20070911093150.pdfTO: Catherine Kennedy
FAX: 206-522-2565
FROM: Ann Bullis, Assistant Building Official
AST—
RE: Plan Check # 2007-0856
Project: Alder Apartments – Restore Fire Separations for Unit G
Project Address: 230 3' Ave South, Unit G
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit 2 sets of revised plans/details to Theresa
Umbaugh, Permit Coordinator.
1. On the floor plan note all uses of space (e.g. living room, bedroom, kitchen, closet, bathroom,
etc.).
2. Note on the 1 -hour wall detail that this detail applies to all surrounding walls (not just the party
walls) of the unit since this is a Type VA (1 -hour rated) building.
3. Note on floor plans if the ceiling sheetrock is being replaced. If it is, the architect must provide
a 1 -hour listed and tested floor -ceiling assembly detail with an STC (sound transmission class)
of 50 or more. If it is not, specify that only the wall sheetrock will be removed.
4. Smoke detectors are required in each sleeping room and in areas accessing each sleeping room.
They must be hardwired with battery backup and be interconnected. Show the locations on the
floor plan.
City of Edmonds
of EDO
n
PLAN REVIEW COMMENTS
BUILDING DIVISION
�St_ 1 sgo
(425) 771-0220
DATE: September 11, 2007
TO: Catherine Kennedy
FAX: 206-522-2565
FROM: Ann Bullis, Assistant Building Official
AST—
RE: Plan Check # 2007-0856
Project: Alder Apartments – Restore Fire Separations for Unit G
Project Address: 230 3' Ave South, Unit G
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit 2 sets of revised plans/details to Theresa
Umbaugh, Permit Coordinator.
1. On the floor plan note all uses of space (e.g. living room, bedroom, kitchen, closet, bathroom,
etc.).
2. Note on the 1 -hour wall detail that this detail applies to all surrounding walls (not just the party
walls) of the unit since this is a Type VA (1 -hour rated) building.
3. Note on floor plans if the ceiling sheetrock is being replaced. If it is, the architect must provide
a 1 -hour listed and tested floor -ceiling assembly detail with an STC (sound transmission class)
of 50 or more. If it is not, specify that only the wall sheetrock will be removed.
4. Smoke detectors are required in each sleeping room and in areas accessing each sleeping room.
They must be hardwired with battery backup and be interconnected. Show the locations on the
floor plan.