Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
20080318095837.pdf
City of Edmonds <oo ' PLAN REVIEW COMMENTS BUFLDING DIVISION Esr g90 (425) 771-0220 DATE: March 18, 2008 TO: Atilla Hegyi 19620 81" Place W Edmonds, WA 98026 FROM: Ann Bullis, Assistant Building Official RE: Plan Check # 2007-0795 Project: Hegyi Remodel/Addition Project Address: 19620 81St Place W During re -review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Please resubmit to Theresa Umbaugh, Permit Coordinator. Applicable previous comments and worksheets referenced below are attached for your convenience. Previous correction 1 (references correction 3 of 1015/07 comments): a. Complete the enclosed Energy Worksheets for the kitchen addition and note all insulation R -values and window U -values on the plans. If the addition cannot meet prescriptive energy code requirements, construction must be revised to accommodate the minimum insulation values, or energy calculations using the Component Performance approach (WSEC Chapter 5) must be provided calculation forms and instructions can be found on the web at www.energy.wsu.edu). For example, 2x6 floor joists cannot hold R-30 batt insulation (minimum would be 2x10), however you may see if rigid insulation will meet this requirement. This will be same issue for 2x4 walls and 2x6 floor joists, and may also be an issue for window and skylight glazing. If any item of the prescriptive Table 6-1 cannot be met, energy calculations using the Component Performance approach will be required.. b. Show the kitchen addition on the site plan and note.the floor area. .2. Special inspection will be required for the installation of epoxy anchors that the structural engineer is requiring on the structural pians. Complete the enclosed Special Inspection and Testing Agreement and return to the City signed by all parties. The Special Inspector must either be WABO certified for reinforced concrete, or a State licensed Professional Engineer (such as your structural. engineer). CITY OF EDMONDS SPECIAL INSPECTION AND TESTING AGREEMENT The project at L�P 2� sI— j��. , {� . issued under building permit number -7- requires special inspection and/or testing per IBC Chapter 17. The complete list of special inspections .is attached to this document. BEFORE A PERMIT CAN BE ISSUED: The owner and contractor and special inspector shall complete this agreement and the attached structural test(s) and inspections schedule including the required acknowledgements. APPROVAL OF SPECIAL INSPECTORS: Each special inspector shall be approved by the Building Official prior to performing any duties or inspections. Each special inspector shall submit Statement of Qualifications to the Building Official for review_ Special inspectors shall display identification when performing special inspections on site. Special inspection and testing shall meet the minimum requirements of IBC Chapter 17 and the following: A. Duties and Responsibilities of the Special Inspector 1. Observe Work The special inspector shall observe the site work for conformance with the approved (stamped) pians and specifications and applicable workmanship provisions of the IBC. Architect or Engineer reviewed shop drawings may be used only as an aid to inspection_ Special Inspections are to be performed on a continuous basis—meaning that the special inspector is on site at all times observing the work requiring special inspection. Periodic inspections, if any, must have prior approval by the City based on a separate written plan reviewed and approved by the Building Official and the engineer or architect of record_ Report Non -conforming Items The special inspector shall bring non -conforming items to the immediate attention of the contractor and note all such items in the daily field report_ Any item not resolved in a timely manner shall be immediate cause of the special inspector to notify the Building Official of the plan deviation, error, change or omission. It shall also be the duty of the special inspector to promptly notify the engineer or architect. 3. Complete Daily Reports Each special inspector shall complete and sign both the special inspection record and the daily report form for each day's inspection. These records shall remain at the jobsite with the contractor for review by the City Building Inspector_ 4. Furnish Weekly Reports The special inspector or inspection agency shall furnish the City with weekly reports of tests and inspections. The project engineer or architect, and others as designated shall also be copied on reports_ Weekly reports must include the following: • Description of daily inspections and tests made with applicable locations • List of all non -conforming items • Report on status of non -conforming items (resolved or unresolved) • Itemized changes authorized by the Architect, Engineer and City if not included in non- conformance items. 5. Furnish Final Construction Report The special inspector or inspection agency shall submit a final signed report to the City stating that all items requiring special inspection and testing were fulfilled and reported. And, to the best of L_1TEMP1BUILDINGlSpeciatlnspectionAgreernentlBC.doc 7/04 his/her knowledge the project is in conformance with the approved plans and specifications, approved change orders and the applicable workmanship provisions of the IBC. Items not in conformance or unresolved items or any discrepancies in inspection coverage, (i.e., missed inspections, periodic inspection when continuous inspections were required, etc.) shall be specifically itemized in this report. B. Contractor Responsibilities 1. Notify the Special Inspector It is the duty of the contractor to notify the special inspector when work is ready for special inspection. Note, the items listed on the attached schedule and as noted on the approved plans and specifications are required to have special inspections. Adequate notice shall be provided by the contractor so that the special inspector has time to become familiar with the project_ 2. Provide Access to Approved Plans The contractor is responsible for providing the special inspector access to approved plans at.the jobsite. 3. Retain Special Inspection Records The contractor is responsible to retain at the jobsite all special inspection records submitted by the special inspector. These records are to be provided to the City building inspector upon request. C. City of Edmonds Buildinp_ Department Responsibilities 1. Approve special inspectors or inspection agencies The building department shall approve all special inspectors and special inspection requirements. 2. Monitor special inspection and approve weekly reports Work requiring special inspection and the performance of special inspectors shall be monitored by the City Building Inspector. His/her approval must be obtained prior to placement of concrete or other similar activities in addition to that of the special inspector. 3. Issue Certificate of Occupancy The Building Official may issue a Certificate of Occupancy after all weekly special inspection reports including the final report have been submitted and accepted. D. Owner Responsibilities The project owner or the engineer or architect of record acting as the owner's agent shall fund special inspection services. E. Engineer or Architect of Record Responsibilities The engineer or architect of record shall include special inspection requirements on the plans and specifications. ACKNOWLEDGEMENTS I have read and agree to comply with the terms and conditions ofthis agreement. Owner Special Inspector General Contractor City Building Official L_1TEMP113UILDINGiSpeciallnspectionAgreementtBC_doc 7/04 Date Date Date Date SPECIAL INSPECTION AND TESTING SCHEDULE REINFORCED CONCRETE, GUNITE, GROUT AND MORTAR - Concrete Ganite Grunt Mortar Apgrcgare Tests Reinforcing Tess mix Designs Rbuforcing Placement Batch Plantln;pcction Inspect Placiat Cast Sat ws Pick-up Samples Comp—sionTcsts PRECASTIPRESTRESSED CONCRETE ....a ,.A.cane rre�reas Aggrelrmc Tests Reaaforcing Tuts Tendon Trus Mix Dmiuns Reinforcing Placement Insert Placement Concrete Batching Cotnerttc Placement Installation Inscpaion Cast Samples Tests MASONRY_ T Special ImPcction Sucsses Used — Preliminary Acceptance Tests (Masonry Units. Wall Prisms) Subsequent Tests (Mortar_ Groat_ Field Wall Prisms) — Placements Inspection of Units BuuvavGrfw.�trrro. STRUCTURAL STEEEJWELDING: Sample and Ttu (list specific lumbers below) Shop Material Identification Welding Inspection O shop O Fuld Ultrasonic Inspection O Shop O Fuld high-strength Bolting Inspection O Shap O Field f] A325 ON OX OF O A490 Mcul Deck Welding Inspection — Reinforcing Steel Welding Inspection ; Metal SEW Welding Inspection Concrete Insert Wilding Inspection FIREPROOFING: — Placettww Inspection — Density Tests — Thickness Tuts — Inspect Batching INSULATING CONCRETE: — Sample and Test — Plammcm Inspection ___. unit Weights FILL MATERIAL: _ Acceptance Tests Placement Inspection .T.. Field Density STRUCTURAL WOOD: Shear Wall Nailing Inspection Inspection of Glu -lam Fab_ Inspection of Truss Joist F- b_ _ ADDITIONAL INSTRUCTIONS OR OTHER TESTS -- Sample Nest Components AND INSPECTIONS: Ferns c-npk-,d by: litre: Telephone No-_ Date_ City of Edmonds 7 = 9, .DT /-/ 7-af3 PLAN REVIEW COMMENTS /"7< ' DATE_ January 17, 2008 TO: Atilla Hegyi 19620 8l$t Place W Edmonds, WA 98026 BUILDING DIVISION (425)771-0220 FROM: Ann Bullis, Assistant Building Officia RE: Plan Check # 2007-0795 Project: Hegyi Remodel/Addition Project Address: 19620 81$` Place W During review of the plans for the above noted project, it was foun- clarifications or changes are needed. Provide written responses to changes can be found on the plans- Please resubmit to Theresa Uy 451114!5- 17V Y4U1 /e/V t the following information, comment and where rh, Permit Coordinator - 1. Regarding your request to defer response to previous item 3, 4 & 5 in Building Division plan review comments dated 10/5/2007, as explained in City letter dated 9124/2007, if you were unable to obtain City or County permit records for the kitchen addition, then the addition must be included with this permit. The Stop Work order will not be lifted until all issues are resolved and permit(s) issued- The design (structural and architectural) of the kitchen and remodel of the living/dining/den/entry area must be reviewed at the same time. For clarification to your statement in your response letter (dated January 10, 2008) regarding item 3g, the area of the kitchen addition shown the site plan approved for the roof cover (permit # 1998-0031) was labeled on the plan submitted to the City as "existing house", and in no way gave approval for the kitchen addition. 2. One set of the structural calculations/plans submitted to the City trust be wet signed by the engineer of record. Have the engineer include as part of his stamped/signed calcul dops : J! a. The full scope of his design, and /' � 7�4e /�>1 fav /Le1146iP/ 7— b. A reduced copy of the plans that support the structural design calculations (or he can stamp the project set of plans). As I explained at our previous meeting, the engineer will need fully dimensioned framing plans to scale to do the structural calculations, so item ##2 of the 10/5/07 comments is still required.. ���r� /•sem; � ,��/r�,. �����:--���/Xo�,6� �� -A' �- �//oo✓ GST 6, ZDU���.9�✓� t�d�t�✓�0✓rPGTIDr+U �3 �J, s oVE04o City of Edmonds � �, W.. PLAN REVIEW COMMENTS BUILD[NG DIVCS[ON (425) 771-0220 DATE: October 5, 2007 TO: Atilla Hegyi 19620 815" Place W Edmonds, WA 98026 FROM: Ann Bullis, Assistant Building Official RE: Plan Check #12007-0795 Project: Regyi Remodel/Addition Project Address: 19620 815` Place W During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed- Provide written responses to each comment and where changes can be found on the plans_ Please resubmit to Theresa Umbaugh, Permit Coordinator- 1- The structural calculations submitted with your 9/21107 resubmittal must be stamped and signed by a State licensed Professional Engineer (TRC 106.1) and contain minimum design information per BC Chapter l6. 2. As discussed at our meeting, please dimension the framing plan for the north half of the roof: Dimension the spans of all beams/headers and rafters, as well as the exterior walls (perimeter) of the building- Without this information the loads cannot be verified_ Also, note the scale of the plan such as V;'= l foot or 3/16" = 1 foot (currently it does not appear to be a recognized scale)_ This is required in the City's Addition/Remodel handout previously provided to you- 3- Kitchen addition (see attached handout): a. As noted in the Building Official's letter to you dated September 24, 2007, provide complete plans of the kitchen addition, including foundation, floor framing, elevation views, (roof framing already provided), and cross reference the building sections that you have drawn on the framing plans. Examples of plans and details can be found in the enclosed handout. b- Based on the section submitted for the Kitchen West Wall Load Path, the roof framing is non -conventional construction and does not meet the conventional provisions of IRC 802-3. Flans and structural calculations must be stamped and Osigned by a State licensed Professional Engineer. Complete the enclosed Energy Worksheets for the kitchen addition and note all insulation R -values and window U -values on the plans_ If the addition cannot meet current energy code requirements, construction must be revised to accommodate the minimum insulation values, or energy calculations using the Component Performance approach (WSEC Chapter 5) must be provided- For example, 2x6 floor joists cannot hold R-30 batt insulation (minimum would be 2x10), however you may see if rigid insulation will meet this requirement- d. Based on the floor plan, walls do not minimum bracing requirements of IRC 602.10 (also see State Amendtnents)_ Lateral calculations must be stamped and signed by a State Licensed Professional Engineer_ e. %' Anchor bolts gust be spaced no more than 6' o- c., located 12" of each end of each plate with minimum 7" embedment and 3"0" washers - f. Specify thickness of wall and roof sheathing, as well as nail spacing_ g. Note the kitchen addition on the site plan. Provide deck plans, including the roof cover over the deck. This must be included in this permit as well. See enclosed deck handout for minimum plaits and details. 4. Specify post and beam connections. 5- Alt wood in contact with concrete must be pressure treated or naturally resistant to decay (such as foundation redwood). Revise plans to show this where ever new members are being added. IRC 319.1. Page 2 of 2 city of edmonds development information Washington State Energy & Ventilation Codes Residential Compliance Worksheets Prescriptive Approach CODES: Edmonds Community Development Code Chapters 19.30 and 19.35 Washington State Energy Code 2006 Edition Washington State Ventilation & Indoor Air Quality Code 2006 Edition The purpose of the State energy code is to provide minimum standards for new or remodeled construction to achieve efficient use and conservation of energy_ This handout provides the basic minimum codes for prescriptive compliance_ The basic prescriptive approach for energy code compliance is the easiest way to determine or show code compliance. It is a straight takeoff and comparison of total window (glazing) and door opening area versus the heated floor space. The percentage of glazing shown on the enclosed charts determines the minimum U -value of all windows and doors for the project, and the insulation R -value for wall, floor, slab and ceiling insulation. This handout is intended to provide minimum prescriptive compliance and it is not intended as a substitute for the entire State Energy Code. Also included in this packet is a Ventilation; and Indoor Air Quality Worksheet. Tighter construction and insulation standards have introduced a vast amount of chemicals and other pollutants into dwellings. The process of natural ventilation has also been greatly reduced due to the required sealing of sheathing at walls and floor levels_ The State Ventilation and Indoor Air Quality Code (VIAQ) has been created as a means for bringing in fresh outdoor air, and exhausting interior stale air. The VIAQ code allows either a manual portal system or a mechanical system that runs unmonitored on a timer to convey the air. Forms and additional information about the State Energy and Ventilation Codes can be found on the WEB at www_energy_wsu.edu. PLEASE COMPLETE THE FOLLOWING ATTACHED ENERGY AND VENTILATION WORKSHEETS AND SUBMIT TWO (2) COPIES WITH YOUR BUILDING PERMIT APPLICATION. Revised 7107 o'V EDS o CITY OF EDMONDS ENERGY & VENTILATION sr 1 gV, RESIDENTIAL COMPLIANCE WORKSHEETS PRESCRIPTIVE APPROACH PLEASE COMPLETE THE FOLLOWING ENERGY AND VENTILATION WORKSHEETS AND SUBMIT TWO (2) COPIES WITH YOUR BUILDING PERMIT APPLICATION. DATE PROPERTY ADDRESS PROPERTY OWNER JOB TYPE ❑ New ❑ Addition ❑ Remodel (check all that apply) ❑ Single Family ❑ Multi -Family #Units HEATED FLOOR AREA Existing HEATING BY ❑ Gas SYSTEM TYPE PLAN REVIEW # ew ❑ Electric ❑ Other ❑ Forced Air Furnace ❑ Wall beaters ❑ Other, MAXIMUM GLAZING % Total Hydronic: Infloor ❑ Radiant ❑ FOR CITY USE ONLY DATE OF REVIEW COMPLIANCE OPTION WHOLE HOUSE VENTILATION SYSTEM TYPE: MANUAL PORT/WINDOW VENT WITH EXHAUST FAN INTEGRATED FORCED -AIR FURNACE 141116 10 I DI ST Revised 7107 2006 WSEC Chapter 6 Qualification Form- Zone I Residential Prescriptive (Chapter 6) Options For All Heat Sources Instructions: �arefully review the requirements for each of the options below. Choose an option that best suits your dwelling design- Glazing percentage typically determines which option to choose. Your building must match the selected option requirements without exceptions or substitutions. Disregard components or equipment that does not apply to your project. Your permit will be processed more efficiently if you provide all of the requested information. Department staff :an help you with general questions about this form. Proposed designs which cannot meet the specific requirements of a listed option above may calculate compliance by Chapter 4 or 5 of the 2006 Washington State Energy Code. Forms can be found on the WEB at WW W-ENERGY-WSU.EDU * Reference Case 0- Nominal R-valucs are for wood frame assemblies only or assemblies built in accordance with Section 601.1. L Minimum requirements for each option listed- For example, if a proposed design has a glazing ratio to the conditioned floor area of 13% it shall comply with all of the requirements of the 15% glazing option (or higher). Proposed design which cannot meet the specific requirement of a listed option above may calculate compliance by Chapter 4 or 5 of this Code. 2. Requirements applies to all ceilings except single rafter or joist vaulted ceilings complying with note 3. `Adv' denotes Advanced Framed Ceiling. 3. Requirement applicable only to single rafter or joist vaulted ceilings where both (a) the distance between the top of the ceiling and the underside of the roof sheathing is less than 12 inches and (b) there is a minimum I -inch vented airspace above the insulation- Other single rafter or joist vaulted ceilings shall comply with the "ceiling" requirements- This option is limited to 500 square feet of ceiling area for one dwelling unit. 4- Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as wall above grade- Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications- See Section 602.2 5- Floors over crawl space or exposed to ambient air conditions. 6. Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602-4- 7. Int. denotes standard framing 16 inches on center with headers insulated with a minimum of R-10 insulation- 8- This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing - 9. Doors, including all fire doors, shall be assigned default U -factors from Table 10-6C 10- Where maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value- Overhead glazing with U -factor of U=0.40 or less is not included in glazing area limitations. I I - Overhead glazing shall have U -factors determined in accordance with NFRC 100 or as specified in Section 502.1-5. 12- Log and solid timber walls with a minimum average thickness of 3-5" are exempt from this insulation requirement. This project will take advantage of the following exceptions to the prescriptive option: 0 602.6 Exception I - One door, that is 24 sq ft or less, that does not meet the standards is allowed. Location of door taking this exemption. 0 602.5 Exception 2. Doors with U -factor of 0.40 allowed without calculations, Option IV only- Location of door(s) taking this exemption_ GlazingU-Factor WaI14 Wai14 Option Glazing Area 10 Vertical Overhead" floor Ut z Ceiling Vaulted AboveWall int ext Floors Stab on % Of Floor Ceiling3 Grade 12 Grade Below Below Grade6 Factor Grade Grade I 10% 0.32 0.58 0.2 R-38 R-30 R-15 R-15 R-10 R-30 R-10 II* 15% 0.35 0-58 0.2 R-38 R-30 R-21 R-21 R-10 R-30 R-10 25% Group R -I and R-2 R-381 R-301 R-211 R-301 III 0-4 0-58 0.2 R-15 R-10 R-10 Occupancies U-0.031 U=0.034 U=0.057 U=0.029 Only Unlimited Group R-3 and .IV R-4 0.35 0-58 0.2 R-38 R-30 R-21 R-21 R-10 R-30 R-10 Occupancies Only Unlimited Group R -I and R-38 R-30/ R-211 R-301 V R-2 0.35 0-58 0-2 R-15 R-10 R-10 IU=0.034 U=0-034 U=0A57 U=0.029 Occupancies Only * Reference Case 0- Nominal R-valucs are for wood frame assemblies only or assemblies built in accordance with Section 601.1. L Minimum requirements for each option listed- For example, if a proposed design has a glazing ratio to the conditioned floor area of 13% it shall comply with all of the requirements of the 15% glazing option (or higher). Proposed design which cannot meet the specific requirement of a listed option above may calculate compliance by Chapter 4 or 5 of this Code. 2. Requirements applies to all ceilings except single rafter or joist vaulted ceilings complying with note 3. `Adv' denotes Advanced Framed Ceiling. 3. Requirement applicable only to single rafter or joist vaulted ceilings where both (a) the distance between the top of the ceiling and the underside of the roof sheathing is less than 12 inches and (b) there is a minimum I -inch vented airspace above the insulation- Other single rafter or joist vaulted ceilings shall comply with the "ceiling" requirements- This option is limited to 500 square feet of ceiling area for one dwelling unit. 4- Below grade walls shall be insulated either on the exterior to a minimum level of R-10, or on the interior to the same level as wall above grade- Exterior insulation installed on below grade walls shall be a water resistant material, manufactured for its intended use, and installed according to the manufacturer's specifications- See Section 602.2 5- Floors over crawl space or exposed to ambient air conditions. 6. Required slab perimeter insulation shall be a water resistant material, manufactured for its intended use, and installed according to manufacturer's specifications. See Section 602-4- 7. Int. denotes standard framing 16 inches on center with headers insulated with a minimum of R-10 insulation- 8- This wall insulation requirement denotes R-19 wall cavity insulation plus R-5 foam sheathing - 9. Doors, including all fire doors, shall be assigned default U -factors from Table 10-6C 10- Where maximum glazing area is listed, the total glazing area (combined vertical plus overhead) as a percent of gross conditioned floor area shall be less than or equal to that value- Overhead glazing with U -factor of U=0.40 or less is not included in glazing area limitations. I I - Overhead glazing shall have U -factors determined in accordance with NFRC 100 or as specified in Section 502.1-5. 12- Log and solid timber walls with a minimum average thickness of 3-5" are exempt from this insulation requirement. This project will take advantage of the following exceptions to the prescriptive option: 0 602.6 Exception I - One door, that is 24 sq ft or less, that does not meet the standards is allowed. Location of door taking this exemption. 0 602.5 Exception 2. Doors with U -factor of 0.40 allowed without calculations, Option IV only- Location of door(s) taking this exemption_ VAPOR BARRIERS shall be installed toward the warm surface as represented below (select one): Floors: Kraft Faced batt insulation Unfaced insulation with ❑ ❑ Plywood Sheathing 1 ❑ _ polyethylene (4 trail) (Exposure or exterior grade) Walls: Face stapled batt insulation Unfaced insulation with ❑ Vapor Retarding Paint ❑ ❑ polyethylene (4 trail) Ceilings*: Face stapled batt insulation Unfaced insulation with ❑ ❑ Vapor ❑ =lull 6mi1poly polyethylene (4 trail ) Retarding Paint *NOTE: Vapor Barrier not required where ventilation space averages 12" or greater above the insulation SLAB INSULATION shall be R-10 minimum and be Iocated on the: ❑ Exterior ❑Interior SLAB INSULATION EXAMPLES 11111=11!11=- = I#I1-11111= NOT CONSTRUCTION DETAILS =11111=!1111-=11 — I_=14111�11111=111 4" Gravel Base Floating Slab with Interior Insulation Silicone Caulk Seal 4" Concrete Slab Floating Slab with Exterior Insulation Flashing/Protection Silicone Caulk Seal 95 / 4" Concrete Slab , Thermal Break Floating Slab on Grade wlInterior Slab Insulation Silicone Caulk Seal Thermal Break 4" Concrete Slab IIIIIIIII = = Ill(= III(= Il- Ilf IIIIF11=-__:_:1111-11111-11111-=F1_ 11II€ff1= ==11�11-=11�1i=1€11f==FI =1111 ��_=<:IIf11=(1111=11�II=hill= -lull >ry=-1Ti1=T1=11111=11111 =d1I&ITi-11111—I `fl_Illil_llfli Illff 11111=1111I-I€f11-11111= Revised 7107 6 mil poly R-10 Insulation 24" minimum Below Grade Wall with Interior Insulation �--IIIII=IIIII=iIltti Il#II-�Tl=il�11-1 =IIIII=11111=Illll (fill=11111=IIill�_ i 1111=II Ili -{Il __= 1111► -11111 <_-_ IIIII�IIII-=111:'':= lull—�u�� 11111=1Tf1i=ffm Silicone Caulk Seat HEATED BASEMENT 4' Concrete Slab lIII[� 6 mit poly Thermal Break _ 11111_1€l1111l11 1111_11111= Ili ='_���s4= 11111=11111_=____ =lull 6mi1poly 1�1111fl1l1l1ll1(_-11111II1I111 =I(=1111=�1_111€=-1=1111l—ff�11111 1111— 1 6milpoly IIH=111!1--11111_IIIII_lllil 11111=11!11=- = I#I1-11111= _� � =__= =11111=!1111-=11 — I_=14111�11111=111 4" Gravel Base 11111=11(11= _ __ `=€1111=11111=11111-1111= 11111 III11=lll11== IIDI=1 .-_____________ _=_<" Ifl1=I --11111_1€III=_ IIIf1_I --11111= =fIT=1Tl 11111=1 = = _=_ _=11111=11111=11111=11111 - _--==11111-11111`11111= �i1T1 ___ -_ _____ ______11 - =11111=l = ® - -_ = I=llllllllll= R-10 Insulation — rrr— — 11111�11111=11111=IIIII= 24" minimum or 11111 _— —_ IIIII R-10 Insulation totrostline IIIII= Wil =III11=f1III- 24" minimum Floating Slab on Grade wlInterior Slab Insulation Silicone Caulk Seal Thermal Break 4" Concrete Slab IIIIIIIII = = Ill(= III(= Il- Ilf IIIIF11=-__:_:1111-11111-11111-=F1_ 11II€ff1= ==11�11-=11�1i=1€11f==FI =1111 ��_=<:IIf11=(1111=11�II=hill= -lull >ry=-1Ti1=T1=11111=11111 =d1I&ITi-11111—I `fl_Illil_llfli Illff 11111=1111I-I€f11-11111= Revised 7107 6 mil poly R-10 Insulation 24" minimum Below Grade Wall with Interior Insulation �--IIIII=IIIII=iIltti Il#II-�Tl=il�11-1 =IIIII=11111=Illll (fill=11111=IIill�_ i 1111=II Ili -{Il __= 1111► -11111 <_-_ IIIII�IIII-=111:'':= lull—�u�� 11111=1Tf1i=ffm Silicone Caulk Seat HEATED BASEMENT 4' Concrete Slab lIII[� 6 mit poly Thermal Break VENTILATION WORKSHEET SOURCE SPECIFIC VENTILATION: Exhaust fans are required in each kitchen, bathroom, laundry room, indoor swimming pool, spa, and other room(s) where excess water vapor or cooking odor is produced. Complete the following table: Location RequEred CF1VI Actual":CFM KITCHEN FAN 100 CFM BATHROOM #1 FAN 50 CFM BATHROOM 92 FAN 50 CFM BATHROOM #3 FAN 50 CFM LAUNDRY FAN 50 CFM WHOLE HOUSE VENTILATION: Each dwelling unit shall be equipped with a whole house ventilation system supplying outdoor air to all habitable rooms and exhausting stale air out via a designated fan_ Complete the following questions and table: ❑ Not applicable for additions less than 500 sq.ft. SELECT TYPE OF WHOLE HOUSE VENTILATION SYSTEM TO BE USED: ❑ Exhaust fan system with ducted forced air heating system (VIAQ 303.4.1): • Exhaust fan sized per table below with 24 hour timer. • Forced air heating system ducted to all habitable rooms. • Interior doors undercut !/211 minimum above floor covering. ❑ Exhaust fan system with fresh air „inlets (VIAQ 303.4.1): • Exhaust fan sized per table below with 24 hour timer. • Manual through -wall port or approved window vent. ❑ Integrated with forced air furnace System (VIAQ 303.4.2): • Outdoor air inlet duct sized per table 3-5 connected to the return air plenum of the forced air system. • Volume damper. ❑ Supply fans stem (VIAQ 303.4.3): • Distribute air through the forced -air system ducts or through dedicated ducts to each habitable space with 24 hour timer. • Outdoor air must be filtered • Outdoor air inlet connected to supply or return. • Back draft and volume dampers. ❑ Heat recovery system (VIAQ 303.4.4) Revised 7/07 A WHOLE HOUSE EXHAUST FAN MUST BE PROVIDED FOR EACH DWELLING UNIT_ Floor Area Bedrooms* (square feet) 2 or less 3 4 5 6 Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. <500 50 75 65 98 80 120 95 143 110 165 501-1000 55 83 70 105 85 128 100 150 11.5 173 1001-1500 60 90 75 113 90 135 105 158 120 180 1501-2000 65 98 80 120 95 143 110 165 125 188 2001-2500 70 105 85 128 100 150 I15 173 130 195 2501-3000 75 113 90 135 105 158 I20 180 135 203 3001-3500 80 120 95 143 110 165 125 188 140 210 35014000 85 128 100 150 115 173 130 195 143 218 4001-5000 95 143 110 165 125 188 140 210 155 233 "tor more than h bedrooms and/or over SUUU square teet see Table 3-2 Washington State Ventilation and Indoor Air Quality Code. Total Floor area: Bedrooms: Whole House Fan Size: Location: ✓ WHOLE HOUSE EXHAUST FAN WILL OPERATE INTERMITTENTLY? Yes ❑ No ❑ Both automatic and manual control needed. Automatic control timer shalt be set to operate whole house fan for a minimum of eight hours per day. ✓ WHOLE HOUSE EXHAUST FAN ALSO SERVES AS A BATH OR LAUNDRY FAN? Yes ❑ No ❑ The capacity shall be the larger CFM requirement. ✓ WHOLE HOUSE EXHAUST FAN WILL OPERATE CONTINUOUSLY? Yes ❑ No ❑ Note. Installers shallprovide the manufacturer's installation, operating instructions, and a whole house ventilation system operation description. A label shall be affixed to the whole house timer control that reads "Whale House Ventilation (see operating instructions)." Revised 7107 Ventilation System Operating Instructions Whole House Ventilation Systems Integrated with a Forced Air Heating System' Your new home has been constructed to use energy efficiently, while maintaining a healthy indoor environment with good supply of fresh air. To help you achieve these benefits, we recommend that you take a few minutes to read these instructions. Your home has been constructed to the most current requirements of the Washington State Energy Code (2003 edition) and the Washington State Ventilation and Indoor Air Quality Code (2003 edition). This means your home and the ductwork of your heating system have been well sealed, which limits uncontrolled exchange of air between the indoors and outdoors. The amount of fresh air provided to your home is under your control. You can increase the ventilation rate of your home by opening windows, or by operating your mechanical ventilation systems. Your home has two types of mechanical ventilation: spot ventilation fans, and a whole house ventilation system integrated with your heating system. �M� A spot fan has been installed in each bathroom, the utility room and the kitchen. if your home includes an indoor spa, or any other room that may need additional ventilation, a spot fan will be included there as well. /The purpose of spot ventilation is to control excess moisture, odors, or chemical byproducts at the source. It is far more effective to quickly eliminate moisture and pollutants when they are created than to allow them to dissipate slowly over time. Controlling moisture reduces the cause of many molds and protects the finishes of your home. Controlling odors and chemical byproducts reduces any health hazard that may be associated with It is particularly important to operate your kitchen fan if you have a gas or propane range. As well as removing moisture and odors created by cooking, your kitchen exhaust fan removes the unhealthy byproducts of combustion, including carbon monoxide and nitrogen oxides. Recommended spot fan operation: • Turn on the spot fan whenever moisture, odors, household chemicals, or combustion byproducts are present in the room, such as during shower- ing, washing clothes, or cooking- - Since moisture vapor, odors, and combustion byproducts tend to linger, run the spot fan for up to 60 minutes beyond the activity that produced them. Whole house ventilation integrated with the heating system. The forced air heating system in this home is equipped with a ventilation system. This system includes a fresh air intake connected to the return air duct (return air is the air that flows into your heating system), a damper that controls the amount of air that enters the system, and a timer that controls when the system operates. To change the amount of ventilation in your home adjust the timer to increase or decrease the time the system operates. In some cases you may also want to adjust the damper. Here's how the system works: 5UPPLY DUCT FRE5H AIR INTAKE= Figure 1. Whole house ventilation system integrated with a Forced air heating system. • When the ventilation timer calls for ventilation, the furnace fan motor turns on. If the ventila- tion system is equipped with a mechanical damper, it also opens. • The furnace fan pulls fresh air through the fresh air intake into the return air duct. • Fresh air is then distributed to the home through the supply air ducts of the heating system. • When the ventilation timer shuts off, the furnace fan motor turns off. If the system has a me- chanical damper, the damper also closes. Note: If your system is not equipped with a mechanical damper, your home will also receive ventilation whenever the system fan operates, including when it's on to provide heating or cooling. Selecting a Whole House Ventilation Schedule: Your contractor has set the timer on your ventilation system to provide a minimum of eight hours of ventilation per day. To get the maximum benefits of the system, you'll want to adjust the timer to suit your own schedule. • Run the system more when you expect to be home, or when more people are expected to be in the home. • Set the timer to cycle the system on and off for short periods. For example, 10 minutes on, 20 minutes off. • Use the manual control to turn the system on when large groups gather in your home. TIME OF DAY ONIOFF PINS AUTO: RUN TIME BASED ON TIMER ON: CONTINUOUS OPERATION Figure 2_ Typical whole house ventilation timer. 2 Ventilation System, Operating Instructions Dampers: There are three types of dampers allowed by the ventilation code. Figure 3 identifies these dampers and describes how they work. This system uses the damper checked below. © Manual Damper ❑ Constant Air Flow Regulator ❑ Motorized Damper As required by code', your heating contractor has tested the flow reate of fresh air brought into your home and set the damper accordingly. Manual Damper Operation: In normal operating conditions, the damper is always open, regardless of the settings on the ventilation timer. The home receives ventilation whenever air handler fan turns on, or when the thermostat calls for heating or cooling. Using the timer to regulate the ventilation rate is always the hest choice. But because this system provides ventilation to the home whenever the air handler fan operates, ventilation rates may be excessive during very cold or very hot weather. This can mean wasted energy and an uncomfortable home. In this case, you may wish to adjust the manual damper. Before doing so, keep a few things in mind: • Before you change the damper setting, make note of the position of the damper adjustment. You will need to return the damper to this setting when the extreme weather passes. • Only reduce the ventilation rate when abso- lutely necessary. • Be aware for signs of under -ventilation, includ- ing smells and high humidity - rYln,,4;JAi. DArATIER ADJUSTMEN' FIXED: AbI, &Y: CP E 14. r_ON5T,ati ; AWFLOW ?,EGUL;ZK PO F F:NA . 5LAi>DEF OAF,ED r'N $KET iUt PUCTI AIR, F ti_E: 5URE AL'WAY5OF—EN. )AW 1 rvt0TOP AYE i� r E �r art ;r;rt H far 13�Tr�E r::��rk_. VOLUME J5 PE�Uc -ATED 6YOPE;PAMPEK P05f T VIN ADJ'J5TMEtT. Figure 3_ Selection of dampers used to meet the viAQ code. Ventilation System Operating Instructions 3