Loading...
20080508143740.pdfDATE: May 7, 2008 City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425)771-0220 TO: Warren LaFon e-mail: warrenlafon@earthlink.net FROM: Ann Bullis, Assistant Building Official RE: Plan Check # 2008-0287 Project: Addition Project Address: 547 Dayton Street During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Provide written responses to each comment and where changes can be found on the plans. Please resubmit to Theresa Umbaugh, Senior Permit Coordinator. 1. Note the following codes on the coversheet of the plans. a. 2006 International Building Code (including Accessibility) with State Amendments b. 2006 International Mechanical Code (including International Fuel Gas Code) with State Amendments c. 2006 International Fire Code with State Amendments d. 2006 Uniform Plumbing Code with State Amendments e. 2006 Washington State Energy Code (WAC 5 1 -11) f 2006 Washington State Ventilation Indoor Air Quality Code (WAC 51-13) g. Edmonds Community Development Code 2. General Notes on coversheet: a. Revised note 7 to reference IBC 717.4.3 exception, which does not require draftstops in buildings sprinkled with and NFPA-13 system. b. Revise note 17 to also note emergency lighting and method of power backup. Remove reference to floor mount exit signs. c. Revise wording of note 18 to meet 2006 IMC (you may want to remove the note and defer this to the mechanical permit). d. Add fire alarm to note 20 (or remove this note since you have a separate deferred submittals list). 3. Provide occupant load calculations for each floor and occupancy and for the total building. 4. The original approved plans for this building show the type of construction as VN (which is now VB). Please revise and justify for entire building. This review was based on VB construction not VA. 5. Provide allowable area calculations on the coversheet of the plans. Provide mixed use ratio calculation if separated uses will be used. If non -separated uses will be used provide allowable area calculations using the most restrictive occupancy (also see item 10 below). 6. Site Plan- a. Dimension the distance from the north exterior wall of the building to the property line (at the closest point). b. Dimension the width of the alley and street right of way. c. Label the accessible parking sign and note the required height of 60" from the bottom of the sign to the parking surface. d. Provide copy of easements for the property (it appears there is at least a drainage easement). 7. The opening in the east exterior wall is not permitted due to the close proximity to the property line (IBC 704.8). 8. The west side of the deck is considered an opening and would not be permitted due to close proximity to the property line. The 1 -hour fire rated exterior wall must be extended to the face north face of the building plane. 9. Based on VB construction, if the north exterior wall of the building is 10 feet or less from the centerline of the alley, the exterior wall must be 1 -hour rated (TBC Table 602). Also openings would be limited in accordance with IBC Table 704.8 (provide opening percentage calcs for each story). 10. Provide a statement on the coversheet of the plans how mixed uses are being addressed in this building 508 (such as separated uses, non -separated uses, incidental uses, accessory uses). The plans currently show no fire separations in this building which needs to be justified. Further comments may follow depending on how this is justified. 11. Provide a letter from the building owner stating what types of items will be stored in the 1St floor storage area so occupancy classification can be determined. 12. The parking garage is considered an enclosed parking garage per IBC 406.2 and must be provided with mechanical ventilation (1.5 cfin per square foot of parking garage area). The shaft and termination of the exhaust outlet must be shown at this stage, since architectural and structural aspects of the building will be affected. Show the location of the mechanical exhaust shaft and outlet. The outlet must meet WAC 501.2.1 42 (copy enclosed for your convenience). 13. On the elevation views note the plate line and ridge elevations based on the datum point. 14. Clearly note on the plans that the parking garage will have a minimum clearance of 7'-0" from all obstructions, including sprinkler heads. 15. Revise wall section on Sheet A6 to show construction requirements of WP8109 (base and face layers of gyp, fastener size/type/spacing, etc.), which is the 1 -hour assembly noted on the section. 16. Clarify on the wall section that the face of the uppermost 18" of the parapet on the roof side will be non-combustible materials. Also, the parapet must be constructed per the 1 -hour exterior wall assembly (IBC 704.11.1). Make it clear on the roof plans that the parapet is required on the east and west exterior walls of the building. 17. Dimension the clear width of the stairways and also the intermediate landing of the "lower stair". 18. Required exits: a. Two exits are required from both floors of the building (WAC 51-50 1019.1) unless the building can meet WAC 51-50 1019.2 Buildings With One Exit which you would need to demonstrate on the plans. The existing north exit door now exits into the parking garage which considered a more hazardous area and would not be permitted. Page 2 of 4 ii. Sheet A8 shows the west and east stairways as required exits from the 2na floor. The west stairway cannot exit into the parking garage (which is a more hazardous area). You may want to consider designating the south stairway as the required exit (to the existing south exterior door) instead of the west stairway. IBC 1014.2 iii. Occupants of the parking garage must also have access to two exits. iv. Exits must be spaced apart 1/3 the maximum overall diagonal dimension of the floor since the building will be sprinkled with an NFPA-13 system. IBC 1015.2.1 exception 2 v. Revise exit signage locations accordingly. vi. Dimension the exit path of travel throughout the building. 19. Required exits must be accessible (IBC 1007.1). The stairways for the second floor meet exceptions 2 & 3 of IBC 1007.3, but the 1" floor must meet this requirement. Clearly show compliance on the plans. 20. Clearly show with details and dimensions that the existing portions of the building meet current accessibility codes (WAC/IBC 3409.5, 3409.7), including but not limited to access from the public sidewalk to the building entrance, building entrance, parking, restrooms, maneuvering clearances at doorways and throughout hallways, customer counters, and overall accessible route (IBC 1102). 21. Show emergency lighting locations and method of power backup. IBC 1006 22. Label which restrooms are male vs. female. IBC Chapter 29 requires 2 male restrooms and 2 female restrooms for this building. Note on the plans. 23. Provide drinking fountain (standard height and adjacent accessible height) and provide detail. WAC 51-50 2903.4 24. How will this building be heated/cooled? Show location of mechanical equipment and provide structural calculations for supporting construction such as roof mounted equipment. Note fuel source (e.g. gas, electric, etc.). 25. Revise stair run on Sheet A6 to note 11" minimum (not max). 26. Revise bottom stair handrail extension to continue to slope downward (rather than tarn and run horizontally). IBC 1012.5 27. Safety glazing is required at the openings between the garage and offices. Depending on your answer to #10 above, these windows/doors may have to be fire rated, or may not be permitted. Also, be aware that wire glass is not permitted where safety glazing is required. 28. Provide a door schedule with size, type, rating, and hardware/locking information and cross reference to the plans. 29. Energy Compliance forms: For the architectural plans, at minimum the Envelope Summary form (see this website for forms http://www.neec.net/resources/resources.htmi) must be submitted showing insulation and glazing compliance. 30. Provide Exterior Lighting Summary form (only the 'interior form was submitted). The form can also be found on the website noted in the previous comment. 31. Provide energy compliance notes on the plans, including but not limited to: interior vapor retarder, air leakage (such as door weatherstripping, caulking, etc.), water piping insulation, duct insulation, etc. 32. Each restroom must have a minimum 50 cfm exhaust fan. Show on floor plans and note whether existing or proposed. 33. Note on the roof plan that a Class C roof is required. Page 3 of 4 34. Note on the plans that interior finishes must meet flame spread and smoke development requirements of IBC Chapter 8. 35. At the garage level clearly show the heated areas vs. unheated areas and provide details showing slab insulation and wall insulation requirements. Cross-reference on the floor and foundation plans. 36. Provide detail of slab -on -grade areas and show the underslab requirements noted in the geotech report. 37. Describe the use of the observation room on the 2nd floor. 3 8. Note what the existing shaft shown on the second floor plan is for. 39. On the floor and site plans, show that the floor of the garage will slope toward the garage entrance and catch basin. 40. Provide a deck construction detail, including finishes and guardrail construction. Guardrail must meet horizontal and top rail loads of IBC 1607.7. 41. Revise section detail on Sheet A6 to show specific foundation drainage requirements noted in the geotech report. 42. Provide construction details to show compliance with weather protection requirements of WAC/IBC 1443, 1404, 1405, 43. Provide a Fire Protection Footprint (example enclosed). 44. Provide a Statement of Special Inspections on the plans per IBC 1705, 45. General contractor to provide written/signed Contractor Responsibility statement to the City prior to permit issuance. 46. Special Inspections are required for this project: By the Geotechnical Engineer of Record a. Proof -rolling and general site preparation b. Soil bearing verification c. Placement of fill and compaction d. Foundation drainage installation e. General site monitoring during wet weather construction f, Final letter By the WABO Certified Special Ins ector s g. High-strength bolting (A325) h. Welding i. Epoxy anchor installation j. Structural wood: wood shearwalls, diaphragms, drag struts, braces, holdowns k. Final letter Complete the enclosed Special Inspection and Testing Agreement. Have all parties sign and return for City approval prior to permit issuance. 47. Dimension depth of footing on the foundation plan and details in accordance with the findings of the geotech report. The grading quantity of 22 cubic yards seems extremely low for this project, especially given the loose soils noted in the auger report. Provide grading calculations and note the cubic yards on the site plan. The Engineering Division may be commenting on this further. See attached structural comments from the City's consultant. Page 4 of 4 2006 International Mechanical Code 501.2 Exhaust Discharge. The air removed by every mechanical exhaust system shall be discharged outdoors at a point where it will not cause a nuisance and not less than the distances specified in Section 501.2.1. The air shall be discharged to a location from which it cannot again be readily drawn in by a ventilation system_ Air shall not be exhausted into an attic or crawlspace_ Exceptions: I _ Whole -house cooling attic fans shall be permitted to discharge into the attic space of dwelling units having private attics. 2_ Commercial cooking recirculating systetns_ 501.2.1 Location of Exhaust Outlet_ The termination point of exhaust outlets and ducts discharging to the outdoors shall be located with the following minimum distances: 1. For ducts conveying explosive or flammable vapors, fumes or dusts: 30 feet (9144 mm) from the property line_ 10 feet (3048 mm).from operable openings into the building; 6 feet (1829 mm) from exterior walls and roots_: 30 feet (9144 mm) from combustible walls and operable openings into the building which are in the direction of the exhaust discharge; 10 feet (3048 mm) above adjoining grade. 2. For other product -conveying outlets: 10 feet (3048 mm) from property lines: 3 feet (9I4 mm) from exterior walls and roofs; 10 feet (3048 mm) from operable openings into the building: 10 feet (3048 mm) above adjoining grade_ 3. For environmental air duct exhaust: 3 feet (914 mm) from property lines, 3 feet (914 mm) from operable openings into the building for all occupancies other that Group U_ and 10 feet (3048 mm) from a mechanical air intake. EXCEP'T'IONS: The separation between an air intake and exhaust outlet on a single listed package FIVAC unit. 2_ Exhaust from environmental air systems other than garages may be discharged into an open parking garage. 3. Except for Group I occupancies, where ventilation system design circumstances require building HVAC air to be relieved. such as during economizer operation, such air may be relieved into an open or enclosed parking garage within the same building. 4. For specific systems: For clothes dryer exhaust. see Section 504.4: for kitchen hoods, see Section 506.3; for dust. stock and refuse conveying systems, see Section 511.2: and for subslab soil exhaust systems. see Section 512.4. (insert Facing Page 33) Effective July 1, 2007 PERMIT # CITY OF EDMONDS SPECIAL INSPECTION AND TESTING AGREEMENT PROJECT SITE ADDRESS: PROJECT NAME: DATE: SPECIAL INSPECTION AGENCY *One form must be completed by each Special Inspection Agency or Inspector. SPECIAL INSPECTIONS REQUIRED: Special inspections are required for this project in accordance with IBC Chapter 17 or in accordance with IRC R109.2 as applicable.. IBC Section 17041 requires the owner or the registered design professional in charge to employ an independent testing/inspection agency/special inspector to perform required special inspections. The independent agency hired to perform the duties of special in is required to be a registered agency with WABO under the Special Inspection Registration Program (SIRP). The special inspector shall be a qualified person with competence for inspection of the particular type of construction or operation requiring special inspection (SOQ may be required by the Building Official). The owner, registered professional, contractor and special inspector/agency shall complete the attached form and submit directly to the Building Division. WORK REQURING SPECIAL INSPECTION: Special inspections will be required for the following categories of work in accordance with IBC Chapter 17 and IRC R109.2: FOR SPECIFIC INFORMATION REGARDING REQUIRED SPECIAL INSPECTIONS SEE THE STATEMENT OF SPECIAL INSPECTION ❑ATTACHED ❑APPROVED PLAN SHEET ❑ Fabrication (1704.2) ❑ Wood Construction (1704.6) o Steel Construction (1704.3) ❑ Soils (1704.7) ❑ Concrete (1704.4) o Bolts installed in Concrete (1704.13) o Special Moment Resisting Concrete Frames (1704A) ❑ Reinforcing Steel, Prestressing Steel Tendons (1704.4) ❑ Structural Welding (1704.3.1) o High Strength Bolting (1704.3.3) ❑ Masonry (1704.5) ❑ Reinforced Gypsum Concrete (1704.4) ❑ Structural Masonry for Seismic Resistance (1708.1) o Structural Observation (1709) o Insulating Concrete Fill (1704.4) ❑ Spray Applied Fire -Resistive Materials (1704.10) ❑ Piling, Drilled Piers, and Caissons (1704.8, 1704.9) ❑ Shotcrete (1704.4) o Pier Foundations (1707.5) ❑ Structural Steel (1707.2) ❑ Grading, Excavation, Fill, Proof Rollin (1704.7) ❑ Smoke -Control Systems (1704.14) ❑ Exterior Insulation and Finish Systems (1704.12) o Designated Seismic Systems (1707.9) o Mechanical Components (1707.8) o Cold Formed Steel Framing (1707.4) n Stora a Racks. (1707.6) ❑ Architectural Components (1707.7) ❑ Structural Wood (1707.3) o Special Cases (1704.I3) ❑ Seismic Isolation System (1707.10) ❑ o Mastic, Intumescent Fire Resistant Coatings (1704.11) ❑ ❑ High Load Diaphragms (1704.6. 1) ❑ .BEFORE A PERMIT CAN BE ISSUED: The owner and contractor and special inspector shall complete this agreement and the attached Special Inspection Information Form, including the required acknowledgements and return to the Building Division for approval prior to permit issuance. W:1BuildinglHANDOUT ICODESTORMSISPECIAL INSPECTION AGREEMENT FORM.doc7/07 APPROVAL OF SPECIAL INSPECTORS: Each special inspector shall be approved by the Building Official prior to performing any duties or inspections. The company performing inspections must be WABO certified as well as the individual completing inspections. When required by the Building Official, each special inspector shall submit Statement of Qualifications to the City for review. Special inspectors shall display identification when performing special inspections on the project site. Special inspection and testing shall meet the minimum requirements of IBC Chapter 17 and the following: A. Duties and Responsibilities of the Special Inspector 1. OBSERVE WORK The special inspector shall observe the site work for conformance with the approved (stamped) plans and specifications and applicable workmanship provisions of the IBC. Architect or Engineer reviewed shop drawings may be used only as an aid to inspection. Special inspections are to be performed on a continuous basis—meaning that the special inspector is on site at all times observing the work requiring special inspection. Periodic inspections are permitted only as specifically noted in the approved project plans in accordance with IBC Chapter 17, and as approved by the Building Official. Continuous Inspection means the same inspector is on site day to day to observe the work requiring special inspection. Periodic Inspection means some inspections may be performed on a periodic basis to satisfy the requirements of continuous inspection, provided these periodic inspections are performed as outlined in the project plans and specifications, and approved by the Building Official. 2. REPORT NONCONFORMING ITEMS The special inspector shall hring non -conforming items to the immediate attention of the contractor and note all such items in the daily field report. Any item not resolved in a timely manner shall be immediate cause of the special inspector to notify the Building Official by telephone at (425-771-0220) or in person at City Hall, of the plan deviation, error, change or omission. It shall also be the duty of the special inspector to promptly notify the engineer or architect of record. 3. DAILY REPORTS KEPT ON SITE WITH CONTRACTOR Each special inspector shall complete and sign a daily report for each day's inspections. The daily reports shall remain at the jobsite with the contractor for review by the City Building Inspector. 4. WEEKLY REPORTS TO CITY The special inspector or inspection agency shall furnish the City with weekly reports of tests and inspections. The project engineer or architect, and others as designated shall also be copied on reports. Weekly reports must include the following: • Description and date of daily inspections and tests made with applicable locations • List of all non -conforming items and locations • Report on status of non -conforming items (how each was resolved or unresolved) • Field changes authorized by the Architect, Engineer or City Inspector if not included in non-conformance items. W:1Bui1dinglI-1ANDOUT ICODESIFORMSISPECIAL INSPECTION AGREEMENT PORM.doc7/07 5. FINAL CONSTRUCTION REPORT The special inspector or inspection agency shall submit a final signed report or Certificate of Compliance to the City stating that all items requiring special inspection and testing were fulfilled and reported. And, to the best of his/hcr knowledge the project is in conformance with the approved plans and specifications, approved change orders and the applicable workmanship provisions of the IBC. Items not in conformance, unresolved items or any discrepancies in inspection coverage (i.e., missed inspections, periodic inspection when continuous inspections were required, etc.) shall be specifically addressed in this report. B. Contractor Responsibilities 1. NOTIFY THE SPECIAL INSPECTOR OF ALL REQUIRED SPECIAL INSPECTIONS It is the duty of the contractor to notify the special inspector when work is ready for special inspection. Note, the items listed on the attached Special Inspection Information Form and as noted on the approved plans and specifications are required to have special inspections. Adequate notice shall be provided by the contractor so that the special inspector has time to become familiar with the project. All work requiring special inspection must be approved prior to concealing or covering said work. 2. PROVIDE ACCESS TO APPROVED PLANS The contractor is responsible for providing the special inspector access to approved plans at the j obsite. 3. RETAIN SPECIAL INSPECTION RECORDS The contractor is responsible to retain at the jobsite all special inspection records submitted by the special inspector. These records are to be provided to the City building inspector upon request. C. City of Edmonds Building Division Responsibilities 1. APPROVE SPECIAL INSPECTION The Building Division shall approve all Special Inspectors and special inspection requirements. 2. MONITOR SPECIAL INSPECTIONS AND APPROVE WEEKLY REPORTS Work requiring special inspection and the performance of special inspectors shall be monitored by the City Building Inspector. Building Inspector approval must be obtained prior to placement of concrete or other similar activities in addition to that of the special inspector. 3. ISSUE CERTIFICATE OF OCCUPANCY The Building Official may issue a Certificate of Occupancy after all weekly special inspection reports including the final report have been submitted and accepted by the City. D. Owner Responsibilities 1. The project owner or the engineer or architect of record acting as the owner's agent shall fund special inspection services. E. Engineer or Architect of Record Responsibilities 1. Prepare Statement of Special Inspections in accordance with IBC Section 1705. 2. Review the special inspection reports and provide corrective action for work that may not conform to the approved plans. W:1Bui1dinglHAND0UT ICODESIFORMSISPECIAL INSPECTION AGREEMENT FORM.doc7/07 Owner name ACKNOWLEDGEMENTS 1 have read and agree to comply with the terms and conditions of this agreement (please print or type) Signature Date General Contractor Company/Owner name (please print or type) Signature Date Special Inspector/Agency name (please print or type) Signature. Architect/Engineer of Record name (please print or type) Signature. Return the original signed agreement to the Building Division City of Edmonds Building Division 1215 ffi Avenue North, City Hall Second Floor Edmonds, WA 98020 ACCEPTED BY CITY OF EDMONDS BUILDING DIVISION: Date Date City Official Signature Date Title: W:1BuildinglHANDOUT ICODESTORMSISPECIAL INSPECTION AGREEMENT FORM.doc7/07 SPECIAL INSPECTION AND TESTING SCHEDULE PROJECT NAME PROJECT ADDRESS REINFORCED CONCRETE, GUNITE, GROUT AND MORTOR: (-nnr_rPte (-'unitP (;milt Mnrtnr PRECAST/PRESTRESSED CONCRETE: Piles Pnst-Tens Pre -Tens r:laddina Aggregate Tests Reinforcing Tests Tendon Tests Mix Designs Reinforcing Placement Insert Placement Concrete Batching Concrete Placement Installation Inspection Cast Samples Pick-up Sam les Compression Tests MASONRY: Special Inspection Stresses Used Preliminary Acceptance Tests (Masonry Units, Wall Prisms) Subsequent Tests (Mortar, Grout, Field Wall Prisms) Placement Inspection of Units FOUNDATION WORK: Soil Bearing Verification Subsurface Drainage Installation Foundation Drainage Installation Temporary Erosion Control Installation BUILDING PERMIT NO. TESTING/INSPECTION AGENCY or SPECIAL INSPECTOR STRUCTURAL STEELfWELDING: Sample and Test (list specific members below) Shop Material Identification Welding Inspection ❑ Shop ❑ Field Ultrasonic Inspection ❑ Shop ❑ Field _ High -Strength Bolting ❑ Shop O Field Inspection ❑ A325 ❑N❑X❑F ❑ Aa90 Metal Deck Welding Reinforcing Steel Welding Inspection Metal Stud Welding Inspection Concrete Insert Welding Inspection FIREPROOFING: _ Placement Inspection _ Density Tests Thickness Tests Inspect Batching INSULATING CONCRETE: _ Sample and Test _ Placement inspection Unit Weights FILL MATERIAL: _ Acceptance Tests _ Placement Inspection _ Field Density (Compaction) _ Proof Rolling Final Site Grading STRUCTURAL WOOD: Shear Wall Nailing Inspection Inspection of Glu -lam Fab. _ Inspection of Truss Joist Fab. Sample and Test Components MISC: Final Geotechnical Report Winterization Measures W:18ui1dinglHANDOUT ICODESIFORMSISPECIAL INSPECTION AGREEMENT FORM.doc7/07 Aggregate Tests Reinforcing Tests Mix Designs Reinforcing Placement Batch Plant Inspection Inspect Placing Cast Samples Pick-up Samples Compression Tests PRECAST/PRESTRESSED CONCRETE: Piles Pnst-Tens Pre -Tens r:laddina Aggregate Tests Reinforcing Tests Tendon Tests Mix Designs Reinforcing Placement Insert Placement Concrete Batching Concrete Placement Installation Inspection Cast Samples Pick-up Sam les Compression Tests MASONRY: Special Inspection Stresses Used Preliminary Acceptance Tests (Masonry Units, Wall Prisms) Subsequent Tests (Mortar, Grout, Field Wall Prisms) Placement Inspection of Units FOUNDATION WORK: Soil Bearing Verification Subsurface Drainage Installation Foundation Drainage Installation Temporary Erosion Control Installation BUILDING PERMIT NO. TESTING/INSPECTION AGENCY or SPECIAL INSPECTOR STRUCTURAL STEELfWELDING: Sample and Test (list specific members below) Shop Material Identification Welding Inspection ❑ Shop ❑ Field Ultrasonic Inspection ❑ Shop ❑ Field _ High -Strength Bolting ❑ Shop O Field Inspection ❑ A325 ❑N❑X❑F ❑ Aa90 Metal Deck Welding Reinforcing Steel Welding Inspection Metal Stud Welding Inspection Concrete Insert Welding Inspection FIREPROOFING: _ Placement Inspection _ Density Tests Thickness Tests Inspect Batching INSULATING CONCRETE: _ Sample and Test _ Placement inspection Unit Weights FILL MATERIAL: _ Acceptance Tests _ Placement Inspection _ Field Density (Compaction) _ Proof Rolling Final Site Grading STRUCTURAL WOOD: Shear Wall Nailing Inspection Inspection of Glu -lam Fab. _ Inspection of Truss Joist Fab. Sample and Test Components MISC: Final Geotechnical Report Winterization Measures W:18ui1dinglHANDOUT ICODESIFORMSISPECIAL INSPECTION AGREEMENT FORM.doc7/07 Additional Instructions on Other Tests and Inspections: W:1BuildinglHANDOUT ICODESIFORMSISPECIAL INSPECTION AGREEMENT FORM.doc7/07 Edmonds Plaza LEGEND 1500 Main Street • 1 how 0:wrdor%vithself- slccupancles: R2, A2, B, M "Type A ' ? < dosing, rated doors, rated of Construction: VA Unit ;�: Dv:elling Unit glazing, firs(arrr4ke dampers at s. stories with basement A duct punatranws Total Building Area. 32,456 sf " 20433 IBC, IMC, IFGC, IFC, UPC, WSEC, VIAQ A 1 hour rateclwaklassemhly Fire Apparatus Access: Paved West, South and East Sides Du'eEling Unit Dvtelling Unit 2 hwT Area Separation 1°dali - with rated doom and gla2lng Active Fire Protgetign Dvading Unit ` ding the exterior of tiro building of the Fire sprinkler system (specify NFPA-13 or NFPA 13-R) • V a Dvtelling Unit ® Area of Evacuation Assistance Fire Department connections a Fire alarm system wl smoke detection and manual pulls A 6A6 Fire Department connectors Fire alarm control panel location Retail Retail Retail d 20 rr>in. rated, self -dosing door Illuminated exit signs Stnraga Emergency lighting wl battery hack -up a A A a e^ O e 60 rrn. rated, set(-ciasing door HVAC automatic shutdown ► - Type Kitchen Tpe I hood and suppression system n A a Q 30 rr�n. raced, 5Blf-Ca451ng door Fire Extinguishers ► Eiev GM Gas Meter Restaurant Lob Dv:ellirg Unit Elev t t .i Electric MetrrrlPana€ Roof Access Hatch d`�sive Fire Protection E e a A ' PIV Past Indicaiing Valve �t rilce controls stem y Office Erveelling Unit ape windows from sleeping rooms #liar rated corridorlexit passageway A .i1c draft stops a t ikatorsmoke door Office a r`. - Dv:elling Unit r A `�• +structural Protection Qifux: Exterior load-bearing walls = 1 -hour Interior load -hearing walls = I •hour l iv ening Unit Exterior non -hearing walls = 1 -hour Structural frame = 1 -hour Officea CA Sample Fire Permanent partitions ='[-hour � des? e Shaft enctosures = 1 -flour Floor -ceiling = 141 our eclaanical A =Y R t]v:elling Unit Protection Roof -ceiling = 1 -hour Exterior openings = NIA due to location on property Footprint Stair enclosure =1-hourfla Roof material class = Type B N Please e-mail Fire Protection Footprint r_P _IV_ Date Prepared for each floor to sMithM@Ci.edmonds.wa.us in .pdf, .jpg or .tif format. Last updated ,i,y,;TernptBuiidiN'tHandoutiCoder_l;cotpnnt.vsd .ilx. Eagle Eye Consulting Engineers, P.S. PO Box 523 Olalla, WA 98359 hoytjeter@centurytel.net 360 874 0562 Fax 360 874 0591 To: Theresa Umbaugh 1215' Ave N Edmonds, WA 98020 Re: Jantz Addition 547 Dayton St Edmonds, WA 98020 Plan Review #2008-0287 Plan review number 0 EECE # EDM 08-35 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the Structural only requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. First Floor S2 3324 Second Floor B 2993 Total 6317 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the Structural only requirements of this project. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. Page 2of5 Plan Review Number 01 EECE#: EDM 08-35 Jantz Addition 2008-0287 STRUCTURAL COMMENTS General 1. Engineer of record (EOR), please submit diaphragm horizontal analysis as required per ASCE 12.10. 2. Office buildings are required to be designed for partition loads. The minimum load to be used shall not be less than 15 lbs. per square foot. It appears the analysis did not account for this, please modify accordingly. 3. It appears the minimum live load required for the corridor has not been used. The live load is required to be 80 lbs. per square foot for corridors above the first floor. Please modify the analysis and drawings accordingly. ASCE table 4-1 4. EOR, please justify a dead load of 12 lbs per square foot used in the design. Please note that suspended ceiling are being provided. 5. EOR, please submit design analysis for foundation system. Sheet Al Site Plan No comments for this sheet at this time. Sheet A4 Existing Elevations No comments for this sheet at this time. Sheet A5 Elevations 6. Please provide deck rail details in order to support the code -required forces. This sheet states see rail sheet A-7 but there is no details for this sheet. 7. Please provide analysis and details for the new parapet being installed. It is not clear how this is going to resist the out of plain forces. All that is noted is to match existing. ASCE 6.4.1.2, ASCE 6.5.11.5, Sheet A2 First Floor Plan No comments for this sheet at this time Sheet A3 2',d Floor Plan 8. The new computer room is required to be designed for a live load of 100 psf. ASCE table 4-1 Page 3 of 5 Plan Review Number 01 EECE#: EDM 08-35 Jantz Addition 2008-0287 Sheet A6 Typical Wall Section/ Stair Details 9. Please provide analysis for the required connection for the stair stringer. Nothing is provided at this time in order to complete the review. All that is shown is schematically what is to be built. Sheet A7 Details No comment at this time. Sheet A8 Reflected Ceiling Plan No comment at this time. Sheet A9 Foundation & 2'6 Floor Framing Plan 10. EOR, please correct the references to the correct sheet. Sheet A5 does not have any details drawn; I believe the intent was sheet A11. 11. ITT hangers 416 appear not to be approved to be non -backed, which is the case when being hung off beam B4. Please modify the hanger accordingly. Simpson Hanger option Matrix. 12. Please specify the required connection of the 5 1/8 and 16 1/2 glu lam to the wl6x89 steel beam. 13. Please specify the required support and connection of beam mark 12 to the wood wall. 14. Please provide details and analysis for the deck connections, nothing is specified at this time. 15. With different depth wide flanged beams intersecting a P6 column, a detail is required at this location. The detail reference 2-A5 assumed to be Al I has not been addressed. 16. Please specify the required collector element for the interior shear walls marked SW2 and SW4. 17. EOR, please submit analysis for w 18x86 the design analysis submitted was for wl8x97, please modify accordingly. 18. Please submit design for the w16x89. "Beam mark 134A", the analysis submitted is not correct for this beam. For example, the span will not exceed 24'. Page 4 of 5 Plan Review Number 01 EECE#: EDM 08-35 Jantz Addition 2008-0287 Sheet A10 Roof Framing Plan 19. Please specify the required posts and connection for beam 9 at the exterior wall. 20. A detail is required for the support of beam mark B9 and B10. These beams have different depths and detail analysis is required for the support of these members. Sheet Al I Details 21. Detail 10: Please note a 90 -degree hook acquired for the vertical bars into the footing. 22. Detail 10: Please specify the required distance the footing shall extend below grade as required for the geotechnical report. Sheet Al2 Structural Notes 23. Please correct the bottom part of the general structural notes; part of this has been erased. 24. Code requires single 3x inch nominal or wider member when nail spacing is 2 inches on center. Please modify schedule accordingly. 25. Shear wall mark 4: please note the shear wall nail at 2 inches on center shall have the nail spacing staggered on all cases. Please modify accordingly. 26. Please note on the drawings the required floor and roof loads. IBC 1603.1 Item 1 27. Please note on the drawings the required ground snow load. IBC 1603.1 Item 2 28. Please add to the drawings the required flat roof snow load, snow exposure factor, snow load importance factor and thermal factor. IBC 1603.1.3 29. Please add to the drawings the applicable wind design internal pressure co- efficient. IBC 1603.1.4 Item 4 30. Please add to the drawing the sight spectral response coefficient SDI. IBC 1603.1.5 Item 4 31. Please note on the drawings the basic seismic force resisting system. IBC 1603.1.5 Item 6 32. Please specify on the drawings the design base shear. IBC 1603.1.5 Item 7 Page 5 of 5 Plan Review Number 01 EECE#: EDM 08-35 Jantz Addition 2008-0287 33. Please specify on the drawings the seismic response coefficient CS. IBC 1603.1.5 Item 8 34. Please specify on the drawings the response modification factor, R. IBC 1603.1.5 Item 9 35. Please specify on the drawing the seismic analysis procedure used. IBC 1603.1.5 Item 10 36. Please specify on the drawings the applicable internal pressure coefficient for the wind design data. IBC 1603.1.4 Item 4 Additional corrections may be required following receipt of corrections and additional information as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874- 0562 between 8:00 a.m. and 5:00 p.m. LO Hoyt Jeter, P.E. President Umbaugh, Theresa From: Hoyt Jeter [hoytjeter@centurytel.net] Sent: Wednesday, April 23, 2008 1:42 PM To: Umbaugh, Theresa Cc: Harrison, Marie Subject: RE: Jantz BLD2008-0287 (EDM08-35) Here are the comments for this one. The engineer who designed this I think has not design office building before. Many basic items were not done. Nevertheless, here are the comments. Let me know if you have any questions. (Also could send me the cost of construction to use for this remodel.)Thanks. -----Original Message ----- From: Umbaugh, Theresa [mailto:Umbaugh@ci.edmonds.wa.us] Sent: Wednesday, April 23, 2008 11:44 AM To: hoytjeter@centurytel.net Subject: Jantz BLD2008-0287 Hello Hoyt, Just checking to make sure that we'll get comments today? Or, let me know your time -frame. Thanks, T Theresa M. Umbaugh S:jriior .Permit Coordinator Developineni Serviees .Dep ar•trrrent Fitt qf'Ldrt onds Fours .44. T Th, F, 8.00ai r to 4: 30pin 1Y'eciru>>rrla,-E" used 4/23/2008