y; : PLAN REVIEW COMMENTS
.y BUILDING DIVISION
�Sr t8go (425) 771-0220
DATE: January 8, 2008
TO: Jeff and Vicki Menna
vicki@vickimenna.com
FROM: Jenny Readwin, Plans Ex ner
RE: Plan Check # 2008-0011
Project: Interior Remodel
Project Address: 12617 1h Place S.
During review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) Smoke detectors are required in each sleeping room as well as in the hallway outside each
separate sleeping area. Show location of existing and proposed smoke detectors.
2). Minimum 100 e n fan is required over the stove. Please note on plans.
3) Provide general roof framing plan to show what loads are being supported by the proposed
beam.
4) Provide calculations for proposed 4x12 beam and show how all loads are carried to bearing. It
appears that it will be supported by the 6x10 beam below. If this is the case, provide calculations
for this beam as well to justify that it is adequate to support the new point load locations.