20081230073327.pdfEagle Eye Consulting Engineers, P.S.
PO Box 523
Olalla, WA 98359
hoytjeter@centurytel.net
360 874 0562
Fax 360 874 0591
To: RPI Fire Protection
29330 1241' Ave NE
Arlington, WA 98223
Re: Sunset 121 Condominiums
121 Sunset Avenue
Edmonds, WA
Plan Review # 2008-1000
RECEIVED
D E C 2 63 2008
BUILDING DEPT,
EECE # EDM 08-93
The above referenced project is in the process of plan review for compliance with
Edmonds ordinances and applicable codes (Fire Suppression only). The following
comments, deficiencies/corrections must be addressed prior to completion of plans review
and subsequent issuance of permits.
Provide revised plans and calculations along with a written response to each of the items
listed below to facilitate a shorter back -check time.
SCOPE OF REVIEW
The scope of this review is for Fire Suppression requirements of this project.
All features were checked only to the extent allowed by the submittals provided. All
portions of this project are assumed to meet or will meet other departmental requirements,
conditions and concerns before permit approval.
FIRE SUPPRESSION COMENTS
'01--+ UD 1
1. On the riser diagram, please show an automatic drip valve on the fire department
connection line. NFPA 13, 8.17.2.6
2. Please show and provide a sidewall sprinkler at the bottom of each elevator shaft.
NFPA 13, 8.15.5.1
3. Please show seismic bracing on the plans. NFPA 13, 9.3.
Page 2 of 2
EECE EDM08-93
Sunset 121 Condos 2008-1000
Sheet FP -2
4. Please show seismic bracing on the plans. NFPA 1.3, 9.3.
Additional corrections may be required following receipt of corrections and additional
information as requested.
Your plans are being reviewed concurrently with the Building Department, Fire
Department, Zoning Department and Public Works Engineering. Changes, clarifications
or additional corrections may be required subsequent to the Building Department plan
review when comments are received from the other concerned departments.
Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (360) 874-
0562 between 8:00 a.m. and 5:00 p.m.
C
Hoyt Jeter, P.E.
President