2009-0084 MKG Revision.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: March 16, 2009 TO: Kim Gardner kmgard@aol.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2009-0084 Project: MKG Martial Arts Revision th Project Address: 111 4 Ave. N. During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to Marie Harrison, Senior Permit Coordinator. Thank you. 1.Please show the door hardware and access-control system for the restroom doors to show compliance with IBC 2902.2.2 that states “Access to toilets serving multiple tenants shall be through a common use area and not through an area controlled by the tenant.” The building code addresses the importance of one tenant not having control over (and in this case not being able to lock the other tenant out of) the toilet room. 2.The minimum clear width required at the water closet is 60 inches from the side wall to the nearest fixture. Please show this dimension from the side wall to the lav. ANSI A117.1 section 604.3. 3.Verify whether the wall between the tenant spaces is a one hour wall. If so, please indicate this on the plans. Please note that the building code allows the use of the unisex toilet room for occupant loads of up to 15 (as calculated by IBC Chapter 29). When both tenant spaces have access to the facility, the occupant load is figured at 19; therefore the presence of the existing restroom in the retail space is necessary to provide an adequate fixture count for the combined space.