}w}:?sā`:`ā. PLAN REVIEW COMMENTS
- BUILDING DIVISION
st, i s9° (425) 771-0220
DATE: February 27, 2008
TO: Joe Myers
joemyersconstraction@comeast.com
FROM: Jenny Readwin, Plans Eaurin
RE: Permit # 2008-0026
Project: Revision
Project Address: 8723 Talbot Rd.
During review of the above noted revision, it was found that the following information, corrections,
or clarifications are needed.
1) Please revise building section on sheet 2 to match actual conditions (i.e. footing supporting 4x4
post at the existing foundation wall, direction of floor joist, etc.).
2) 6x10 beam for crawl space access does not reflect actual construction. The existing foundation
all at this location, per my site visit, was about 2'-3' high and was all open into the crawlspace
area. Please show beam for this area to completely support the floor joist and provide beam.
calculation.
3) Please show 2x10 floor joists extending all the way to the 4x10 at the fireplace.
4) Plans show 4x10 at the fireplace between the two footings but how will the floor joists be
supported on the other sides of that beam? If the beam extends to the exterior wall and to the
beam past the furnace please show it as well as how it is carried to bearing at each end (i.e.
hangers at the furnace side and post and footing the other).
5) For the 6x10 in the middle please show how it extends or how the floor joists are supported by
the water heater. If beam extends and hangs off the other beam please specify hanger.
6) Please specify size of the beam that runs the same direction as the floor joist near the storage
area and provide calculation including point loads if the 6x10 and 4x10 beams are hanging from
them.