PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: February 14, 2008
TO: Howard Chermak
howard@chermak.com
FROM: Jenny Readwin, Plans Ex ner
RE: Permit # 2007-1083
Project: Revision
Project Address: 1214 11" Place N
During review of the above noted revision, it was found that the following information, corrections,
or clarifications are needed.
1) Plans still show a sliding glass door and landing off the East side of the storage addition but the
site plan does not show the landing. Based on my conversation with Ed Sibrel nothing is
permitted to encroach in that area not even a step or landing. Also, when the addition was in line
with the existing house it meet conventional wall bracing because the existing wall was taken
into consideration. Now that it is inset it no longer meets conventional wall bracing. Some
options would be to replace the door with a window and provide later calculations stamped and
signed by a Washington State Licensed Professional Engineer or Relocate door/window to
another wall where it would meet conventional construction or eliminate all together.