201 Main St pre App.DOC
EDMONDS FIRE DEPARTMENT
MEMORANDUM
Date: June 3, 2010
To: File
From: Mike Smith Fire Inspector 425-775-7720
Subject: Pre App 201 Main St Doug Spee
The Fire Department has the following comments:
1) Fire Sprinkler (throughout) and Fire Alarm with off site monitoring required.
2) Height of building requires a Class I Standpipe to be installed in stairwells up to and
including the roof.
3) A stretcher size Elevator Car is required (based on 4 story building height).
4) Life Safety Plan and Fire Protection footprint required (handouts available).
5) Fire Hydrant spacing appears OK per City Standard. An additional hydrant may be
nd
required on 2 Ave N located midway between Main and Bell Streets.
6) Fire Line Connection Permit required. Please call my office for more details.
7) During construction the building owner shall designate a Fire Prevention
Superintendent. Contact my office for details.
8) FD Lockbox required for Emergency Access. Contact my office for details.