2008-0257 Sound Transit-Edmonds Station.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: November 19, 2009
TO: Andrea Clinkscales, Sound Transit
Andrea.clinkscales@soundtransit.org
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2009-0257
Project: Edmonds Station
Project Address: 209 West Dayton St
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can be found
on the plans, and submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. Thank you.
1.
Not all sets of the Civil and Structural plans are signed. Please have the appropriate design
professionals sign the plans.
2.The plans show two waiting shelters in the bus loading area (sheet PV3) in addition to the
four platform shelters shown. Please include plan views of these two shelters in the
architectural and site plan drawings, not just the civil drawings. Also, revise the Project
Information section on sheet AZ1.4 to represent all six structures.
3.At the south platform ramp, a handrail is required on both sides of the ramp. 12 inch
extentions are required at top and bottom of the handrails. See sheet AU1.1. IBC 1010.8 and
1012.5. Please note that neither the top or bottom handrail extensions shown on sheet A4.4
comply with section 1012.5. For reference, see previously submitted sheet A4.4 dated
6/6/08.
4.At the south platform ramp, provide ramp edge protection details showing compliance with
IBC 1010.9.
5.At the mini high ramps shown on sheet A4.4, provide handrail extensions at the top and
bottom to comply with IBC 1012.5. Please modify all effected plan sheets and details
accordingly. See #3 above.
6.On sheet GD1, the ramp slope reads 12:1 MAX. Please modify to read 1:12 MAX.
Also, please add this same note at this ramp on sheet AU1.1.
7.On sheet STR1.3, it is noted for the (relocated) TVM shelter attachment to be the same as
existing. Provide construction and attachment details for the shelter on the plans.
8.Provide details for the TVM shelter to show how it meets the accessibility requirements of
ANSI A117.1 section 707.
9.Details 3 and 11 on sheet A6.3 do not apply to the TVM shelter as called out on A4.7. Please
delete references to these details.
10.Please be aware that upon the deferred submittal for signage, the platform signage will need
to comply with IBC E109.2.4.
Page 2 of 2