PLAN REVIEW COMMENTS
BUILDING DIVISION
ESQ. i s9° (425) 771-0220
DATE: January 28, 2008
TO: Kurt Schlichting
Kurt. schlichting@yahoo.com
FROM: Jenny Readwin, Plans Eaurin
RE: Plan Check ## 2008-0012
Project: Whitsman Interior Remodel
Project Address: 8307 188th Street SW
During re -review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) 1128108 Please note this information on the plans. Note garage/dwelling separation on plans.
Minimum %2" sheetrock required on garage side of wall and 5/8" type X on the ceiling when
there is habitable space above and minimum 20 minute rated or 1 3/8" solid core door.
2) 1128108 A continuous foundation is still not shown on the detail and is required by code for
all exterior walls. Provide a section detail through old garage door/new window from
foundation through the roof. Per R403.1 all exterior walls must be supported on a continuous
foundation. Show how wall is supported and how it is protected form weather at the base.
3) ok
4) ok.
5) ok
6) 1128108 The Building Official is willing to accept upgrading ceiling insulation to R-38
throughout the existing house in lieu of R-30 floor insulation. If this is chosen then it must
be complete by final of this permit and noted on the plans. Heated space requires minimum R-
30 floor insulation or R-10 under slab insulation. Specify how the minimum floor insulation will
be obtained or a component performance analysis will be required (see item 5 above).
7) .128108 Please note this information on the plans. Because this room has a closet it is
considered a sleeping room. Window must meet egress and a smoke detector is required inside
the room and in the hall outside. Please note on plans.