Loading...
2008-0319 Nordic Center.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: December 5, 2008 TO: Megumi Matsumura CDA Architects megumim@cdaarch.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2008-0319 Review #2 Project: Nordic Center th Project Address: 310 5 Ave. S. During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. Thank you. 1.Previous item 3. You have indicated that you intend to complete the office and retail spaces under this permit. In this case, please provide a seating plan for reception areas, reference rooms and lounges, etc. Also, show on the drawings all fixed equipment such as copy machines, display cases, merchandise racks and public counters (including accessible features). 2.Previous item 5. On the shoring detail 4/A-1.1 and on the Updated Geotechnical Report dated October 11, 2008, indicate whether there is an expected surcharge on the shoring. If there is a surcharge, or if the ecology block wall (drawn as an option) is taller than 8 feet, then provide engineering calculations along with the design. These calculations will require peer review at full cost to the applicant. Please indicate the maximum height of the ecology block wall. 3.Previous item 26. You removed the exit sign in the garage that was potentially confusing to occupants, however an exit sign will be required at the southwest exit door of the garage. Please add this to the plans. 4.Previous item 30. The door (C3a) at the north stairway that opens into the exit passageway must be as close to the bottom of the stairs as practical to preserve the nature of the vertical exit enclosure. Please move the door closer to the stairway while maintaining a minimum landing of 48” between the stairs and the door; and provide adequate accessible door approach dimensions. 5.Previous item 46. On the Wall Types, please include on the plan details the type, size and spacing requirements for drywall fasteners according to the listing of the assembly, typical. 6.Previous item 52. The Residential Energy and Ventilation Worksheet shows electrical wall heaters and manual air inlets for the second floor. Please show on the plans how each habitable room on the second floor will be provided with 4 square inches of outside air. (ie. Vented window frames). 7.Previous item 59. Provide structural skylight calculations or manufacturer listing to show compliance with IBC 2404. 8.Previous item 61. More detail is needed to show accessibility features in the Type B units. Please indicate on the plans that each of the residential units is Type B, and show dimensions for features such as door threshold heights, light switches and electrical outlets, plumbing fixture controls, clear space for toilets, tubs and sinks, etc. Also show reinforcement (backing) for the future installation of grab bars at toilets and tubs. ANSI 117.1 Section 1004. 9. Previous item 63. Even though mechanical plans will be a deferred submittal, it is necessary to include construction details for anticipated penetrations of fire-resistive assemblies. Please show how the fire rating will be maintained at ceiling fans and can lights (if any), ductwork in ceilings, and venting of lower floor appliances. If rated shafts or gyp tenting is to be used, show how these are to be constructed. Air handling units are shown above the restroom and break room areas—how will this work? 10.Previous item 64. The garage exhaust outlet must terminate per WAC 51-52-501.2.1 #2. This information may not be deferred as the exhaust location may impact other features of the building/site. Clearly show location and required dimensioned distances on the plans. If a rated shaft will be provided as part of the redesign, please provide a detail and listed and tested fire assembly. Also show how the make-up air will be provided for the garage exhaust system—this will be of particular concern since an overhead door is proposed. 11.Please see the following structural comments from the city’s consultant. Please contact Mr. Jeter directly if there are particular structural concerns you may have. Plan Review # 2008-0319 EECE # EDM 08-42 (2) Plan review number 02 Structure Occupancy Gross Area S.F. Parking S2 5730 Garage/Basement Retail/ First floor M 2176 Office / First Floor B 3404 nd Residential/ 2 Floor R2 5395 Total 16705 Decks 234 Grand total16939 Sprinklers16939 AC 5580 Page 2 of 6 Edmonds The above referenced project is in the process of plan review for compliance with ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back-check time. Original comment will be written in italic if more information is required. SCOPE OF REVIEW Structural only The scope of this review is for therequirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. STRUCTURAL COMMENTS General 1.3. The restrained retaining wall was not designed for the additional 100 psf added to the active pressure. Please resubmit the retrained wall analysis with the 100 psf added as required per the geotechnical report. Please resubmit all restrained retaining walls with the correct active equivalent fluid pleasure. The retaining wall analysis submitted shows the base of the wall ratio exceeding 1 and the minimum code is therefore not met. Revise analysis and drawings accordingly. 2.4. Please submit the geotechnical report with the plot showing the location of the test boring. (The report state see site plan but the site plan does not includes. Also the report shall have this information contained in the report) IBC 1802.6 This still has not been submitted as required per the code. Please submit. IBC 1802.6 3.6. Engineer of Record (EOR), please justify 50 psf live to be used for the parking garage vault lid. The load also of 3000 pound applied over an area of 4.5 inches X 4.5 inches also must be considered. This appears to be able to control the design of the vault lid and not 50 psf. Please modify accordingly. ASCE table 4-1. The response statement that “the vault lid is not used for passenger vehicle storage so this does not have to be used” is not correct. The or footnote states floors in garages portions of a building used for the storage of motor vehicles shall be designed for the point loads. Therefore, floors in garages shall be designed for the uniform distributive live loads of table 4-1 or the following concentrated loads. For a garage restricted to passenger vehicles accommodating not more then 9 passengers, 3000 pound force must be investigated on the floor system. Please submit analysis for this design force. 4.7. Please clarify how the stirrup area was determine to be .44 in^2 when there is not any stirrup specified for the vault lid. Please clarify upon the response. The response appears to be designing the slab as a beam. Beams have stirrups but slabs do not. The shear design for the beam reinforcement shall be placed in the shear plane, but the slab reinforcement does not have reinforcement in the shear plane. Shear is diagonal cracking and not flexure. In Page 3 of 6 addition, the deflection shall be computed off the cracked moment of inertia, not the gross moment of inertia. See ACI section 9.5 Sheet S1 General Notes and columns and beam schedule 5.8. EOR, please add to the drawing a statement of special inspections as required per IBC 1705. The response states all epoxies are not a statement of special inspections as per IBC 1705. Please add the requirement of IBC section 1705. 6.9. EOR, please add the pertinent information from the snow load design to the drawings as required per IBC 1603.1.1 The response states “see updated notes S-1.” However, this sheet does not have Ce or the Cr factors as required per the code. Please modify accordingly. 7.11. EOR, please add all the required earthquake design date to the drawings as required per IBC 1603.1.5. IBC 1603.1.5. EOR, per the response, please clarify the seismic force resisting system “to be A13”. This is not a defined seismic resisting force system. The definition of seismic force system-resisting system as defined per code does not have A13, but the definitions is the following.: That part of the structural system that has been considered in the design to provide that required resistance to the seismic forces prescribed in the code. ASCE 11.2 Sheet S-2 Foundations Plan and Details 8.13. Detail 10: EOR, Please provide analysis for ht ¼” Diameter KWIK bolts. The ESR-1197 does not have this size. The smallest size of bolt is 3/8”. Submit ICBO report and analysis for the ¼” Diameter bolts to transfer the required design forces. The response states “See attached Hilti Catalog for the ¼” bolt.” ICC approved values must be used, not the manufacturer’s catalog. The ICC report ESR-1917 which is the current one for the Hilti Kwik bolts does not approve ¼” bolts. Also the attached catalog is outdated and not approved at this time. Submit analysis and modify the drawing to approved anchoring system. ICC ESR 1917 and Hilti 1-800-879-9000 Sheet S-3 Lower level shear Walls with First Floor Framing Plan 9.14. EOR, please provide a detail for the connection for beam mark 27 to the wide flange beam. The response states 4X6 flat ripped at bottom of beam is required, but the drawings do not reflect this requirement. Please modify the drawings to show this requirement. 10.16. EOR, please clarify on the drawing the required connection of the floor system to the perimeter concrete walls. Nothing is specified at this time in order to complete the review. The revised drawings still do not reflect how this will be connected. Please modify the drawings accordingly. 11.17. EOR, please provide a detail for the bearing wall on the wide flange beam to transfer the design forces. There still is not any detail or reference as to how the shear wall forces will be transferred when they are bearing on the wide flange beams. For example, you have a bearing wall along grid B wide flange beam mark 20. Please provide analysis and detail to show how the design forces will be transferred. Sheet S-4 First Floor Shear Wall with Second floor Framing Plan Page 4 of 6 12.19. EOR, please specify the required post and connections for the 5-1/8X13-1/2 with a mark of “#” in the hexagon. The response states posts are (3) 2x6 with CC66. The width of CC with the bolted holes is 5.5” but (3)2x6 have only a width of 4.5“ (3*1.5) Please provide a detail at these locations. ( Also, please correct the call out in the hexagon with the number sign and not the actual number.) 13.20. EOR, please clarify on the drawing the required connections of wide flange beam mark 23 to the diagonal beam mark 5 along grid line C1 between grid 3 and grid 4. The response states “½” Diameter CB is required at each side of the web. See attached steel beam – Glulam BM connections detail”. However, this is not specified on the drawing. Please modify accordingly to show a complete load path. 14.22. Please add to the drawing for the length of the shear wall on this level. It appears the length used in the analysis does not match the drawings. Please add this required minimum length to the drawings. The lengths are still not referenced on the drawings. All that is stated is they do match the drawings. Please add the length to assure the shear walls are built as designed. Sheet S-5 Second Floor Shear walls and Roof Framing Plan 15.23. The effective width of the Shear wall mark SW4 exceeds the maximum height to width ratios. Please modify accordingly. IBC table 2305.3.4. The shear wall SW4 that is at a diagonal cannot use the full width as per the design. The effective width must be used. Therefore, per the response, the width of 3 feet is not correct. 16.24. Please add to the drawing the required width of the shear wall notes as required per the analysis. This still has not been addressed at this time on the drawings. Please add the required minimum width as per the analysis. 17.25. EOR, the beams marks 34 does not match the schedule on sheet on sheet S2. Please clarify the required connection and modify accordingly. The response states BM 34 is designed as a 3-1/8X10-1/2, but the drawings reflect something different. In addition, the response states See updated sheet”. But It appears this sheet has not been updated. 18.26. EOR, please specify the required connections of the 6x6 post to beam mark 40. Nothing is specified at this time. For some reason, the post and beam have been deleted from the revised set. Please specify the required beam size and the post required to support the beams at the perimeter. I assume a layer was turned off when the revised set was printed. Shoring Comments Sheet A1-1 A.EOR, please submit shoring drawings and analysis. The geotechnical reports state temporary shoring is required. However, there was neither analysis nor shoring drawings submitted for review. Drawings and analysis are required for the shoring system, not just a note that the geotechnical engineer will provide inspections. IBC 1803.1 Page 5 of 6 B.Please submit geotechnical recommendations for the cut slope of 1.25 to 1 as noted on this sheet. There is an existing street, and without shoring, how is the soil able to be stabilized? Since there is an existing asphalt street, some type of shoring must be provided for this structure with analysis and details. C.There is an existing building noted that will effect the excavations and constructions of this site. Submit drawings and shoring procedure for this site. It also appears an easement will be required from the existing property. IBC figure 1805.3.1. Additional corrections may be required following receipt of corrections and additional information as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874-0562 between 8:00 a.m. and 5:00 p.m. By: Hoyt Jeter, P.E. President Page 6 of 6