2009-0519 Modern Nails.pdf
City of Edmonds
PLAN REVIEW COMMENTS
BUILDING DIVISION
(425) 771-0220
DATE: August 19, 2009
TO: Evergreen Construction
evergreenbellevue@yahoo.com
FROM: Leif Bjorback, Assistant Building Official
RE: Plan Check: 2009-0519
Project: Modern Nails TI
Project Address: 23632 Highway 99 #S
During review of the plans for the above noted project, it was found that the following information,
clarifications or changes are needed. Please provide written responses as to where the changes can be found
on the plans, and submit revised plans/documents to Theresa Umbaugh, Senior Permit Coordinator. Thank
you.
1.Please complete and submit the Interior Lighting Summary form as found online at
www.neec.net/resources/resources.html.
2.Engineer of Record, please stamp and sign sheets A-1.1 and G-1.0.
3.Please verify the actual square footage of the tenant space. The dimensions provided do not agree
with the figure of 990 square feet as on sheet G-1.0, nor do they agree with existing City records that
show 1180 square feet. Modify the occupant load calculations if needed.
4.The reception desk must be accessible. Please indicate on the plans how it will meet the provisions
of section 904.3 of ANSI A117.1 with a maximum height of 36 for a minimum length of 30.
5.The alterations require accessibility upgrades to the existing space per WAC 51.50 (IBC 3409.7).
On the plans clearly show that the entire exterior and interior accessible route of travel complies
with current code, or provide upgrades per the previously referenced section. Specifically, one
recent code change requires a vertical grab bar on the wall adjacent to the toilet per ANSI A117.1
section 604.5.1. Please show this grab bar and any other upgrades on the plans.
6.Please show the locations of the ceiling supply and exhaust grilles in plan view, in proximity to each
other and to the work stations.
7.Please show by analysis that the exhaust system proposed is not negatively affected by, nor
negatively affects, the HVAC system for the entire space.
8.Show how ventilation air is provided to the Office room. IMC 401.2