20080331072438.pdfof EOE City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
�sf. ts9° (425) 771-6220
DATE: March 31, 2008
TO: Wayne Davenport
e-mail: wayneandtone@hotmail.com
FROM: Ann Bullis, Assistant Building Official
RE: Plan Check # 2008-0239
Project: Campbell Nelson Nissan — My Friends Cafe
Project Address: 24329 Highway 99
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Provide written responses to each comment and where
changes can be found on the plans. Please resubmit to Marie Harrison, Permit Coordinator.
Please provide this comment letter to your architect for response and coordination with plumbing
and mechanical.
1. On the coversheet, note current code information (2006 editions), current Type of Construction,
current occupancies, and occupant loads.
2. Show the floor area of the cafe (including kitchen, customer, and seating areas) and show that it
is less than 750 sf (IBC 303.1 exceptions) or an accessory occupancy (IBC 508.3.1).
3. Plumbing must be included with this permit. Please submit plumbing plan (8 % x 11 ok) for
drain/waste/vent and hot/cold potable water piping — see enclosed handout. Also provide for
condensate wastes for refrigeration equipment.
4. A Type IT hood is required over the cooking equipment unless calculations are provided showing
that the heat and moisture produced can be accounted for in the existing HVAC system (11\4C
507.2.2). Calculations must be stamped and signed by a State licensed mechanical engineer. If
a Type H hood will be provided, show the location and efin rating, and show how it will be
vented to the outside.
5. Label the existing l -hour fire barrier on the plans. All penetrations (such as electrical and
plumbing) must be fire stopped with 1 -hour fire stopping assemblies. Please note on the plans.
city of edmonds
development information
/nc. I Sqo
Plumbing
Permit Submittal Requirements
PERMIT REQUIRED: A permit is required to install, alter, repair, relocate, or replace any
portion of a potable or waste plumbing System. Including gas hot water
tank replacement, water service line repair or replacement, propane
tanks, and to install or alter gas piping.
EXEMPT WORK: The clearing of stoppages or the repairing of leaks in drains, pipes,
valves, vents or fixtures, and the removal and reinstallation of water
closets, provided such repairs do not involve or require the replacement
or rearrangement of valves, pipes or fixtures.
CODES: Uniform Plumbing Code 2006 Edition
International Fuel Gas Code 2006 Edition
LPG per 2001 NFPA-58 and 2002 ANSI 2223_ UNFPA -54
FEE: Base fee $30 plus additional fees based on the number and type of
plumbing fixtures plus $15 City surcharge fee
SUBMITTAL REQUIREMENTS FOR NEW INSTALLATIONS:
I . Permit Application Farm C and Plumbing Fixture Form B (attached)
2. On a scaled floor plan show the following:
a. Drain, Waste and Vent piping layout; sizing, slope and pipe material
b. Potable water line layout, sizing and pipe material
c. Fixture unit and flow calculations to support line sizing
3. Cross connection devices are required on all direct connections to the potable water system.
Specify all fixtures that require cross connection devices (i.e., ice machines, soap ejection
systems, beverage dispensers, boilers, etc_) and note the make and model of each device.
4. Indicate the location and cross connection device for premise isolation
5. Manufacturer's specifications for equipment such as sump pumps, ejector pumps, water heater
boosters, etc.
6. Gas piping layout, sizing and pipe material, pipe sizing calculations, maximum design operating
pressure and location of pressure regulators
7. For Commercial and Multifamily projects, provide Listed and Tested Fire Stopping Assemblies
NOTE_ THE PURPOSE OF THIS HANDOUT IS TO ASSIST THE PUBLIC IN COMPLYING WITH DETAILED PERMIT SUBMITTAL
REQUIREMENTS. IT IS NOT A COMPLETE LIST OF PERMIT OR CODE REQUIREMENTS AND SHOULD NOT BE USED AS A SUBSTITUTE
FOR APPLICABLE LAWS AND REGULATIONS. IT IS THE RESPONSIBILITY OF THE OWNER/DESIGN PROFESSIONAL TO REVIEW THE
SUBMITTAL FOR COMPLETENESS AND APPLICABILrFY TO OTHER CODES. ONLY COMPLETE APPLICATIONS WILL BE ACCEPTED
BY THE CITY FOR REVIEW.
Revised 7/07
rF'r
PLUMBING FIXTURE COUNT {Form B
Number
Fixture Tvue
Revised 7/07
Water Closet (Toilet)
Sink (kitchen, laundry, bar, etc_)
Lavatory
Tub/Shower
Dishwasher
Hose Bib
Water Heater
Expansion Tank For Water Heater
Floor Drain
Pressure Reduction Valve
Water Service Line
Drinking Fountain
Bidet/Urinat
Clothes Washer
Backflow Protection Device
Hydronic Heat In Floor Wall
Other
GAS OUTLETS
AC Unit BTUs Location
Furnace BTUs Location
Water Heater BTUs Location
Boiler BTUs Location
Dryer
Stove/Range/Oven
Fireplacelinsert BTUs Location
Outdoor BBQ
Revised 7/07