20080423111536.pdfo� Epi City of Edmonds O PLAN REVIEW COMMENTS BUILDING DIVISION �Sr $qo (425) 771-0220 DATE: April 22, 2008 TO: Stephen Redmond FROM: Jeannine Graf, Building Officinal RE: Plan Check # BLD20080255 Project: Kirkendall SFR Project Address: 18819 Olympic View Drive During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. Please resubmit two (2) copies of revised sheets and/or documents with a written response to each of the items below to the Permit Coordinator assigned to your project: 1) In general the site plan must match the house plans. Please add the following information to the site plan. • Covered entry porch • Property lines must be indicated • Provide top and bottom wall elevations for the bulkhead retaining walls, (the wall design shall be supplemented with supporting calculations) • Label all cantilevered features, covered porches, decks, etc. and indicate setback distances to property lines ■ Height must be taken from the smallest rectangle that encompasses all four corners of the proposed residence. The original undisturbed grade (before demolition) must be re- established which may require the services of a licensed surveyor. Point A must be taken from grade prior to demolition. • Indicate all existing asphalt that will remain and indicate all new proposed asphalt or concrete on site. • Provide grades at two foot contours on entire lot. • Site plan is missing all utility connections (gas, water, sewer, storm, phone, cable, etc.) ■ Indicate distance from any structure, slab, patio, deck, etc. to top of slope. Resubmit three (3) new site plans scaled (one scaled site plan shall be no larger than 8 1/z" x 14") 2) Note the 2006 edition of codes on the soils report. 3) The geotechnical report is also required for compliance to IRC R403 and not only ECDC 23.80; supplement as necessary. 4) Complete the fan page for sizing on the energy worksheet. 5) The floor plans are missing where the section views apply. 6) Complete the stair detail and provide a guard detail. 7) Provide a typical exterior landing detail. 8) Call out all interior wall finishes for all rooms and spaces. 9) Provide a bollard to protect garage mechanical equipment. 10) Specify door type between dwelling and garage. 11) For habitable rooms that have no natural light or ventilation provide details for the code exception. 12) Specify all glazing required to be safety glazed on elevation views and floor plans. 13) Show how kitchen sinks will be vented through the roof or with a loop vent as permitted by UPC 909.0. Air admittance valves are not permitted unless first approved by the Building Official under a formal alternate design request per UPC 301.2 (additional fee required). 14) Indicate note on fireblocking requirements for furred walls per IRC 602.8. 15) Specify on the elevation views where the grades slope away from the building. If minimum 6" within 10' is not possible or habitable or useable space is below grade, foundation drainage is required. Provide footing drain detail on foundation sections complying with R405.1 and the soils report and show required drain locations on the foundation plan. 16) Retaining walls located in a critical area must have plans designed consistent with ECDC Chapter 23.80 (including design calculations) and stamped by a Washington State Licensed Professional Engineer. The City requires peer review and special inspections for all retaining walls in critical areas or their buffers. 17) Special inspections are required for this project and must be clearly noted on the plans. Complete the enclosed special inspection agreement (note the form must be signed by the owner, the general contractor and the special inspector and submit to the City for approval prior to issuance). 18) See attached structural comments from city consultant. Respond to each item in writing. Page 2 of 2 Eagle Eye Consulting Engineers, P.S. PO Box 523 Olalla, WA 98359 m, hoytjeter@centurytel.net 360 874 0562 Fax 360 874 0591 To: Marie Harrison 121 5th Ave N Edmonds, WA 98020 Re: Kirkendall -Spring Residence 18819 Olympic View Dr Edmonds, WA 98020 Plan Review # 2008-0255 EECE # EDM 08-28 PIan review number 01 Structure Stated Area S.F. Basement 1482 Main 1994 Second 1280 Total 4756 Garage 512 Total 5268 Covered Porch 60 Grand total 5328 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the Ordinance, Structural, V&IAQC and Energy requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. Page 2 of 6 Plan Review Number 01 EECE#: EDM 08-28 Kirkendall -Spring Residence 2008-0255 ORDINANCE COMMENTS General 1. Architect of Record (AOR), please clearly add to the drawing the required riser and tread depth for the stairs. I was unable to find where this information was specified. R311.5.3 2. Please note on the drawings that the smoke alarms shall be hot-wired with battery back-up. R313.2 3. Please clarify on the drawing the roof drainage and method to drainage away from the foundations. R903.4 & R401.3 Sheet 10: 4. Drawing state roof is by others. Please provide information for the roofing. R801.1 /l ���/��►rvl c✓ PLM: v/i4cL r9�'�PG�Ct�Ci �D Sheet B 5. Please submit the DSS that may override the plans as noted on this sheet. Sheet 1 First Floor Plan 6. Please specify the required light activation at the top and bottom of the stairs, per R303.6.1. 7. Please clarify the locations of the smoke alarm on this level. One is required on each level. R313.2 item 3 8. Smoke alarms shall be installed outside each separate sleeping area in the immediate vicinity of the bedrooms. Please add this to the drawings. R313.2 Sheet 2 Second Floor Plan 9. Please clarify the locations of the smoke alarm on this level. R313.2 10. Smoke alarms shall be installed outside each separate sleeping area in the immediate vicinity of the bedrooms. R313.2 11. Please provide guard details at the loft opening to below. Nothing is specified at this time. R312 Sheet 3 Foundation & Basement Plan Page 3 of 6 Plan Review Number 01 EECE##: EDM 08-28 Kirkendall -Spring Residence 2008-0255 12. Please specify that all the penetrations through the garage to house separation wall shall be protected by filling the opening around the penetrating item with approved material to resist the free passage of flame and products of combustion. R309.1.2 13. Architect of Record (AOR), please note the garage slab slope to the main door. All that is notes is per code. Please specify the required slope. R309.3 14. The plan shows a closet will be under the stairs. Usable space under stairways shall have the walls and soffits on the enclosed side protected with a minimum of 1/2 - Gypsum. Please add this to the drawings. R311.2.2 15. Please provide information for the window well. This is required to meet the IRC sections R310.2. All that is notes is by others. R310.2 16. Per definitions, the storage room maybe classified as a bedroom and smoke alarms and egress shall be met. The room label as a dark room, could be classified as a closet and must meet the life safety issues of the code. Please add a smoke alarm in this room and egress requirements. R313 and R311 Sheet 12 Cross Section thru C-1 17. Please complete the references that are blank on this sheet. STRUCTURAL COMMENTS Sheet 7 First Floor Framing Plan 18. EOR, please provide a detail at the intersection of beam mark QQ (5-1/8X9" GLU) and 5-18X19-1/2 glu-lam. Sheet 8 Second Floor Framing Plan 19. EOR, please clarify the capacity for the LU -P28 hanger. This is not in the Simpson catalog so I was unable to check the capacity. There is LU and LUS but it appear there is not a LUP. Please clarify upon the response. Sheet 9 Roof Framing Plan 20. EOR, please provide a detail at the support of the beam mark Q-11 and W-15. Since the beam are different depth of 3" a detail and analysis should be provide to show how the forces would be resisted. 21. EOR please provide a detail at the intersection of the beam R-17, Q-11, Q-08 and 3-1/2X16-1/2 Y21. Page 4of6 PIan Review Number 01 EECE#: EDM 08-28 Kirkendall -Spring Residence 2008-0255 Sheet 18 Details 22. Detail A: Provide analysis for the A34 connecting to the plywood backing to support the design loads. Based off the detail the required design forces will not be resisted. Please modify accordingly. Sheet 20 Details 23. Please provide information for the connector shown. All that is stated is #780-4. What is a 780-4. Please provide this information when resubmitted. Sheet 22 Details 24. Detail H: Please clarify on the drawings where this detail is referenced. The details state hanger per plan but I was unable to find this information specified. Please clarify on the response in order to complete this review. Sheet B General Notes 25. Please modify the rafter to plate toe nailing to meet the minimum requirements of Table R602.3(1), Rafter to plate shall be a minimum 2-16d and not 3-8d. In addition, the fiber board sheathing requirements are less then required per this table. Please update the nailing to the adopted code. ( It is fine to have more then required but not less) Table R602.3 Sheet S-1 Shear wall Schedule 26. Shear wall schedule: Please modify note 4 to state a minimum size washer shall be a minimum 3X3X.229. The note on this sheet states 3X3X3/16" to use, which has a thickness of .1875". This is less then required per the adopted code. IBC 2305.3.11 27. EOR, please clarify on the drawings where the lateral restraint panel will be used. This is important to make sure the correct header is used. I was unable able to find on the drawings where this was referenced. Figure 2308.9.3.2 Sheet S-3 Schedules 28. Design analysis submitted use an active pressure of 30 PCF. The geotechnical report prepared by Krazan & Associate states for active conditions the pressure shall be 35 psf Please modify accordingly. 29. Please submit design analysis for all the wall heights shown. The submitted analysis only has height for an 8 -foot wall and a 9 -foot wall. However, the Page S of 6 Plan Review Number 01 EECE#: EDM 08-28 Kirkendall -Spring Residence 2008-0255 schedule has many different heights, even heights that exceed the des Win parameters. C 1806 / 'Jl� M til% � /'qi f 1 4)14 ®� '� !�✓�%f T7; Mir ' 30. EOR, please clarify why the design of the wall for the restrained conditions did not use the at -rest conditions. For active conditions, the wall shall be able to deflect. VENTILATION & INDOOR AIR QUALITY CONTROL COMMENTS General 31. Please specify the location of the whole house fan location on the drawings. 32. Please specify the required CFM for the whole house fan. WSV&IAQC 302.3 Sheet 1 First Floor Plan 33. Please specify the required fan in the water closet. WSV&IAQC 303.3.1 34. Please specify the required fan to use in the kitchen. WSV&IAQC 303.3.1 35. Please specify the required fan to use to the master bathroom WSV&IAQC 303.3.1 Sheet 2 Second Floor Plan 36. Please specify the required fan in the water closet. WSV&IAQC 303.3.1 Sheet 3 Foundation & Basement Plan 37. Please specify the required fan in the water closet. WSV&IAQC 303.3.1 ENERGY COMMENTS General 38. Please specify the required U value for the window for this project. The state 2006 code has modified this from older energy codes. Please add thus information to the drawings. Sheet 12 39. Please specify the required insulation to use for the roof system. For 2x12 the rafter insulations shall be R38 High density fiberglass batt or equivalent. WSEC table 6-1 footnote 3. Page 6 of 6 Plan Review Number OJ EECE#: EDM 08-28 Kirkendall -Spring Residence 2008-0255 40. Please specify the required insulation for the wall system. Additional corrections may be required following receipt of corrections and additional infonnation as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874- 0562 between 8:00 a.m. and 5:00 p.m. By: Hoyt Jeter, P.E. President