2009-0530 Harbor Square Revision #3-2.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: February 3, 2012 TO: Warren LaFon 849 Puget Way Edmonds, WA 98020 FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2009-0530 nd Project: Harbor Square Athletic Club Revision #3, 2 review Project Address: 160 West Dayton During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a Permit Coordinator. Thank you. 1.The toilet room that has been relocated next to the gym door must be accessible, as it does not meet any of the code exceptions for accessibility. This includes fixture clearances, door clearances, grab bars, etc. IBC 1109.2 Your response to this item included swing up bars, but these are only allowed in limited residential applications. Please adjust the plans to show: a.Minimum 18 inch clearance on the latch edge of the door, on the inside of the restroom. ANSI A117.1 section 404.2.3 b.Minimum 60 inch width clearance at the toilet from the wall to the sink. ANSI A117.1 section 604.3 c.Provide grab bars (side, rear and vertical) per ANSI A117.1 section 604.5. 2.Please indicate fire retardant treated woodor steel framing in the exterior wall portion of detail 13/A-5A. Untreated wood framing is not permitted in exterior walls of Type 3A construction. Please note the plywood sheathing in the detail is fire retardant treated. 3.Complete 4.Complete 1.