Loading...
20070912115434.pdfo E� City of Edmonds PLAN REVIEW COMMENTS ` BUILDING DIVISION FS r. is9° (425) 771-0220 DATE: September 12, 2007 TO: Kyle Kragseth Kyle.lffagseth@lewisbuilds.com FROM: Jenny Readwin, Plans Exq+ RE: Plan Check # 2007-0776 Project: Kragseth new SFR Project Address: 22706 95"i Place W During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Please add the following information to the site plan. Show North garage door landing (36"x 36" minimum). You may redline plans or resubmit three (3) new site plans scaled no smaller than 1"=20' and one on paper no larger than 8 %Z" x 14". 2) Based on comments dated September 10, 2007 by Jen Machuga, planner a geotechnical report is required. Please make sure your geotech addresses all the requirements of IRC chapter 4. See attached for minimum building department geotech report requirements to assure that the report covers Building and Planning requirements. 3) Per completed energy form the whole house fan is required to be 120-180 cfm. Please note on plans. 4) See attached structural comments from city consultant. Respond to each item in writing. BJY Northwest Architecture • Engineering • Planning . Government Services August 29, 2007 To: City of Edmonds Contact person: Theresa City of Edmonds 425,771.0220 x 1389 Re: Project Description: Kraegseth, new SFR PLAN CK # 2007- 0776 22706 967H PL W. SJY# 052 1 1 FLOOR U BUILDING 1yl:I AREA 5.F The above referenced project is in the process of plan review for compliance with The City of Edmonds ordinances and applicable codes (Structural, Non Structural & Energy). The following comments, deficiencies/corrections must be addressed prior to completion of pians review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the ordinance, structural and non-structural portion of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. ARCHITECTURAL COMMENTS Non Structural & Energy Review Approved STRUCTURAL COM-MENTS DRAWINGS SHEET A — 2 1 1. Provide design of deck railing per IBC 1607.1 (50 PLF)& 1607.1.1. (200# point load). Verify fastener design considers exposure per IBC sec. 2304.9.5 & IRC Sec. 319.3 SHEET A4 A5. 2. Missing shear wall on one side. Please clarify 3. Missing header beams. Please provide. SHEET L.— 1 4. Section A A'should show the deck beyond and its footing. Please provide the embedment of concrete pad footing of deck. SHEET G — 1 5. Typical walls section shows craw space, which is in variance with A3, and so on. Please clarify. Additional corrections may be required following receipt of corrections and additional information as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact . BJY at tedchenCa7 ly.com (206) 264-8440 between 8=04 am and 5:44 pm. By: 2 SOILS INVESTIGATION AND/OR REPORT (Cont.) The following information from IRC Table R401.4.1, will assist individuals in determining the soil classification of the building site. The Building Official may require this classification to be made by a Washington State licensed Geotechnical Engineer or Engineering Geologist in a written report when soils are riot adaptable to conventional spread footings or if allowable foundation and lateral pressures do not meet the values set forth in the table below. The allowable foundation and lateral pressures may not exceed the values in this table, unless data to substantiate the use of higher values is submitted. Sidehill or steep slope construction W IS NOT considered conventional construction and sons reports are required for lots with 15% or more sloe unless determined unnecessary by the Building „Official. For more specific and technical information on soil capacity, foundation design and construction components, refer to IBC Chapter 18 and IRC Chapter 4 or contact a professional engineer. vy` TABLE 8401.4.1 PRESUMPTIVE LOAD-BEARING VALUES OF FOUNDATION MATERIALS' For SI: 1 pound per square foot = 0.0479 kN1m2. a. When soil tests are required by Section R401.4, the allowable bearing capacities of the soil shall be part of the recommendations. b. Where the building official determines that in-place soils with an allowable bearing capacity of less than 1,500 psf are likely to be present at the site, the allowable bearing capacity shall be determined by a soils investigation. When soils reports are required, they shall include the following: 1. A plot plan showing the location of test borings and/or excavations. 2. A complete record of the soil samples. 3. A record of the soils profile. 4. Elevation of the water table, if encountered. 5. Recommendations for foundation type and design criteria, including but not limited to: bearing capacity of natural or compacted soil; provisions to mitigate the effects of expansive soils; mitigation of the effects of liquefaction, differential settlement and carrying soil strength, the effects of adjacent loads, and foundation drainage. 5. Expected total and differential settlement. 7. Pile and pier foundation information in accordance with IBC Section 1808.2.2. 8. Special design and construction provisions for footings or foundations founded on expansive soils, as necessary. 9. Compacted fill material properties and testing in accordance with IBC Section 1803.5. NOTE: Report recommendations shall be incorporated into the foundation design 4. DRAINAGE PLAN (3 copies) (See Handout #E72) Development of over 2,000 square feet of impervious area requires an on-site drainage system. Impervious area includes: building pad with cave overhangs, paved or graveled areas, solid surface decks, patios, walkways, breezeways, awnings, accessory structures, sidewalks, and driveways. Submit three (3) drainage plans, scaled I "=20', showing all impervious area with square footages as well as the location of the proposed drainage detention system. Attach three (3) copies of the drainage worksheet. Note: The plan must provide for temporary and permanent erosion control and must include footing drain details. Revised 7107 LOAD-BEARING PRESSURE CLASS OF MATERIAL(pounds per square foot Crystalline bedrock 12,000 Sedimentary and foliated rock 4,000 Sandy gravel and/or gravel (GW and GP) 3,000 Sand, silty sand, clayey sand, silty gravel and clayey gravel (SW, SP, SM, SC, GM and GC} 2,000 Clay, sandy clay, silty clay, clayey silt, silt and sandy silt (C1, ML, MH and CH) 1,500, For SI: 1 pound per square foot = 0.0479 kN1m2. a. When soil tests are required by Section R401.4, the allowable bearing capacities of the soil shall be part of the recommendations. b. Where the building official determines that in-place soils with an allowable bearing capacity of less than 1,500 psf are likely to be present at the site, the allowable bearing capacity shall be determined by a soils investigation. When soils reports are required, they shall include the following: 1. A plot plan showing the location of test borings and/or excavations. 2. A complete record of the soil samples. 3. A record of the soils profile. 4. Elevation of the water table, if encountered. 5. Recommendations for foundation type and design criteria, including but not limited to: bearing capacity of natural or compacted soil; provisions to mitigate the effects of expansive soils; mitigation of the effects of liquefaction, differential settlement and carrying soil strength, the effects of adjacent loads, and foundation drainage. 5. Expected total and differential settlement. 7. Pile and pier foundation information in accordance with IBC Section 1808.2.2. 8. Special design and construction provisions for footings or foundations founded on expansive soils, as necessary. 9. Compacted fill material properties and testing in accordance with IBC Section 1803.5. NOTE: Report recommendations shall be incorporated into the foundation design 4. DRAINAGE PLAN (3 copies) (See Handout #E72) Development of over 2,000 square feet of impervious area requires an on-site drainage system. Impervious area includes: building pad with cave overhangs, paved or graveled areas, solid surface decks, patios, walkways, breezeways, awnings, accessory structures, sidewalks, and driveways. Submit three (3) drainage plans, scaled I "=20', showing all impervious area with square footages as well as the location of the proposed drainage detention system. Attach three (3) copies of the drainage worksheet. Note: The plan must provide for temporary and permanent erosion control and must include footing drain details. Revised 7107