2009-0237 Sub Shop #3.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: June 11, 2009
TO: Ted Clark
th
719 13 Way SW
Edmonds, WA 98020
Subshops@mac.com
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2009-0237 Review #3
Project: Sub Shop
Project Address: 650 Edmonds Way
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can
be found on the plans, and submit revised plans/documents to Theresa Umbaugh, Senior Permit
Coordinator. Thank you.
1.Original item #8:
Show on the plans that the rear exit leads directly to a public way. If
This item has
there is a gate in the exit path, it must have panic hardware. IBC 1008.2.
not been addressed. Further, what is the use of the space outside the rear exit? If it is to
be outdoor seating for dining, please show this on the plans.
2.Original item #10:
Please fill out completely the (attached) Commercial Kitchen Hood
We have received the completed worksheet, however the information (model
Worksheet.
number, etc.) must be coordinated with information on the Mechanical Summary form
and the Equipment list on sheet KC-1, as well as with the Captivaire specs provided.
3.Previous item #6.
A specification packet has been received for a 3 ton heating/cooling
unit, however this unit does not appear on the plans or in the Mechanical Summary
form. Please show the location of the unit and any ductwork on the plans and provide
the appropriate information in the Mechanical Summary form. Also, if the unit is to be
mounted on the roof, structural engineering will be required to show the roof structure
can support the weight. If the unit weighs more than 400 pounds, engineering
calculations will be required for the design of seismic attachments for unit to curb and
This
curb to roof. Please indicate the size and location of the gas line to this unit also.
item has not yet been addressed.
4.Original item #14:
Indicate backflow prevention devices where required on plumbing
. Please indicate either an air gap or RPBA on the supply line for the ice maker.
fixtures
5.Original item #15:
Please provide a copy of the approval letter from Snohomish Health
. This is a requirement prior to issuing the building permit.
District
6.Original item #16:
Show existing (or proposed) accessible parking spaces (one is
required), show accessible signage and the travel route from the accessible spaces to the
building entry. If the travel route includes a raised front walk, show a code compliant
curb ramp. Please show these elements clearly on the site plan:
a.Location and dimensions of accessible parking stall including adjacent
disembarkment zone. ANSI A117.1 Section 502
b.Signage for the accessible stall. ANSI A117.1 Section 502
c.Details for a code compliant ramp including the slope, width, and handrails.
(Handrails are required on both sides of ramps where the rise exceeds 6 inches
and the slope is greater than 1 in 20. The maximum slope allowed is 1 in 12.)
IBC 1010.
A new and accurate site plan will be required to show this information.
The above are comments generated from the third review by the Building Division. Please be aware
that subsequent reviews for this permit will be charged a flat fee of $170 for each review.
Page 2 of 2