20071128133551.pdfOV EDo City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION Fs. lggo (425) 771-0220 DATE: November 28, 2007 TO: Eric Sundquist Fax 425-774-6315 FROM: fenny Readwin, Plans Emin RE: Plan Check # 2007-0767 Project: SFR Project Address: 23565 74h Ave W During re -review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Ok 2) 11/28/07 Response said Soundview Plumbing will be installing an air administrating valve. This is not a conventional method of venting. Still need. Show how island sink will be vented through the roof or with a loop vent as permitted by UPC 909.0.Air admittance valves are not permitted unless first approved by the Building Official under and alternate method per UPC 301.2. 3) ok 4) ok 5) 11/28/07 Will need before permit is issued. Special inspections are required for the following. Complete the enclosed special inspection agreement signed by the owner, the general contractor and the special inspector and submit to the City for approval prior to issuance. • Excavation, grading, & site preparation • Soil bearing verification • Placement of fill & compaction • Proof Rolling • Subsurface drainage installation including footing drains. • Temporary and final erosion Control • Site retaining wall/ rockery construction. • Final letter from geotechnical engineer of record 6) 11/28/07 See attached comments. See attached structural comments from city consultant. Respond to each item in writing. r t Eagle Eye Consulting Engineers, P.S. PO Box 523 Olalla, WA 98359 "^ hoytjeter@centurytel.net 360 874 0562 Fax 360 874 0591 To: Theresa Umbaugh 121 5th Ave. N Edmonds, WA 98020 Re: Sunquist Residence Date: November 12, 2007 23565 Sunquist Ave. W Edmonds, WA 98020 Plan Review 4 2007-0767 EECE ## EDM 07-57 Structure Area S.F. Main floor 1717 Second floor 1797 Total 3514 Garage 708 Total 4222 Deck 360 Grand total 4582 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the Ordinance, Structural, V&IAQC and Enemy requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. STRUCTURAL COMMENTS General Page 2 of 3 EECE#: EDM 07-57 Sunquist Residence 2007-0767 1. These drawings appear to be per the 2003 code and not the 2006 code as adopted by the state of Washington July 1, 2007. Please modify the drawings to reflect the state adopted code. For example, the general notes clearly reference the 2003 IRC. Sheet A3 Detail Sheet 2. Detail 8: Engineer of Record (EOR), please specifies the required ledger bolts. The detail states per plan but I was unable to find where this information was specified. Please add this information to the drawings in order to check ledger capacity. Also, submit an analysis for this connection. R502.2.2 Sheet A4 Foundations Plan & Main Floor Framing Plan 3. EOR, please provide a detail at the locations where there is (3) 4x4 post. It is not clear how this will be built based off the drawings. The plywood will not support the design forces. Please add a detail at this location. Sheet A5 Main Floor Plan & Upper Floor Framing Plan 4. EOR, please provide a detail at the locations where there is (3) 4x4 post. This is located where beam UO2, U41 and U07 frame into each other at the family room. It is not clear how this will be built based off the drawings. The plywood will not support the design forces. Please add a detail at this location. 5. AOR/EOR please specify the required spacing of the vertical deck guard post. As noted in detail 81A3. Detail 8 on sheet A3 states 4x4 POST per plan. This information is needed in order to check the connections and member capacity. Please add this to the drawings. ORDINANCE COMMENTS General 6. These drawings appear to be per the 2003 code and not the 2006 code as adopted by the state of Washington July 1, 2007. Please modify the drawings to reflect the state adopted code. Sheet A6 Upper Floor Plan 7. Please note the window in bedroom 3 shall have a net opening width 20" clear for egress. It appears based off the drawings this will not be met. Please modify accordingly. 8310 ENERGY COMMENTS Page 3 of 3 EECE#: EDM 07.57 Sunquist Residence 2007-0767 Sheet Al General Notes 8. Please modify the energy code table to the adopted code at this time. The state energy code is 2006 editions adopted July 1 2007. Additional corrections may be required following receipt of corrections and additional information as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 574-0562 between 5:00 a.m. and 5:00 p.m. By. �'� Hoyt Jeter, P.E. President