Re: Building Permit Application: BLD20070536
Site Address: 8410 Main St, Edmonds
Expiration Date: November 16, 2007
Dear Mr. Kwon:
The purpose of this letter is to inform you that the above referenced permit application
will expire November 16, 2007. According to Edmonds Community Development Code
Chapter 19.00.005(A)(5), applications are only valid for a period of 180 days unless a
written request for extension is submitted to the Building Official. If an application
extension is granted it may only be extended for an additional 180 days for a total period
of one year. To extend the subject permit application you must submit a request in
writing to the Building Official prior to the referenced expiration date.
Please be advised, once a permit application expires, the application materials and plans
on file with the City will be destroyed within ten working days. Also, if you wish to
pursue the project in the future a new permit application and new fees will be required.
Also, please respond to the attached comments from Eagle Eye Consulting Engineers,
P.S. dated November 1, 2007.
If you have any questions, please feel free to call our offices at 425-771-0220.
Sincerely,
Marie Harrison
Senior Permit Coordinator
Cc: File
L17'emp\DST'slMaster LetterslApp Due to expire l0/21/00
' Incorporated August 11, 1890 0
Eagle Eye Consulting Engineers, P.S.
PO Box 523 /J_'d
Olal[a, WA 98359
hoytjeter@centurytel.net
360 874 0562
Fax 360 874 0591
To: Marie Harrison
121 5th Avenue N
Edmonds, WA 98020
Re: Kwon Date: November 1. 2007
8410 Main Street
Edmonds, WA 98020
Plan Review # 2007-0536 EECE # EDM 07-20 (2)
Second Comment letter
The above referenced project is in the process of plan review for compliance with
Edmonds ordinances and applicable codes. The following comments,
deficiencies/corrections must be addressed prior to completion of plans review and
subsequent issuance of permits.
Provide revised plans and calculations along with a written response to each of the items
listed below to facilitate a shorter back -check time.
SCOPE OF REVIEW
The scope of this review is for the Structural requirements of this project.
All features were checked only to the extent allowed by the submittals provided. All
portions of this project are assumed to meet or will meet other departmental requirements,
conditions and concerns before permit approval.
STRUCTURAL COMMENTS
General
1. The new analysis submitted is designed per the 2006 IBC requirements, and not the
2003. This structure is vested under the 2003 IBC and must meet these provisions.
If you want to resubmit the analysis and drawings under the new adopted code at
this time then this must be approved by the building department and may require a
new permit application and completely new review.
2. 1. The drawings do not specify the height of the walls on the drawings. Please add
this in order to complete the review. This has still not been addressed at this time.
Please add this information to the drawings.
Page 3 of 3
EECE#: EDM 07-20 (2)
Kwon Residence
9. 9. EOR the drawings are showing addition forces are being added to the open web
trusses due to the braces being added. Suhnzit analysis to justify the existing 14"
WEB truss will resist this force. This still has not been addressed at this time. This
is required to be submitted to justify. TBC 1604.4
Additional corrections may be required following receipt of corrections and additional
information as requested.
Your pians are being reviewed concurrently with the Building Department, Fire
Department, Zoning Department and Public Works Engineering. Changes, clarifications
or additional corrections may be required subsequent to the Building Department plan
review when comments are received from the other concerned departments.
Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874-
0562 between 8:00 a.m. and 5:00 p.m.