Loading...
20090112081640.pdfOV 8D 0 City of Edmonds .6 PLAN REVIEW COMMENTS "`'' BUILDING DIVISION �St 1890 (425) 771-0220 DATE: 1-9-2009 TO: Mr and Mrs Kenneth Weyant FROM: Pat Lawler RE: Plan Check: BLD20090008 Project: Addition Project Address: 1233 7"' Ave. S During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. 1. Provide the lateral calculations that are the basis for the engineered shear -wall table and details. 2. Provide engineered gravity calculations for the built-up beam. 3. Provide engineered gravity calculations for footing at 6x6 post location. 4. Call out hardware for post and beam, built-up beam to beam, and joist connections at the addition. 5. Call out post size, .species and grade at built up beam location. 6. Provide floor system, membrane specs, and flashing details at the mini -balcony. 7. Provide guard details at the same location. 8. It is not clear whether the HD5A holdowns at the existing garage wall are existing or will be retrofitted. If they are to be retrofitted, have the EOR spec out the bolting and epoxy requirements. Pat Lawler Plans Examiner 425 7710220 x1703