PLAN REVIEW COMMENTS
BUILDING DIVISION
Fsa_ i$go (425) 771-0220
DATE: October 1, 2007
TO: Kathryn Wohnovtka
kwohnovtka@msn.com
FROM: Jenny Readwin, Plans Ex ine
RE: Plan Check # 2007-0921
Project: McCloughan Addition/Remodel
Project Address: 938 Pine Street
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Please add the following information to the site plan.
R It appears that there will be a new roof over the entire house. Please note this on the site
plan. Everything currently is labeled as "existing". Contact the Planning Department for
requirements on replacing portion of the existing structure within the current setbacks.
■ On the site plan please clearly show where the trellis roof over the proposed deck is located.
You may redline plans or resubmit three (3) new site plans scaled no smaller than 1 "-20' and
one on paper no larger than 8 %2" x 14".
2) Show how island sink will be vented through the roof or with a loop vent as permitted by UPC
909.0.Air admittance valves are not permitted unless first approved by the Building Official
under and alternate method per UPC 301.2.
3) See attached structural comments from city consultant. Respond to each item in writing.
Eagle Eye Consulting Engineers, P.S.
PO Box 523
OEalla, WA 98359
hoytleter@centurytel.net
360 874 0562
Fax 360 874 0591
To: Jeff and Jenny McCloughan
Re: McCloughan Residence
938 Pine St.
Edmonds, WA, WA 98020
Plan Review # 2007-0921
Date: September 21, 2007
EECE # EDM 07-37
Structure
Stated Area S.F.
Existing Basement
601
Exist in Main floor
1225
Main Floor Addition
803
Total
2629
Existing Garage
624
Total
3253
New Deck
599
rand total
3852
The above referenced project is in the process of plan review for compliance with Edmonds
ordinances and applicable codes. The following comments, deficiencies/corrections must be
addressed prior to completion of plans review and subsequent issuance of permits.
Provide revised plans and calculations along with a written response to each of the items listed
below to facilitate a shorter back -check time.
SCOPE OF REVIEW
The scope of this review is for the Ordnance Energy and Ventilations and Indoor Aar
Quality and Structural requirements of this project.
All features were checked only to the extent allowed by the submittals provided. All portions
of this project are assumed to meet or will meet other departmental requirements, conditions
and concerns before permit approval.
STRUCTURAL COMMENTS
Sheet A-2.0: Floor Plans
1. Please clarify the 3x3 post question mark by the stairs. Is this a new post? R 106. 1.1
Sheet S2.0: Foundation Plan
Page 2 of 3
EECE#: EDM 07-37
McCloughan Resinence
2. Please justify by analysis that the existing slab on grade can support the point load at
the stair wall, under the 6x8 beam.
Sheet S2.1: Main Floor Plan & framing Plan
3. Please clarify what is supporting the existing 6x8 beam at the stair wall.
4. Please specify the required attachment of the new (3)2x10's at the existing 6x8 beam.
5. Please specify the required attachment of the new (3)2x10's at the exterior wall
6. Please specify the required attachment of the new (3)2x10's at the new 3-1/2xPSL
beams.
ORDINANCE COMMENTS
General
7. Please specify the venting at the eave or cornice vents (size and number). In order to
use the 1/300 venting allowance, it must be shown that at least 20% of the venting is in
the lower portion of the roof. R806
Sheet A-3.0: Elevations
8. It appears all the windows are being replaced. Please clearly note the locations the
safety glazing on the drawings. 8308 (i!
9. Please specify all locations of the egress windows and the required size. The required
operable size should be specified. 8310
Sheet A-2.0: Floor Plans
10. Please specify and locate the new crawl space ventilation on the basement plan.
11. Please show the locations of the smoke alarms in existing bedrooms. 8311
12. Please show the location of the required smoke alarm in the basement.
13. Please specify handrails for the stairs at for the new deck. There is more than 4 riser
and handrails are required.
Sheet A-4.0: Sections and Schedules:
14. It is not clear if there will be attic spaces access exceeding 30". Please either add attic
access or clarify the space will not exceed 30". R807.
s
Page 3 of 3
EECE#: EDM 07-37
McCloughan Resinence
ENERGY CODE
Sheet A-4.0: Sections & Schedules
15. Please modify the U value specified to state U of .35 and not U=.36. WSEC table 6-1
VENTILATION & INDOOR AIR QUALITY CODE (V&IAQC)
No comments at this time
Additional corrections may be required following receipt of corrections and additional
information as requested.
Your plans are being reviewed concurrently with the Building Department, Fire
Department, Zoning Department and Public Works Engineering. Changes,
clarifications or additional corrections may be required subsequent to the Building
Department plan review when comments are received from the other concerned
departments.
Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360)
874-0562 between 8:00 a.m. and 5:00 p.m.
By:
Hoyt Jeter, P.E.
President