Loading...
20080409084429.pdfLANDAU AssOCIATES TM TO- Jeannine Graf, Building Official City of Edmonds "Building Department FROM: Dennis R. Stealer, P;E_ ( W116 - Chad McMullen, P.E. DATE April .8, 2008 RE: GEOTECHNICAL PEER REVIEW COOPER RETAINING WALLS 730"616ei' PLACE'SW EDMONDS, WAS IINGT'ON INTRODUCTION This. technical memorandum provides our geotechnical peer review of technical documents and plans submitted to the City of Edmonds (City) for the proposed retaining walls at the Cooper single ramily :residence; The purpose of this geotechnical:peer review, was to review portions of the submittal package and assess its.complianc:e with 'City development"and building permit requirements as contained in Edmonds Community Development Code (ECD.C) Chapter 23.80, and City of Edmonds Retaining Wall Permit Submittal Requirements (as contained in City Handout B.62). This geotechnical peer review Was accomplished in accordance with Task Order Na. 08-05 of Landau Associates' On -Call. Geotechnical Engineering Services Agreement with the City: We have received the following information forwarded by the City for review:. 41 Landslide hivestigatron, and Slab' ization Reconzynendaticim, Jvlrrt ;C'ooper .Resiclelace,. 7306 - 164"' Place SW, Edmonds, Washinglon, L. &A Job No. 8A 010 letter Tepor"t prepared by Liu & Associates, Inc. for John. Cooper,. dated March 4; 21008, 0 Design Calculadons, Pin Pile Walls, John. Cooper- Residence, 7306 164`1' .Place SW, Edinoi. zds, Washington prepared by Liu ..& Associates, Inc., dated March 8, 2008, • Slide Repair and Slove $tab lirnt on, Plan Sltoet S$4 of ].prepared by Liu & Associates, Inc. for John Cooper Residence, dated March 9, 200$... Two retaining walls are proposed to address :a landslide that reportedly .occurred behind the residence on December 3, 2007. Access.to the.landslide area is limited and the proposed repair scheme has been .developed using materials and construttion techniques that can be accomplished with hand or ;limited access equipment. The: landslide :stabilization structure consists of two tiers of pin -pile and fagging walls. Null .support is:supplemented: with helical -anchors, which are io.cated at"appro�imatel , the M.id height of each wall:. The maximum retained height of:each of the walls will be approximately 6 feet, 1.30.2nd Avenue South O Edmonds, WA 98020 • .(425) 778-0.907 a fax (425) 778=6409: ■ www.landauinc:com with an 8-ft minimum embedded depth of the pin piles. Nearby level ground will exist above the upper tier and between the bottom of the upper tier and top of the lower tier. The ground profile in front of the lower tier slopes downward at approximately 35 degrees below horizontal. Backfill behind the walls will consist of geofoam to within 2 feet of the planned ground surface and structural backfill in the upper 2 feet. TECHNICAL. REVIEW The proposed concept and approach to the landslide stabilization appears to be appropriate for the site conditions. The following summarizes our specific technical review comments Slope Stability The landside and the proposed remedial construction occur within a Geologically Hazardous Area as defined in ECDC 23.80. Consequently, the provisions and requirements of ECDC 23.80 apply to this project. The geotechnical report for the project addresses some of the ECDC 23.80 requirements. The report outlines the slope conditions, geologic characteristics, and soils exposed in the landslide scarp area. The report also addresses the approach to remediate the recent landslide. However, the geotechnical report does not address the larger geologic hazard presented by the slope or the overall stability of the steep slope below the residence. The report should address the report requirements of ECDC 23.80.050, including, but not limited to, the extent of the geologic hazards area; the relationship of the existing and proposed construction to the geologic hazard; a hazards assessment of the overall slope; the history of the site regarding previous landslides, erosion, or grading; the stability of the slope before and after the proposed retaining wall construction; a discussion of how the proposed retaining walls maintains or reduces the pre-existing level of risk presented by the geologic hazard; and related requirements outlined in ECDC 23.80.050. Earth Pressures Active and passive earth pressures on the retaining walls are provided in the geotechnical report and the design plans. The report states that a factor of safety on the wall design for sliding and overturning of 1.7 is incorporated into the design. The .calculations provided in the submittal were difficult to follow to verify that the recommended factor of safety was provided. We request that the designer review the calculations to confirm that the factor of safety stated in the report is incorporated into the design. The geometry of the passive wedges at the bottom of each wall tier is of concern. The passive earth pressure provided in the geotechnical report and used for wall design is consistent with level ground 41WU8 1 EdmdatalprolectM741148 Cooper Ret Wal[WileRmlRlCooper PeerReview TM.doc LANDAU ASSOCIATES 2 conditions only. For the lower wall, the ground slopes steeply away from the wall and the available passive pressure would be substantially reduced. In addition, because of the close proximity of the upper wall to the lower wall, the passive pressure wedge of the upper wall would intersect with the lower wall, potentially inducing greater load on the lower wall. The available passive resistance should reflect the slope geometry within the passive wedge and the influence of the nearby lower retaining wall. Helical Anchors There is no stated requirement regarding how long the minimum length of helical anchors should be. These should be located well behind the active wedge of the retained soil. A minimum installation length of soil anchors should be provided by the designer. The overall retaining wall design (anchor length and pin pile depth) should also be assessed with respect to global stability of the wall system. Site Drainage and Erosion Control The geotechnical report indicates that a tightline roof drain was extended to the base of the slope shortly after the slope failure. The report does not comment upon the suitability of the tightline installation for long-term use, nor does it discuss the suitability of the discharge location and the potential influence to the subject property or adjacent properties. The report should address the adequacy of the current tightline installation and if the current system is not adequate, the design documents should include a permanent roof drain tightline system including size, type, and location of pipe materials, pipe anchorage, energy dissipation fixtures, and an appropriate location for discharge. Temporary erosion and sedimentation control measures are required in accordance with the provisions of ECDC 18.30. Provisions for temporary erosion and sedimentation control are not included in the retaining wall design plans. Permanent erosion control will consist of re -vegetation of the affected area. The design plans should include temporary erosion and sediment control measures to be employed during and after construction, until permanent vegetation is established Inspections City requirements for retaining wall permits (see City Handout B62) outline the owner requirements for calling for Building Inspections by the City during construction, and Special Inspection Requirements that call for the Geotechnical Engineer of Record to monitor the construction to verify the site conditions and construction and to submit Field Reports to the City. The requirements for City Building Inspections and Special Inspections by the Geotechnical Engineer of Record should be included on the design plans. 418108 11Edmdata5projedsNWAI48 Cooper Ret Wall%FileRmlRlCooper AeerReAew TM.doe LAW)Au AssOCIATES 3 CLOSURE This technical memorandum has been prepared for use by the City of Edmonds in evaluating the adequacy of design documents submitted for a permit related to the proposed retaining walls for landslide stabilization at the Cooper single family residence at 7306 164"' Place SW. The focus of this review was the geotechnical aspects of the documents. The purpose of the review was to assess the adequacy of the application documents for compliance with City requirements contained in ECDC 23.80, City of Edmonds Retaining Wall Permit Submittal Requirements, and conformance with conventionally accepted geotechnical engineering practices. This geotechnical peer review by Landau Associates does not lessen the requirements for the applicant's geotechnical consultant and other design professionals to prepare an appropriate design for the site conditions. We appreciate this opportunity to be of service to the City. Please contact us if you have any questions, or if we may be of further service. DRS/CTM/rgm 4008 51EdmdatakprojectsWM148 Cooper Ret WallkFileRm\RICooper_PeerReOew_TM.doc LAN RAu ASSOCIATES 4