20071127100125.pdfflF City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
i (425) 771-0220
ES t. 189
DATE: November 27, 2007
TO: Sara Winters
1138 6th Ave S
Edmonds, WA 98020
FROM: Jenny Readwin, Plans E amin
RE: Plan Check # 2007-1148
Project: Interior Remodel
Project Address: 1138 6t" Ave S.
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) An additional smoke detector is required outside bedroom 1. note on plans.
2) Label egress window in bedroom 1.
3) New French door addition to bedroom 2 does not meet conventional wall bracing of IRC. Revise
to meet conventional or provide lateral calculations stamped and signed by a Washington State
Licensed Professional Engineer.
4) Provide general roof framing plan to show that all walls being removed are non-bearing. I see
existing rafter location in Bedroom 2 but what happens over the bathrooms and bedroom 1? If
any new beams are proposed show size and location on the plans as well as clearly show how all
loads are carried to bearing and provide beam calculations.