20071024082032.pdfSTAFF: Ann Bullis, Assistant Building Official RE: Project: 20728 76th Ave W Murphy Townhomes A preliminary review was done with the pre -application materials provided (site plan and front elevation view only) and we have the following comments. Below are comments in general for the project, as well as those specific to either the TRC or IBC, depending on which code is used for design of this project. General Comments: 1) Codes in effect at the time of this meeting: a) 2006 International Building Code (including Accessibility) with State Amendments b) 2006 International Residential Code with State Amendments c) 2006 International Mechanical Code (including International Fuel Gas Code) with State Amendments d) 2006 International Fire Code with State Amendments e) 2006 Uniform Plumbing Code with State Amendments f) 2006 Washington State Energy Code (WAC 51-11) g) 2006 Washington State Ventilation Indoor Air Quality Code (WAC 51-13) h) Edmonds Community Development Code 2) Basic Design Loads specific to Edmonds a) Snow load 25 psf — nonreducible b) Seismic design category D (D2 for IRC) c) Wind speed 85 mph, 3 sec gust d) Wind exposure B (207th and 76th location) 3) List all deferred submittals on the cover sheet of the plans. The City prefers that mechanical and plumbing plans be included with and issued with the main building permit to help avoid any construction delays, however they can be deferred. Other common deferred items are fire sprinkler, fire alarm, signs, side sewer, water meter, shop drawings, State electrical, State elevator, etc. 4) A soils report prepared by a State Licensed Geotechnical Engineer is required. 5) Sleeping rooms must be provided with egress windows. 6) Smoke detectors are required in each sleeping room, in each area accessing a sleeping room and on each floor. They must be hardwired with battery back-up and interconnected. Building Division Pre -application Comments 1 oY City of Edmonds PRE -APPLICATION COMMENTS BUILDING DIVISION DATE October 25, 2007 STAFF: Ann Bullis, Assistant Building Official RE: Project: 20728 76th Ave W Murphy Townhomes A preliminary review was done with the pre -application materials provided (site plan and front elevation view only) and we have the following comments. Below are comments in general for the project, as well as those specific to either the TRC or IBC, depending on which code is used for design of this project. General Comments: 1) Codes in effect at the time of this meeting: a) 2006 International Building Code (including Accessibility) with State Amendments b) 2006 International Residential Code with State Amendments c) 2006 International Mechanical Code (including International Fuel Gas Code) with State Amendments d) 2006 International Fire Code with State Amendments e) 2006 Uniform Plumbing Code with State Amendments f) 2006 Washington State Energy Code (WAC 51-11) g) 2006 Washington State Ventilation Indoor Air Quality Code (WAC 51-13) h) Edmonds Community Development Code 2) Basic Design Loads specific to Edmonds a) Snow load 25 psf — nonreducible b) Seismic design category D (D2 for IRC) c) Wind speed 85 mph, 3 sec gust d) Wind exposure B (207th and 76th location) 3) List all deferred submittals on the cover sheet of the plans. The City prefers that mechanical and plumbing plans be included with and issued with the main building permit to help avoid any construction delays, however they can be deferred. Other common deferred items are fire sprinkler, fire alarm, signs, side sewer, water meter, shop drawings, State electrical, State elevator, etc. 4) A soils report prepared by a State Licensed Geotechnical Engineer is required. 5) Sleeping rooms must be provided with egress windows. 6) Smoke detectors are required in each sleeping room, in each area accessing a sleeping room and on each floor. They must be hardwired with battery back-up and interconnected. Building Division Pre -application Comments 1 7) Complete the City's Residential Energy and Ventilation Worksheets and submit with your permit application. _ 8) These buildings are subject to EHB 1848 (see attached bulletin). If the buildings will house condominiums, building enclosure documents stamped/signed by a State licensed Architect or Engineer are required, and special inspection is required of the installation of the building enclosure elements. If these building will be apartments, building enclosure documents are required OR ,Sale Prohibition Covenants must be submitted for each building prior to issuance of the building permits (City will provide covenant form). 9) Caution on encroachment of patios and decks in the setback area. Contact Planning Division for code requirements. 10) Plans must be stamped by a State licensed Architect or Professional Engineer. 11) Contact Steve Fisher, Recycling Coordinator, at 425-771-0235 regarding dumpster enclosure location and size. 12) Contact Linda McMurphy, Cross -connection Control Specialist, at 425-771-0235 regarding premise isolation requirements to protect the public water system. Comments specific to the International Residential Code 13) Townhouses must be separated from each other in accordance with IRC R317.2 (also see State Amendments), with either construction of two 1 -hour rated exterior walls, or one common 2 - hour rated wall. Provide construction details from the foundation through the roof showing compliance, continuity, and listed and tested fire rated assembly(ies). 14) Buildings containing more than 4 dwelling units must be provided with an automatic sprinkler system (NFPA-13R) with fire alarm for monitoring purposes. 15) Buildings containing 4 or more dwelling units must be accessible (IRC R322), including but not limited to Type B dwelling units, accessible parking, building/unit entrance, maneuvering distances, pedestrian access from the public sidewalk, mailboxes, accessible route through site, etc. Provide details showing compliance. 16) Walls separating dwelling units must have a Sound Transmission Class (STC) of 45 or more. Appendix K Comments specific to the International Building Code 17) Provide allowable area calculations for each building. 18) Specify occupancy (R2 dwelling with U private garage) and Type of Construction (VB assumed for this review). 19) Automatic sprinkler system required (NFPA 13R) with fire alarm for monitoring purposes. 20) Townhouses must be separated from each other with a 1 -hour rated fire partition (IBC 708). Provide construction details showing code compliance, including listed and tested fire rated assembly(ies). 21) The each garage must be separated from its associated dwelling in accordance with IBC 406.1.4, including self-closing, self -latching door. 22) Walls separating dwelling units must have a Sound Transmission Class (STC) of 50 or more. IBC 1207 23) The building and site must be accessible including but not limited to the building/unit entrance, maneuvering distances, parking, pedestrian access from the public sidewalk, Building Division Pre -application Comments 2 mailboxes, accessible route through site, etc. Provide details showing compliance. All units must be Type B accessible. FREQUENTLY OVERLOOKED ITEMS The following is a list of frequently overlooked items that apply to many projects. They are listed as a tool to help minimize corrections required during plan review. General • Incomplete submittals, insufficient number of copies, plans not separated out • General coordination of all plans not done prior to permit submittal nor throughout resubmittals (architectural, structural, landscape, civil, mechanical, plumbing, fire sprinkler, etc.) Overall coordination of plans with details clearly and accurately referenced throughout the plans as to where they apply. For example, a fire rated wall must be clearly identified and refer to a construction detail that accurately describes how the wall is to be constructed so it meets the listed and tested assembly requirements, including insulation for sound transmission control if applicable. • Deferred submittals and separate permits not called out on plans • Site plan, landscape plan and civil plan not to same scale --usually a vast difference between landscape plan and civil for parking space width, planters, patios, driveway width, location of electrical equipment, parking spaces, etc. • Shoring plan not submitted with initial application or submitted very late in the process; plans show shoring extending onto adjacent private property or into City RW • Energy calculations deferred to mechanical permit submittal, energy submitted late which affects framing approval • Allowable area calculations not provided with permit application, yards on site plans not adequately shown • Fire hydrant locations not specified at pre -application meeting • Structures that require a permit are shown on landscape plans not on architecturals • Stairs, landings, walkways, ramps not shown on site plans • Garage headroom to obstructions such as sprinkler heads, pipes, ducts, beams, insulation Fire Resistive Construction • Fire ratings and locations of required occupancy separations, fire walls, horizontal separation walls, exit passageways, corridors, exterior walls, etc not clearly specified on floor plans and in section views • Listed and tested fire -rated assemblies not specified on plans and do not match construction details • Listed and tested fire -rated assemblies and details showing structural frame protection (such as for columns and beams) not provided on plans, including those within wall and floor -ceiling assemblies • Fire -stopping details and products not specified on plans • Fire rated corridor detail not provided • Column jacketing in parking garage to protect fire -resistive covering from damage Building Division Pre -application Comments 3 Mechanical/Plumbin • Locations of all fire/smoke dampers not shown on mechanical plans • Routing of exhaust ducts, dryer vents, gas appliance vents, HVAC ductwork not coordinated prior to issuance of main permit • Locations and construction details of all mechanical shafts not provided on plans • Mechanical exhaust outlet locations, especially for parking garage exhaust not shown on floor plans, roof plans, sections and elevations (generator location not approved by ADB and placed in setback areas) • Appropriate cross -connection control devices provided at the property line on domestic water line, fire sprinkler line, and irrigation line. • Appropriate cross -connection control devices provided on fixtures within the building. Exiting • General exiting configuration not submitted at pre -application -meeting, creates redesign in many cases • Exit enclosure must exit directly to the outside or to an exit passageway • Elevators not permitted to open into exit passageways, lobbies not provided when required • Occupant load calculations not included with permit application Accessibility • Accessible signage location and details not provided on plans • Accessible means of egress and areas of refuge not shown on plans • Length and width of accessible parking space not shown on plans • Accessible cross walk not provided with in route of gavel when crossing vehicular drive aisles • Accessible route of travel not complete nor adequately detailed on the plans. For example, from the public way (sidewalk) to the main building entrance, from the accessible parking space(s) to the building entrance, to mailboxes, dumpsters, and accessory buildings, and throughout building. Detail ramps, slopes, handrails, landings, width of path of travel, etc. Building Division Pre -application Comments 4 , Multi -Unit Buildinq Permits ATTENTION: Developers of Condominiums and Multi -Unit Buildings Engrossed House Bill 1848, an act relating to managing construction defect disputes involving multi -unit housing is effective August 1, 2005. The Act affects all multi -unit buildings containing more than two dwelling units including commercial mixed-use buildings containing more than two dwelling units. This Act is applicable to all permit applications issued August 1 2005 or later regardless of the original permit submittal or application date. The following classes of buildings are not subject to this Bill: Hotels/Motels •. Dormitories Care Facilities Floating homes -.• A building containing attached dwelling units that are each located on a single platted lot A building in which all of the dwelling units are held under one ownership and is subject to a recorded irrevocable Sale: Prohibition Covenant. What this means to the applicant at permit submittal. All permit applications for construction or rehabilitative construction of multi -unit buildings must include building enclosure design documents and details (prepared and stamped by a State licensed Architect or Engineer) that identifies the building enclosure construction including but not limited to; waterproofing, weather proofing and/or other protection from water or moisture intrusion. This requirement may be waived if a recorded irrevocable Sale Prohibition Covenant is submitted with the permit application. ✓ Rehabilitative Construction means construction work on the building enclosure of a multi -unit residential building if the cost of such construction work (based on a licensed contractors bid including labor and materials) is more than 5% of the assessed value of the building (assessed value is determined from the Snohomish County Assessors website). ✓ Building Enclosure means that part of any building, above or below grade, that physically separates the outside or exterior environment from interior environments and which weatherproofs, waterproofs, or otherwise protects the building or its components from water or moisture intrusion_ Interior environments consist of both heated and unheated enclosed spaces. The building enclosure includes, but is not limited to, that portion of roofs, walls, balcony support columns, decks, windows, doors, vents, and other penetrations through exterior walls, which is waterproof, weatherproof, or otherwise protect the building or its components from water or moisture intrusion. ✓ Building Enclosure Design Documents means plans, details, and specifications for the building enclosure that have been stamped by a licensed architect or engineer. The documents shall include details of flashing, intersections at roof, eaves or parapets, means of drainage, water -resistive membrane and details around openings. ✓ Sale Prohibition Covenant means a recorded covenant that prohibits the safe or other disposition of individual dwelling units as or as part of a condominium for five years or more from the date of first occupancy_ The covenant must be recorded • What this means to the City. Effective August 1, 2005, the City is prohibited from issuing a permit for construction or rehabilitation/repair construction unless proper building enclosure documents and details are provided including a stamped statement by the Architect or Engineer indicating; "The undersigned has provided building enclosure documents that in my professional judgment are appropriate to satisfy the requirements of EHB 1848 Sections 1 through 10 of this Act" (unless a covenant is provided as described above.) • Inspection requirements. All multi -unit buildings shall have the building enclosure progress inspected by a Qualified Inspector during the course of construction and during rehabilitative or repair construction. The Qualified Inspector is a third party independent inspector paid by the applicant. The architect or engineer of record is permitted to be the Qualified Inspector. IN Final occupancylapproval conditions. The City is prohibited from issuing a Certificate of Occupancy or granting final project approval until the Qualified Inspector has submitted field reports including a final report certifying that the building enclosure has been properly inspected during the course of construction or rehabilitative construction/repair, and that the work is in substantial compliance with the building enclosure design documents. The City is not responsible for determining whether the building enclosure design documents or the inspections performed are adequate or appropriate to satisfy the requirements of the Act. For a complete copy of EH13 1848: http,/lwww.leg.wa.govipub[billinfol2005-06/Htm/Bills/House°/a20Passed%2OLegislatu re/l 848.PL.htm