PLAN REVIEW COMMENTS
BUILDING DIVISION
Fsc. 1 S9 (425) 771-0220
DATE: October 8, 2007
TO: Terri (Murphy) Gietzen and Daniel Gietzen
murphyts@comcast.net
FROM: Jenny Readwin, Plans E amine
RE: Plan Check # 2007-1022
Project: New SFR
Project Address: 8715 Talbot Rd.
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Please add the following information to the site plan.
■ Now this is considered a new single family residence rather than a 2'd story addition. Please
change labels on the site plan accordingly.
■ Show all landings (i.e. garage man door, laundry room door and family room French doors.
You may redline plans or resubmit three (3) new site plans scaled no smaller than 1"=20' and
one on paper no larger than 8 %" x 14".
2) Cross reference all details to their location on the plans. Cross out any details that do not apply
to this house.
3) Per letter dated August 27, 2007 from the Building Official (see attached) the existing
construction to remain must be inspected by the structural engineer of record and justified for
the proposed addition/remodel. Please provide letter from engineer of record stating that he has
inspected the existing foundation and provide calculations to justify that it, along with the
proposed alterations on sheet S2, will adequately support the new residence.
4) Plans must clearly show new construction. General notes, such as the note on sheet 3 of 8 that
all exterior walls are new construction is not adequate for plans. They must clearly show all
proposed work as new. Please revise plans accordingly.
5) See attached structural comments from city consultant. Respond to each item in writing.
Eagle Eye Consulting Engineers, P.S.
PO Box 523
Olalla, WA 98359
hoytjeter@centurytel.net
360 874 0562
Fax 360 874 0591
To: Marie Harrison
121 5th Ave. N
Edmonds, WA, WA 98020
Re: Geitzen Addition
8715 Talbot Road
Edmonds, WA, WA 98020
Plan Review # 2006-1215
2.1
Date: October 8, 2007
EECE # EDM 07-42
The- above referenced project is in the process of plan review for compliance with
Edmonds ordinances and applicable codes. The following comments,
deficiencies/corrections must be addressed prior to completion of plans review and
subsequent issuance of permits.
Provide revised plans and calculations along with a written response to each of the items
listed below to facilitate a shorter back -check time.
SCOPE OF REVIEW
The scope of this review is for the Structural Only requirements of this project.
All features were checked only to the extent allowed by the submittals provided. All
portions of this project are assumed to meet or will meet other departmental requirements,
conditions and concerns before permit approval.
STRUCTURAL COMMENTS
General
Main floor
2792
Second floor
2020
Total
4812
Garage
723
Total
5535
Deck Second Floor
98 j
Porch
53
Grand total
5686
EECE # EDM 07-42
The- above referenced project is in the process of plan review for compliance with
Edmonds ordinances and applicable codes. The following comments,
deficiencies/corrections must be addressed prior to completion of plans review and
subsequent issuance of permits.
Provide revised plans and calculations along with a written response to each of the items
listed below to facilitate a shorter back -check time.
SCOPE OF REVIEW
The scope of this review is for the Structural Only requirements of this project.
All features were checked only to the extent allowed by the submittals provided. All
portions of this project are assumed to meet or will meet other departmental requirements,
conditions and concerns before permit approval.
STRUCTURAL COMMENTS
General
Page 2 of 4
EECE#: EDM 07-42
Geitzen Addition
1. It appears that the house is going to be completely demolished and a new complete
house is going to be built. Please verify on response and modify the drawings to
show all constructions requirements...
2. The current drawings are noted to use the IBC 2003. This is not the adopted code
as of July 1 2007. Modify the drawings per the IBC/IRC 2006.
Design analysis used for wind design 10.6 psf. This is not correct based off the
roof slope. Modify the analysis and drawings accordingly for the correct wind force
applied over this structures. ASCE 7-05 Figure 6-2.
4. Engineer of Record (EOR), the bending stressed used for the sawn lumber beams
was 1250 psi. Please clarify how the allowable bending stress to use for 4x8 and
4x10 was determined. This does not match the NDS adopted values. (Note also the
allowable shear stress used is not correct but it is conservative to use an Fv of 75
psi) NDS table 4A
5. Vertical distributions for the lateral design are per the UBC and not the ASCE 7-
05. This has been modified from the lateral distribution used per the UBC.
Resubmit analysis per the adopted code at this time. ASCE 12.14.8.2
6. Please add dimensions at locations of the columns. This should not be scaled but
should be clearly specified on the drawings.
7. EOR, please clarify how the tributary height of the wall lateral was determined.
Based off the drawings it appears not to be correct. The cross sections clearly show
8'upper floor and 9' on the lower floor with 1' in-between. Please modify lateral
analysis accordingly.
Sheet 2 AS built
8. Please add dimension on this sheet to show the as built locations. It is not clear
what is going to be removed and what is going to be added or add to the drawings a
demolition plan. It is not clear all load paths that have been accounted for, based
off the drawings submitted. More new framing may be required or verified based
off this being submitted.
Sheet 5 Foundations and Main floor Framing Plan
9. EOR, please submit analysis for the alternated details shown on this sheet.
10. Please specify the required epoxy and embedment of the #4 dowels epoxy into the
wall. Nothing is specified on the drawings except the note to "epoxy grout typ."
Page 3 of 4
EECE#: EDM 07-42
Geitzen Addition
11. EOR, please specify the required connection of the 4x10 to the exterior wall at the
new crawl space.
12. Submit analysis for the continuous footing to support the design loads at the
garage.
Sheet 6 Upper Floor Framing Plan
13. Design analysis for the beam E appears not to include the point load of the girder
beam. Please clarify on response.
14. Please specify the required connection of the 6X8 beam to the house at the entry.
15. Provide analysis for the built up beam connections. This does not match the IRC
table R602.3.
16. Please add the pertinent information for IRC table 602.3. This has been revised for
typical framing and should be added to the drawings. WSA R602.3
17. Please specify the number of stud columns under the girder beams and provide
analysis.
18. It appears based off the drawing the shear wall will not meet the minimum height
to width requirements as per the code. I had to scale the drawings since there is no
dimension shown. Please clarify on the response.
19. Please provide details for the construction of the new deck.
Sheet 7 Roof Framing
20. The building code does not allow nailing of 2" OIC to be used for 2" nominal
member. Please modify accordingly. IBC table 2306.4.1 footnote e.
21. Please specify the required connections of the 4X12 beam to the girder truss.
22. EOR, please specify the required collector element to the interior shear wall. There
is no way for the lateral load to be transferred to these walls at this time. Please
drawings modify accordingly.
23. EOR, please provide detail and analysis for the support of the girder truss. Truss
manufactures do not supply this. Please add this to the drawings.
24. EOR, please specify the required connection of the beam to the supporting post. It
is not clear the required support or the connections to be used. Please modify
accordingly.
Page 4 of 4
EECE#: EDM 07-42
Geitzen Addition
25. EOR, submit analysis for the 6x12 supporting the girder truss.
26. EOR, specify the required connections of the girder truss on the drawings. Nothing
is specified to support the required forces.
27. EOR, please provide a detail for the interior shear wall to the structures. Nothing is
specified at this time.
28. EOR, please specify the required connections of the new 6x10 to the main house.
Sheet 8 Elevations
29. Railing sections: EOR, submit analysis for the railing sections connections to resist
the code required forces.
Sheet S 1 Structural Details
30. EOR, please reference where each detail shall be used on the framing plan. This
should not be left up to the contractor.
31. Detail 3: EOR, submit analysis for the H2.5 to resist the uplift forces.
32. Detail 6: U hanger required full depth blocking. Modify detail accordingly.
Simpson Hanger option Matrix
Sheet S2 Structural details
33. EOR, please reference where each detail shall be used on the framing plan. This
should not be left up to the contractor.
34. EOR, the details are not referenced to the drawings and are unreadable. Please
modify in order to read all pertinent information's.
Additional corrections may be required following receipt of corrections and additional
information as requested.
Your plans are being reviewed concurrently with the Building Department, Fire
Department, Zoning Department and Public Works Engineering. Changes, clarifications
or additional corrections may be required subsequent to the Building Department plan
review when comments are received from the other concerned departments.
Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874-
0562 between 8:00 a.m. and 5:00 p.m.
By:
Hoyt Jeter, P.E.
President
/tic_ 1S9v
CITY OF EDMONDS
121 5TH AVENUE NORTH • EDMONDS, WA 98420 • (425) 771-0224 -FAX (425} 771-0221
Website: wwwaedmonds.wa-us
DEVELOPMENT SERVICES DEPARTMENT
Planning • Building • Engineering
August 27, 2007
Scott Delap Construction
3517 95t` Place Southeast
Everett, Washington 98208
RE: 8715 Talbot Road, Edmonds
Building Permit BLD20061215
VIA FACSIMILE
To Whore It May Concern:
GARY HAAKENSON
MAYOR
On friday August 24, 2007 my office was informed by the Public Works Department that the
referenced residence was nearly completely demolished. A check of City permit records
confirmed that the residence was to only be partially demolished.
This morning a STOP WORK order was issued to the project for demolition work exceeding the
approved plans. By way of this letter the homeowner is instructed to STOP WORK and
resubmit complete construction plans showing all required reconstruction for City review and
approval.
Please note the following issues that may now have to be addressed since the scope of work has
changed:
• Storm Drainage requirements (contact Jaime Hawkins, Engineering Technician)
• Setback requirements (contact Jen Machuga, City Planner)
• The existing construction to remain must be inspected by the structural engineer of record
and justified for the proposed addition/remodel (contact Jennifer Readwin, Plans
Examiner)
If you have any questions regarding the STOP WORK please feel free to contact my office
during City business hours at 425-771-0220 extension 1226.
Sincerely,
Jeannine L. Graf
Building Official
Cc: Daniel & Terri Gietzen
Incorporated August 11, 1890 '