PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: April 24, 2009
TO: All Climate Heating & Air Conditioning
comfort@allclimate.net
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2009-0200
Project: Old Milltown Gas Piping
th
Project Address: 201 5 Ave S.
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to Theresa Umbaugh, Senior Permit
Coordinator. Thank you.
1.Please provide pipe sizing calculations for the entire system.
2.Please include piping to RTU 14 and RTU 15 as they are included in the mechanical
permit for the building.
3.Please indicate on the plans where the gas meters are located, and how many meters
there are. (This may be accomplished as a redline on the existing plans if it is a simple
description.)