Loading...
2009-0005 Kruger Clinic canopy.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: January 21, 2009 TO: Gina Dais TGB Architects th 21911 76 Ave. W. #210 gdais@tgbarchitects.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2009-0005 Project: Kruger Clinic Canopy Project Address: 21600 Highway 99 During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. Thank you. 1.The drawings do not contain adequate details to perform a complete structural review of the canopy. Please include details on the drawings for steel column top and bottom attachments, show what portions of the footings, base plates and columns are to be reused, and show the structural attachments of the roof frame. If the roof system is to be independently manufactured, please provide the stamped engineered specifications for this system from the manufacturer. I assume this is what the PSM Engineering packet refers to as a “secondary structural system.” This should also include calculations for the laminated glass panels. 2.Please provide the structural engineer’s wet stamp on each drawing on which their associated details appear. 3.Indicate on the plans that all welding shall be performed by a WABO certified welder. 4.Several detail callouts refer to sheet A2.01, however this sheet was not provided. Please change the callouts to refer to the correct sheet.