) Options For All Heat Sources Instructions: -arefully review the requirements for each of the options below. Choose an option that best suits your dwelling design_ Glazing percentage typically ieternrines which option to choose. Your building must match the selected option requirements without exceptions or substitutions_ Disregard components or ,quipment that does not apply to your project. Your permit will be processed more efficiently if you provide all of the requested information. Department staff ;an help you with general questions about this form. Proposed. designs which cannot meet the specific requirements of a listed option above may calculate ;ompliance by Chapter 4 or 5 o€the 2006 Washington State Energy Code. Forms can be found on the WEB at WWW_ENERGY.WSU.EDU * Reference Case 0_ Nominal R -values are for wood frame assemblies only or assemblies built in accordance with Section 601.1- 1. Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 13% it shall comply with all of the requirements of the 15% glazing option (or higher). Proposed design which cannot meet the specific requirement of a listed option above may calculate compliance by Chapter 4 or 5 of this Code. 2. Requirements applies to all ceilings except single rafter or joist vaulted ceilings complying with note 3. `Adv' denotes Advanced Framed Ceiling. 3. Requirement applicable only to single rafter or joist vaulted ceilings where both (a) the distance between the top of the ceiling and the underside of the roof sheathing is less than 12 inches and (b) there is a minimum 1 -inch vented airspace above the insulation. Other single rafter or joist vaulted ceilings shall comply with the "ceiling" requirements. This option is limited to 500 square feet of ceiling area for one dwelling unit. 4. Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as wall above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2 5. Floors over crawl space or exposed to ambient air conditions. 6. Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications_ See Section 602.4, 7_ Int_ denotes standard framing 16 inches on center with headers insulated with a minimum of R-10 insulation_ 8_ This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing. 9. Doors, including all €ire doors, shall be assigned default U -factors from Table 10-6C 10_ Where maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value. Overhead glazing with U -factor of U=0.40 or less is not included in glazing area limitations. 11. Overhead glazing shall have U -factors determined in accordance with NFRC 100 or as specified in Section 502.1-5- 12- Log and solid timber walls with a minimum average thickness of 3.5" are exempt from this insulation requirement_ This project will take advantage of the following exceptions to the prescriptive option: 0 602.6 Exception I.One door, that is 24 sq ft or less, that doe_ s not meet the standards is allowed. location of door taking this exemption - 0 602.5 Exception 2_ Doors with U -factor of 0.40 allowed without calculations, Option IV only_ Location of door(s) taking this exemption: Glazing U -Factor Option Glazing Area 10 Vertical Overhead i� Doo? Door U- Ceiling 2 Vaulted 3 Wall Above Wall° int Wall° ext Floor$ Stab on % Of Floor Factor Ceilin g Grade'2 Below Below Grade b Grade Grade 1 10% 0.32 0.58 0.2 R-38 R-30 R-15 R-15 R-10 R-30 R-10 11* 15% 0.35 0.58 0.2 R-38 R-30 R-21 R-21 R-10 R-30 R-10 25% Group R-1 III and R-2 0.4 0.58 0.2 R-38/ R-30/ R-21/ R-15 R-10 R-301 R-10 Occupancies U=0.031 U=0.034 U=0.057 U=0.029 Only Unlimited Group R-3 and tv R-4 0.35 0.58 0.2 R-38 R-30 R-21 R-21 R-10 R-30 R -l0 Occupancies Only Unlimited Group R-1 and V R-2 0.35 0.58 0.2 R-38 R-301 R-21/ R-15 R-10 R-30/ R-10 Occupancies /U=0.034 U=0.034 U=0.057 U=0-029 Only * Reference Case 0_ Nominal R -values are for wood frame assemblies only or assemblies built in accordance with Section 601.1- 1. Minimum requirements for each option listed. For example, if a proposed design has a glazing ratio to the conditioned floor area of 13% it shall comply with all of the requirements of the 15% glazing option (or higher). Proposed design which cannot meet the specific requirement of a listed option above may calculate compliance by Chapter 4 or 5 of this Code. 2. Requirements applies to all ceilings except single rafter or joist vaulted ceilings complying with note 3. `Adv' denotes Advanced Framed Ceiling. 3. Requirement applicable only to single rafter or joist vaulted ceilings where both (a) the distance between the top of the ceiling and the underside of the roof sheathing is less than 12 inches and (b) there is a minimum 1 -inch vented airspace above the insulation. Other single rafter or joist vaulted ceilings shall comply with the "ceiling" requirements. This option is limited to 500 square feet of ceiling area for one dwelling unit. 4. Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as wall above grade. Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications. See Section 602.2 5. Floors over crawl space or exposed to ambient air conditions. 6. Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications_ See Section 602.4, 7_ Int_ denotes standard framing 16 inches on center with headers insulated with a minimum of R-10 insulation_ 8_ This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing. 9. Doors, including all €ire doors, shall be assigned default U -factors from Table 10-6C 10_ Where maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value. Overhead glazing with U -factor of U=0.40 or less is not included in glazing area limitations. 11. Overhead glazing shall have U -factors determined in accordance with NFRC 100 or as specified in Section 502.1-5- 12- Log and solid timber walls with a minimum average thickness of 3.5" are exempt from this insulation requirement_ This project will take advantage of the following exceptions to the prescriptive option: 0 602.6 Exception I.One door, that is 24 sq ft or less, that doe_ s not meet the standards is allowed. location of door taking this exemption - 0 602.5 Exception 2_ Doors with U -factor of 0.40 allowed without calculations, Option IV only_ Location of door(s) taking this exemption: VAPOR BARRIERS shall be installed toward the warm surface as represented below (select once): Floors: Kraft Faced Unfaced insulation withPlywood Sheathing batt insulation ❑ polyethylene (4 mil) ❑ (Exposure I or exterior grade) ❑ Walls: Face stapled Unfaced insulation with batt insulation ❑ polyethylene (4 mil) ❑ Vapor Retarding Paint ❑ Ceilings*: Face stapled Unfaced insulation with batt insulation ❑ polyethylene (4 mil ) ❑ Vapor Retarding Paint *NOTE: Vapor Barrier not required where ventilation space averages 12" or greater above the insulation SLAB INSULATION shall be R-10 minimum and be located on the: ❑ Exterior ❑Interior SLAB INSULATION EXAMPLES NOT CONSTRUCTION DETAILS Floating Slab with Interior Insulation Silicone Caulk Seal 4" Concrete Slab Floating Slab on Grade wllnterior Slab Insulation Silicone Caulk Seal Thermal Break 111101111 __ =1111=IIII-1111= 111 =11111=I1 I_<_ 11HNII111_IIfIl fllTl— lil!!� i1111=0111=111-111= _-_=11111=11111=IIIII1!111 — —— �=11111 `�=_� -11111=11lII�III11=11111 1_11111-11111=11111 11111-11111"=11111=1.1111= Revised 7107 4" Concrete Slab Floating Slab with Exterior Insulation Flashing/Protection Silicone Caulk Seal JK z . Thermal Break 4" Concrete Slab =IIII............... =11111 == = Ill 1l-i�fllY II—VIII— mil pay IIIII=1!111=11111=IIIII=IMI 11111=11111, = _ _ =IIIIIRIII1 -NIIL !Illi= X11111—IIIII =_ —11111=11111=IIIII=11il1 11111=1 = == -!_=IIIII-HIII_Illii_ __ __- _______-1=1 IIIII-- II111— — –IIIII= R-10 Insulation III11=11111=1111=111!1- 24" minimum Below Grade Wall with Interior Insulation Silicone Caulk Seal Damp Proofing HEATED 11lIi=IIII =___`_ BASEMENT 6 mil poly 1!111=IIIII=IHI1= --_ - _- IIII!_1IIlITIIlIl 4"ConcreteSraa R-10 Insulation Illll=#! III=!IIii =IIII 24 mini — — mum —IIIII-IIIII—INI#=�=::�-<= "-- - ----- --- -- -- IIIII=IIIII=IIIIIIIII=:11-:111 --- IIIIE 1111IT:_:_: ___ <_ --::- ::>_ _:_ : IIII 1111= _ _ -- !1111=1111= �-�' _ __- - 6 mil o3 _ I _..IIIIf IIIII-IIIII =111 :.:_...=::::_-:-"�':_� =IIIII=LEI : Lull = LLI1J-(� IIIII=ITIT1 f1T11=f)JI1=1T(TI= Thermal creak 11111-11111 11119=1111111111====u-11111=_ =11111— III 11111=11111-W 11111-I#illlllil=____ ___=_II11=1118= IIIM111=1 =!IIII= 6mil poly =11111 III1f-11111=-_=_____ 11111-111111111 =1Hll=loll-1_ ` =11111=11111—f 11 ' 4" Gravel Base 1111JJ1== i 19=1 _______ ----I =_=_y 1111=1 =ill! _-_ _: IIIII=1_-11111- =11111= =1111 ____ _____-____ 11111 -_ _______=_!1_11111_=1 -_ _ _=IIIII= R-10 Insulation 11111=Iild1-11111.=111!1= 24" minimum or to frostline Floating Slab on Grade wllnterior Slab Insulation Silicone Caulk Seal Thermal Break 111101111 __ =1111=IIII-1111= 111 =11111=I1 I_<_ 11HNII111_IIfIl fllTl— lil!!� i1111=0111=111-111= _-_=11111=11111=IIIII1!111 — —— �=11111 `�=_� -11111=11lII�III11=11111 1_11111-11111=11111 11111-11111"=11111=1.1111= Revised 7107 4" Concrete Slab Floating Slab with Exterior Insulation Flashing/Protection Silicone Caulk Seal JK z . Thermal Break 4" Concrete Slab =IIII............... =11111 == = Ill 1l-i�fllY II—VIII— mil pay IIIII=1!111=11111=IIIII=IMI 11111=11111, = _ _ =IIIIIRIII1 -NIIL !Illi= X11111—IIIII =_ —11111=11111=IIIII=11il1 11111=1 = == -!_=IIIII-HIII_Illii_ __ __- _______-1=1 IIIII-- II111— — –IIIII= R-10 Insulation III11=11111=1111=111!1- 24" minimum Below Grade Wall with Interior Insulation Silicone Caulk Seal Damp Proofing HEATED 11lIi=IIII =___`_ BASEMENT 6 mil poly 1!111=IIIII=IHI1= --_ - _- IIII!_1IIlITIIlIl 4"ConcreteSraa R-10 Insulation Illll=#! III=!IIii =IIII 24 mini — — mum —IIIII-IIIII—INI#=�=::�-<= "-- - ----- --- -- -- IIIII=IIIII=IIIIIIIII=:11-:111 --- IIIIE 1111IT:_:_: ___ <_ --::- ::>_ _:_ : IIII 1111= _ _ -- !1111=1111= �-�' _ __- - 6 mil o3 _ I _..IIIIf IIIII-IIIII =111 :.:_...=::::_-:-"�':_� =IIIII=LEI : Lull = LLI1J-(� IIIII=ITIT1 f1T11=f)JI1=1T(TI= Thermal creak VENTILATION WORKSHEET SOURCE SPECIFIC VENTILATION: Exhaust fans are required in each kitchen, bathroom, laundry room, indoor swimming pool, spa, and other room(s) where excess water vapor or cooking odor is produced. Complete the following table: Location .: Reyu�red.CFM `: Actual CF11M KITCHEN FAN 100 CFM BATHROOM #1 FAN 50 CFM BATHROOM 92 FAN 50 CFM BATHROOM #3 FAN 50 CFM LAUNDRY FAN 50 CFM WHOLE HOUSE VENTILATION: Each dwelling unit shall be equipped with a whole house ventilation system supplying outdoor air to all habitable rooms and exhausting stale air out via a designated fan. Complete the following questions and table: [:]Not applicable for additions less than 500 sq.ft. SELECT TYPE OF WHOLE HOUSE VENTILATION SYSTEM TO BE USED: ❑ Exhaust fan system with ducted forced air heating system (VIAQ 303.4.1)-- 0 03.4.1):• Exhaust fan sized per table below with 24 hour timer. • Forced air heating system ducted to all habitable rooms. • Interior doors undercut %" minimum above floor covering. ❑ Exhaust fan system with fresh air inlets (VIAQ 303.4.1): • Exhaust fan sized per table below with 24 hour timer. • Manual through -wall port or approved window vent. ❑ Integrated with forced air furnace System (VIAQ 303.4.2): • Outdoor air inlet duct sized per table 3-5 connected to the return air plenum of the forced air system. • Volume damper. ❑ Supply fan system (VIAQ 303.4.3): • Distribute air through the forced -air system ducts or through dedicated ducts to each habitable space with 24 hour timer. • Outdoor air must be filtered • Outdoor air inlet connected to supply or return. • Back draft and volume dampers. ❑ Heat recovery system (VIAQ 303.4.4) Revised 7107 A WHOLE HOUSE EXHAUST FAN MUST BE PROVIDED FOR EACH DWELLING UNIT_ Floor Area Bedrooms* (square feet) 2 or less 3 4 5 6 Min. Max. Min. Max. Min. Max. Min. Max. Min. I Max. <500 50 75 65 98 80 120 95 143 110 165 501-1000 55 83 70 105 85 128 100 150 115 173 1001-1500 60 90 75 113 90 135 105 158 120 180 150I-2000 65 98 80 120 95 143 110 165 125 188 2001-2500 70 105 85 128 100 150 115 173 130 195 2501-3000 75 113 90 135 105 I58 120 180 135 203 3001-3500 80 120 95 143 110 165 125 188 140 210 3501-4000 85 128 100 150 115 173 130 195 143 218 4001-5000 95 143 110 165 t 125 188 140 2 1O�-T 155 233 'tor more than 0 bedrooms and/or over SUUU square feet see Table 3-2 Washington State Ventilation and Indoor Air Quality Code_ Total Floor area: Bedrooms: Whole House Fan Size: Location: ✓ WHOLE HOUSE EXHAUST FAN WILL OPERATE INTERMITTENTLY? Yes ❑ No ❑ Both automatic and manual control needed. Automatic control timer shall be set to operate whole house fan for a minimum of eight hours per day. ✓ WHOLE HOUSE EXHAUST FAN ALSO SERVES AS A BATH OR LAUNDRY FAN? Yes ❑ No ❑ The capacity shall be the larger CFM requirement_ ✓ WHOLE HOUSE EXHAUST FAN WILL OPERATE CONTINUOUSLY? Yes ❑ No ❑ Note: Installers shallprovide the manufacturer's installation, operating instructions, and a whole house ventilation system operation description. A label shall be affixed to the whole house timer control that reads "Whole House Ventilation (see operating instructions). " Revised 7107 Ventilation System Operating Instructions '1111hoie goose Ventilation Systems integrated with a Forced Air Heating System' Your new home.has been constructed to use energy efficiently, while maintaining a healthy indoor environment with good supply of fresh air. To help you achieve these benefits, we recommend that you take a few minutes to read these instructions. Your home has been constructed to the most current requirements of the Washington State Energy Code (2003 edition) and the Washington State Ventilation and Indoor Air Quality Code (2003 edition). This means your home and the ductwork of your heating system have been well sealed, which limits uncontrolled exchange of air between the indoors and outdoors. The amount of fresh air provided to your home is under your control. You can increase the ventilation rate of your home by opening windows, or by operating your mechanical ventilation systems. Your home has two types of mechanical ventilation: spot ventilation fans, and a whole house ventilation system integrated with your heating system_ Spot Fans: A spot fan has been installed in each bathroom, the utility room and the kitchen. If your home includes an indoor spa, or any other room that may need additional ventilation, a spot fan will be included there as well. The purpose of spot ventilation is to control excess moisture, odors, or f chemical byproducts at the source. It is far more effective to quickly eliminate moisture and pollutants when they are created than to allow them to dissipate slowly over time. Controlling moisture reduces the cause of many molds and protects the finishes of your home. Controlling odors and chemical byproducts reduces any health hazard that may be associated with them. It is particularly important to operate your kitchen fan if you have a gas or propane range. As well as removing moisture and odors created by cooking, your kitchen exhaust fan removes the unhealthy byproducts of combustion, including carbon monoxide and nitrogen oxides. Recommended spot fain operation: • Turn on the spot fan whenever moisture, odors, household chemicals, or combustion byproducts are present in the room, such as during shower- ing, washing clothes, or cooking. • Since moisture vapor, odors,. and combustion byproducts tend to linger, run the spot fan for up to 60 minutes beyond the activity that produced them. Whole house ventilation integrated with the heating system. The forced air heating system in this home is equipped with a ventilation system. This system includes a fresh air intake connected to the return air duct (return air is the air that flows into your heating system), a damper that controls the amount of air that enters the system, and a timer that controls when the system operates. To change the amount of ventilation in your home adjust the timer to increase or decrease the time the system operates. In some cases you may also want to adjust the damper. Here's how the system works: SUPPLY DUCT FRESH AIR INTAKE Figure i _ Whole house ventilation system integrated with a forced air heating system. • When the ventilation timer calls for ventilation, the furnace fan motor turns on. If the ventila- tion system is equipped with a mechanical damper, it also opens_ • The furnace fan pulls fresh air through the fresh air intake into the return air duct. • Fresh air is then distributed to the home through the supply air ducts of the heating system. • When the ventilation timer shuts off, the furnace fan motor turns off. If the system has a me- chanical damper, the damper also closes. Note: If your system is not equipped with a mechanical damper, your home will also receive ventilation whenever the system fan operates, including when it's on to provide heating or cooling. Selecting a Whole House Ventilation Schedule: Your contractor has set the timer on your ventilation system to provide a minimum of eight hours of ventilation per day. To get the maximum benefits of the system, you'll want to adjust the timer to suit your own schedule. • Run the system more when you expect to be home, or when more people are expected to be in the home. • Set the timer to cycle the system on and off for short periods. for example, 10 minutes on, 20 minutes off. Use the manual control to turn the system on when large groups gather in your home. TIME OF DAY ON/OFF PINS AUTO: RUN TIME BASED ON TIMER ON: CONTINUOUS OPERATION Figure 2_ Typical whole house ventilation timer. 2 Ventilation System Operating Instructions Dampers: There are three types of dampers allowed by the ventilation code. Figure 3 identities these dampers and describes how they work- This system uses the damper checked below. ❑ Manual Damper ❑ Constant Air Flow Regulator ❑ Motorized Damper As required by code-, your heating contractor has tested the flow reate of fresh air brought into your home and set the damper accordingly - Manual Damper Operatio": In normal operating conditions, the damper is always open, regardless of the settings on the ventilation timer. The home receives ventilation whenever air handier fan turns on, or when the thermostat calls for heating or cooling. Using the timer to regulate the ventilation rate is always the best choice. But because this system provides ventilation to the home whenever the air handler fan operates, ventilation rates may be excessive during very cold or very hot weather. This can mean wasted energy and an uncomfortable home- In this case, you may wish to adjust the manual damper. Before doing so, keep a few things in mind: • Before you change the damper setting, make note of the position of the damper adjustment. You will need to return the damper to this setting when the extreme weather passes. • Only reduce the ventilation rate when abso- lutely necessary. • Be aware for signs of under -ventilation, includ- ing smells and high humidity - FAANJA;. DAMPER AL WAY5 OPEN. GON5TANT AIRFLOW �EGULA-O2 I%r:Ttr:ALbLAD ER t;Av ONRETURN GUG' AIF`PRESSURE Al_ M5 OPEN. PAMPER A Iv nTCFz: kVEN5 THE GA%4-ER OWJi HE; rENTILAi- I[15G;�LLEV FOO FYTHr rs, EV. �ILtSME15iEGUL T-61) t3'(O'EN PAMPER PC351-T7,11AOJU51 ENT. Figure 3. Selection of dampers used to meet the ViAQ code- Ventilation System Operating Instructions 3 CITY OF EDMONDS SPECIAL INSPECTION AND TESTING AGREEMENT The project at issued under building permit number requires special inspection and/or testing per IBC Chapter 17. The complete list of special .inspections is attached to this document. BEFORE A PERNIIT CAN BE ISSUED: The owner and contractor and special inspector shall complete this agreement and the attached structural test(s) and inspections schedule including the required acknowledgements. APPROVAL OF SPECIAL INSPECTORS: Each special inspector shall be approved by the Building Official prior to performing any duties or inspections. Each special inspector shall submit Statement of Qualifications to the Building Official for review. Special inspectors shall display identification when performing special inspections on site. Special inspection and testing shall meet the minimum requirements of IBC Chapter 17 and the following: A. Duties and Responsibilities of the Special inspector 1. Observe Work The special inspector shall observe the site work for conformance with the approved (stamped) plans and specifications and applicable workmanship provisions of the IBC_ Architect or Engineer reviewed shop drawings may be used only as an aid to inspection. Special Inspections are to be performed on a continuous basis—meaning that the special inspector is on site at all times observing the work requiring special inspection_ Periodic inspections, if any, must have prior approval by the City based on a separate written plan reviewed and approved by the Building Official and the engineer or architect of record. 2. Report Non -conforming Items The special inspector shall bring non -conforming items to the immediate attention of the contractor and note all such items in the daily field report. Any item not resolved in a timely manner shall be immediate cause of the special inspector to notify the Building Official of the plan deviation, error, change or omission. It shall also be the duty of the special inspector to promptly notify the engineer or architect. 3. Complete Daily Reports Each special inspector shall complete and sign both the special inspection record and the daily report form for each day's inspection. These records shall remain at the jobsite with the contractor for review by the City Building Inspector. 4. Furnish Weekly Reports The special inspector or inspection agency shall furnish the City with weekly reports of tests and inspections. The project engineer or architect, and others as designated shall also be copied on reports. Weekly reports must include the following: • Description of daily inspections and tests made with applicable locations • List of all non -conforming items • Report on status of non -conforming items (resolved or unresolved) • Itemized changes authorized by the Architect, Engineer and City if not included in non- conformance items. 5. Furnish Final Construction Report The special inspector or inspection agency shall submit a final signed report to the City stating that all items requiring special inspection and testing were fulfilled and reported. And, to the best of L_\,TEMP'1BUILDINGISpeciailnspectionAgreementlBC-doc 7/04 his/her knowledge the project is in conformance with the approved plans and specifications, approved change orders and the applicable workmanship provisions of the IBC. Items not in conformance or unresolved items or any discrepancies in inspection coverage, (Le., missed inspections, periodic inspection .when continuous inspections were required, etc.) shall be specifically itemized in this report. B. Contractor Responsibilities 1. Notify the Special Inspector It is the duty of the contractor to notify the special inspector when work is ready for special inspection_ Note, the items listed on the attached schedule and as noted on the approved plans and specifications are required to have special inspections. Adequate notice shall be provided by the contractor so that the special inspector has time to become familiar with the project_ 2. Provide Access to Approved Plans The contractor is responsible for providing the special inspector access to approved plans at.,the jobsite. 3. Retain Special Inspection Records The contractor is responsible to retain at the jobsite all special inspection records submitted by the special inspector. These records are to be provided to the City building inspector upon request. C. City of Edmonds Building Department Responsibilities 1. Approve special inspectors or inspection agencies The building department shall approve all special inspectors and special inspection requirements. 2. Monitor special inspection and approve weekly reports Work requiring special inspection and the performance of special inspectors shall be monitored by the City Building Inspector. flis/Her approval must be obtained prior to placement of concrete or other similar activities in addition to that of the special inspector. 3. Issue Certificate of Occupancy The Building Official may issue a Certificate of Occupancy after all weekly special inspection reports including the final report have been submitted and accepted. D_ _Owner Responsibilities The project owner or the engineer or architect of record acting as the owner's agent shall fund special inspection services. E. Engineer or Architect of Record_ Responsibilities The engineer or architect of record shall include special inspection requirements on the plans and specifications. ACKNOWLEDGEMENTS I have read and agree to comply with the terms and conditions of this agreement. Owner Special Inspector General Contractor City Building Official L_1TEMI'IBUILDING\SpeciallnspectionAgreernentlBC.doc 7/04 Date Date Date Date SPECIAL INSPECTION AND TESTING SCHEDULE MULCT NAME FROM" ADVf&SS REINFORCED CONCRETE, GUNITE, GROUT AND MORTAR: Concrete Gnnitc Grunt Mnrrnr A&—gate Tests Reinforcing Tcsts Mix Designs Reinforcing Placemen[ Batch Plant Irspcction Inspc" Placing _ . Cast Sanrnlcs Tests PRECASFIPRFSTRESSED CONCRETE: -acus :rr-rcns %-Matorg - Aggrt•ga[e 3ests Reinforcing Tcsts Tendon Tests Mix Desi¢os Reinforcing Placement Insert Placement Concrctc Batching Concrete Placement t llation Inscpaion Samnlcs 7'CS Tests MASONRY — Special Inspection Stresses Used Preliminary Acceptance Tests fMasonry Units_ Wall Pnsms) — Subsequent Tests (Mortal, Groot, Field Wall Prisms_) — Placement Inspection of Units ADDITIONAL INSTRUCTIONS OR OTHER TESTS AND INSPECTIONS: Form eompkwd by= "Iclephow No__ — suaiwcet=�trrrrNo Actavcr asrect,u_u�srrt-�[t STRUCTURAL STEELiWELDIN(;: --.- Sample and Test (list specific members blow) — Shop Material Idcatification -w Welding Ittspcction O Sbop ❑ Fidd — Ultrasonic Inspccrion ©Shop ❑Meld — Ifigh'strength Bolting ksf__�_ © Shop O Field O A325 DA490 DN Ox OF — Metal Dock Welding Inspection — Reinforcing Steel Welding hmpmlion I — Metal Stud Welding Inspcctica — Concrete Insert Welding saspection FIREPROOFING: — Placcrrrnu Inspection — Density Tcsts Thickness Tests Inspect $arching INSULATING CONCRETE: — Sample and Test — Placctncntlnspection Unit Weights . FILL MATERIAL: — Acceptance Tests — Placement Inspection — f=ield Density STRUCTURAL WOOD_ Shear Wall Failing Inspection Inspection of Glu -Jam Fab, Inspection of Truss Joist Fab. --_ Sample and res[ Components Title- Date-