20080108150035.pdfoV CDS City of Edmonds y; : PLAN REVIEW COMMENTS .y BUILDING DIVISION �Sr t8go (425) 771-0220 DATE: January 8, 2008 TO: Jeff and Vicki Menna vicki@vickimenna.com FROM: Jenny Readwin, Plans Ex ner RE: Plan Check # 2008-0011 Project: Interior Remodel Project Address: 12617 1h Place S. During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the items below to a Permit Coordinator. 1) Smoke detectors are required in each sleeping room as well as in the hallway outside each separate sleeping area. Show location of existing and proposed smoke detectors. 2). Minimum 100 e n fan is required over the stove. Please note on plans. 3) Provide general roof framing plan to show what loads are being supported by the proposed beam. 4) Provide calculations for proposed 4x12 beam and show how all loads are carried to bearing. It appears that it will be supported by the 6x10 beam below. If this is the case, provide calculations for this beam as well to justify that it is adequate to support the new point load locations.