City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: October 22, 2008
TO: Warren LaFon
e-mail: warrenlafon@earthlink.net
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2008-0287
Project: Addition
Project Address: 547 Dayton St.
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to a Permit Coordinator. Redlining of
the plans will be allowed.
General:
1.Previous item 4: Please show on the floor plan the rating of the doors to the Storage Room,
indicating self-closing and smokeĀgasketed; and describe the construction of the walls to
achieve the smoke barrier per IBC 709.
2.Previous item 10: As per our discussion on 10/22/08, provide a letter stamped and signed by the
architect stating the entire building, as altered under this permit, will fully comply with current
accessibility codes as required by IBC 3409.7
Structural:
1. Previous item 5: Please provide dimensions for footings and foundation walls on applicable
details.
2. Previous item 7: Per our discussion, the 9 foot high parapet will not be used, and the 2 foot 3
inch parapet on the plans will be used. Thank you for your clarification.
3. Previous item 8: Per our discussion, the computer room will not need an upgraded design as the
computers will all be of the desktop variety. Thank you for your clarification.
4. Please indicate the extent of the coil strap at the second floor framing level. Clarify with the EOR
if this strap needs to extend over the shear walls below, and if so, how far?